Laserfiche WebLink
SAN J O A R N Environmental Health Department <br /> -:a U ;� i _# �V AMENDED <br /> 6/25/2020 <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> Regional Transportation Center 2849 E Myrtle St, Stockton September 25, 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 304 HSC 25290.1(d)Monitoring system not maintained to detect entry into secondary containment(after Jul 2004). <br /> OBSERVATION: The diesel vacuum sensor is not functional at the time of inspection. <br /> REGULATION GUIDANCE: The continuous monitoring system shall be maintained to detect the entry of the liquid <br /> or vapor phase of the hazardous substance stored in the primary containment into the secondary containment, and <br /> to detect water intrusion into the secondary containment. <br /> CORRECTIVE ACTION: Correct immediately by having a properly licensed,trained, and certified contractor replace <br /> the failed component with a functional component(LG 113-x listed, if applicable), and obtain a permit within one <br /> business day from the EHD, if needed. If the failed component can't be replaced immediately,there is a possibility <br /> that the [GRADE] UST system may be red tagged to prevent fuel inputs. <br /> This is a minor violation. <br /> 305 HSC 25290.1(e)VPH monitoring of the interstitial spaces of the UST system is not maintained. <br /> OBSERVATION: The diesel vacuum sensor is not functional at the time of inspection. <br /> REGULATION GUIDANCE: The interstitial space of the UST shall be maintained, as designed, under constant <br /> vacuum or pressure such that a breach in the primary or secondary containment is detected before the hazardous <br /> substance is released into the environment. <br /> CORRECTIVE ACTION: Correct immediately by having a properly licensed,trained, and certified contractor replace <br /> the failed component with a functional component(LG 113-x listed, if applicable), and obtain a permit within one <br /> business day from the EHD, if needed. If the failed component can't be replaced immediately,there is a possibility <br /> that the [GRADE] UST system may be red tagged to prevent fuel inputs. <br /> This is a repeat violation, Class II. <br /> 313 HSC 25290.1,25290.2, 25291 Failure to construct, operate, and maintain primary containment as product-tight. <br /> OBSERVATION: Diesel piping is leaking, indicating a leak in the primary containment. <br /> REGULATION GUIDANCE:All primary containment for the UST system must be product tight. <br /> CORRECTIVE ACTION: Immediately have a properly licensed,trained, and certified contractor repair or replace the <br /> failed component(s), under permit and inspection of the EHD if necessary. <br /> This is a minor violation. <br /> FA0022301 PR0538822 SCO01 09/25/2019 <br /> EHD 23-01 Rev.9/20/2019 Page 6 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />