Laserfiche WebLink
UNDERGROUND STORAGE TANK <br /> OVERFILL PREVENTION EQUIPMENT INSPECTION REPORT FORM (Page 1 of 1) <br /> Foff ❑ Installation Inspection ❑Repair Inspection ❑x 36 Month Inspection <br /> 1. FACILITY INFORMATION <br /> CERS ID Date of Overfill Prevention Equipment Inspection <br /> 10151579 2/8/2019 <br /> Business Name(Same as Facilily Name or DBA-Doing Business As) <br /> Tracy USD Service Center <br /> Business Site Address City ZIP Code <br /> 1975 W. Lowell Ave Tracy 95376 <br /> II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION <br /> Name of UST Service Technician Performing the Inspection(Print as shown on the ICC Certification.) Phone# <br /> Andrew Bagley 1 (209) 367-4800 <br /> Contractor/Tank Tester License# ICC Certification# ICC Certification Expiration Date <br /> 774802 8012449 12/24/2020 <br /> Overfill Prevention Equipment Inspection Training and Certifications(List applicable certfRcations.) �� <br /> OPW. Emco-Wheaton � ._. ,, <br /> CRV5D Ill. OVERFILL PREVENTION EQUIPMENT INSPECTION INFORMATION <br /> Inspection Method ❑Manufacturer Guidelines(Specify): <br /> Used: <br /> ❑x Industry Code or Engineering Standard(Specify):PEI/RP 1200-17 ENVIRONMENTAL HEALTH <br /> ❑Engineered Method(Specify): DEPARTMENT <br /> Attach the inspection procedures and all documentation required to determine the results. #of Attached Pages <br /> TANK ID:(By tank number,stored product,etc.) 252102/87/1 OK <br /> What is the tank inside diameter?(Inches) Cis r <br /> Is the fill piping secondarily contained? E Yes ❑No ❑Yes ❑No ❑Yes ❑No ❑Yes ❑No <br /> Is the vent piping secondarily contained? 0 Yes ❑No ❑Yes ❑No ❑Yes ❑No ❑Yes ❑No <br /> Overfill Prevention Equipment Manufacturer(s) 0 1°W <br /> What is the overfill prevention equipment response ❑x Shuts Off Flow ❑Shuts Off Flow ❑Shuts Off Flow ❑Shuts Off Flow <br /> when activated? <br /> (Check all that apply.) ❑Restricts Flow ❑Restricts Flow ❑Restricts Flow ❑Restricts Flow <br /> ❑AN Alarm ❑AIV Alarm ❑A/V Alarm ❑A/V Alarm <br /> Are flow restrictors Installed on vent piping? ❑Yes ❑x No ❑Yes ❑No ❑Yes ❑No ❑Yes ❑No <br /> At what level in the tank is the overfill prevention set <br /> to activate?(Inches from bottom of tank.) 8511 <br /> What is the percent capacity of the tank at which the <br /> overfill prevention equipment activates? 93.6% <br /> Is the overfill prevention in proper operating condition ❑x Yes ❑Yes ❑Yes ❑Yes <br /> to respond when the substance reaches the <br /> appropriate level? ❑No(Specify in V.) ❑No(Specify in V.) ❑No(Specify in V.) ❑No(Specify in V.) <br /> IV. SUMMARY OF INSPECTION RESULTS <br /> Overfill Prevention Inspection Results [xl Pess ❑Fail I []Pass ❑Fail I ❑Pass ❑Fail ❑Pa.ss ❑Fill <br /> V. COMMENTS <br /> Any items marked Fail"must be explained in this section. Any additional comments may also be provided here. <br /> This is a re-inspection.The valve was originally inspected on 10/1212018, however, the valve/tube was rusted and could <br /> not be removed for inpection and was subsequently noted as a"FAIL".A re-attempt to remove the valve for inspection <br /> and testing on 02/08/2019 was successful.The valve will shut-off flow at 93.6%of tank capacity and is considered a" <br /> PASS". <br /> Vi. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS INSPECTION <br /> I hereby certify that the overfill prevention equipment was inspected In accordance with California Code of Regulations,Title 23, <br /> Division 3,Chapter 16,Section 2637.2 and all th9onformation contained herein is accurate. <br /> UST Service Technician Signature "i <br /> If the facility has more components than this forrdoccomrqbdates,add !es of this page may be attached. <br /> CERS=Caf(orrra Environmental Reporting System,ID=Identification,UST=Underground SbmW Tank,ICC=InWnational Code Council,AN=Audible and Visual <br />