ROOFTOP HVAC UNITS (GAS HEAT) <br /> UNIT ZONE/AREA MANUFACTURER NOMINAL OUTSIDE AIR (OA) ESP COOLING CAPACITY @ DESIGN CONDITIONS HEATING CAPACITY ® DESIGN CONDITIONS ELECTRICAL E.E.R MAX. UNIT UNIT HEIGHT REMARKS Architecture / Development <br /> NO. SERVED & MODEL NO. TONNAGE CFM CFM (INCH) SENSIBLE (NET) TOTAL (NET) INPUT OUTPUT %EFF. VOLT/PH/HZ M.C.A MOCP (@ ARI CONDITIONS) WEIGHT (LBS) WITH CURB (INCHES) 14901 Quorum Drive <br /> KBTU H KBTU H Suite 300 <br /> aAC <br /> DINING CARRIER 7.5 3000 1000 1.0 70.1 88.2 180.0 120.0 80 208/3/60 39.0 50 12.0 925 51.25 1,2,4-7.9-16 Dallas Texas 75254 <br /> 1 48HCO8 Ph: (972)239-8884 <br /> Fax: (972)239-5054 <br /> AC DINING CARRIER 7.5 3000 1000 1.0 70.1 88.2 180.0 120.0 80 208/3/60 39.0 50 12.0 925 51.25 1,2,4-7.9-16 <br /> 2 48HC08 ISSUE RECORD <br /> DATE DESCRIPTION <br /> AC KITCHEN CARRIER 15.0 6000 2000 1.0 134.9 173.9 220.0 178.0 80 208/3/60 69.2 90 12.0 1892 65.37 1,2,4-7.9-18 URBAN PROTOTYPE DESIGN <br /> 3 48HC17 <br /> 10-22-2018 ISSUED FOR PERMIT <br /> REMARKS <br /> NOTES 1. NEW MFG MODEL UNIT W/R410A REFRIGERANT. 12. BAROMETRIC RELIEF DAMPER W/POWERED EXHAUST <br /> 2. 14" ROOF CURB 13. MERV 8 FILTERS <br /> 1• UNITS SELECTED AT DESIGN INDOOR CONDITIONS OF 75°F, 50% RH AND OUTDOOR CONDITIONS OF 100°F DB/ 69°F WB AMBIENT. 3. HAIL GUARDS 14. MOTORIZED OUTSIDE AIR DAMPER (CLOSE UPON UNIT DEACTIVATION) <br /> *ESP MEASUREMENT DOES NOT INCLUDE ECONOMIZER, HUMIDIMIZER ®, OR POWERED EXHAUST PRESSURE DROPS. 4. FACTORY INSTALLED DISCONNECT SWITCH. 15. S/A DUCT SMOKE DETECTOR (SHALL BE UL 268A COMPLIANT AND INSTALLED PER NFPA 96). ACTUATION <br /> 5. UNIT MOUNTED RECEPTACLE (NON-WIRED) SHALL ACTIVATE VISIBLE AND AUDIBLE ALARM AT AN APPROVED LOCATION, IDENTIFIED AS AIR DUCT DETECTOR <br /> 6. PREMIUM EFFICIENCY MOTORS TROUBLE OR CONNECTED TO THE BUILDING FIRE ALARM SYSTEM (IF AVAILABLE). PROVIDE WITH REMOTE <br /> 7. 7-DAY PROGRAMMABLE INTERFACE WITH 57 HEATING-COOLING DEAD-BAND AND SET-BACK CAPABILITY. TEST/RESET STATION WITH LED INDICATOR. <br /> 8. HUMIDITY CONTROL (HOT GAS REHEAT) 16. ALL UNITS SHALL SHUT DOWN UPON DETECTION OF ANY SMOKE IN THE SUPPLY AIR DUCT. REFERENCE FAN <br /> 9. REMOTE, NON-ADJUSTABLE, TEMPERATURE AND HUMIDITY (HUMIDITY CONTROL/HOT GAS REHEAT OPTION CONTROL SCHEMATIC ON SHEET E8.0 <br /> ONLY) SENSORS. HUMIDITY SENSORS ARE DUCT MOUNTED AND TO BE CARRIER J10-809-336. 17. GAS FLUE DEFLECTOR REVISION RECORD <br /> 10. DISCHARGE AIR TEMPERATURE CONTROL 18. AC-3 SHALL BE AUTOMATICALLY ACTIVATED WHEN THE KITCHEN EXHAUST FANS ARE INITIATED. <br /> 11. 100% ECONOMIZER-X W/ ENTHALPY CONTROL (HIGH LIMIT: Hon > 28 BTU/LB) <br /> EXHAUST FANS AIR BALANCE <br /> SOURCE <br /> UNIT MANUFACTURER ZONE/AREA LOCATION TYPE AIRFLOW ESP SPEED ELECTRICAL OPER. WT. REMARKS EA OA SA RA <br /> NO. & MODEL NO. SERVED (CFM) (INCH) (RPM) VOLTS/PH/HZ HP (LBS) EF-1 RR/KITCHEN 550 -- -- -- PROFESSI NAL SEAL <br /> EF COOK 100ACRUB ROOF RESTROOMS & CENTRIFUGAL 550 .5 1977 120/1/60 1/4 82 2,3,4,5,9,11,12,13 EF-2 ONION EXHAUST 250 -- -- -- <br /> DRESSING ROOMS <br /> EF-3 FRYER HOOD 985 Q <br /> EF COOK 100ACRUB ROOF2 ONION EXHAUST CENTRIFUGAL 250 1.45 1484 120/1/60 1/6 83 1.4,911,12,13 -- -- -- <br /> EF-4 GRIDDLE HOOD 585 <br /> EF EF-5 GRIDDLE HOODS 1170 L12M <br /> CENTRAL RE-12 ROOF FRYER HOOD CENTRIFUGAL 985 1.3 1834 208/3/60 1 140 1,4,6-14 <br /> 3 AC-1 DINING ROOM -- 1000 3000 2000 0100 <br /> -- <br /> EF CENTRAL RE-12 ROOF GRIDDLE HOOD CENTRIFUGAL 585 1.2 2070 208/3/60 1 90 1,4,6-14 AC-2 DINING ROOM 1000 3000 2000 �D , <br /> 4 # AC-3 KITCHEN -- 2000 6000 4000 <br /> 5 CENTRAL RE-12 ROOF GRIDDLE <br /> IAND FOODS CENTRIFUGAL 1170 1.5 2194 208/3/60 1 170 1,4,6-14 <br /> TOTAL 3540 4000 12000 8000 <br /> DINING ROOM: +2000 CFM <br /> ZONE SUB-TOTAL: KITCHEN AREA: -1540 CFM (2000 - 3540) t M <br /> REMARKS 7. FANS PROVIDED WITH CAPACITOR ASSISTED MOTORS. BUILDING IS 460 CFM POSITIVE engineering consultants <br /> 1. FAN, ROOFCURB, AND WEATHER COVER FURNISHED BY KITCHEN EQUIPMENT SUPPLIER. 8. FANS PROVIDED WITH GREASE RESERVOIR. 14901 Quorum Dr. #565 Dallas, TX 75254 <br /> 2. CENTRIFUGAL FAN WITH BIRDSCREEN AND BACKDRAFT DAMPER PROVIDED BY CONTRACTOR. 9. MAINTAIN 10' OF CLEARANCE BETWEEN EXHAUST DISCHARGE AND ANY OUTSIDE AIR INTAKE. rtmassociates.com 1 972.387.3500 <br /> 3. PROVIDE WITH ROOF CURB. 10. EXHAUST FANS SERVING TYPE 1 HOODS ARE DESIGNED TO AUTOMATICALLY ACTIVATE WHEN COOKING OPERATIONS <br /> 4. FURNISH NEMA 3R FACTORY DISCONNECT. REFERENCE SHEET E6.0 FOR MOUNTING/INSTALLATION. COORDINATE OCCUR. 18.GHAA.033 <br /> WITH ELECTRICAL SCOPE. 11. REFERENCE E8.0 FOR FAN CONTROL SCHEMATIC(S). PROTOTYPE VERSION <br /> 5. INTERLOCK WITH RESTROOM LIGHTS (REFERENCE ELECTRICAL PLANS). 12. COORDINATE ELECTRICAL REQUIREMENTS INCLUDING CABLING AND CONDUIT WITH ELECTRICAL PLANS. URBAN DESIGN <br /> 6. UL762 LISTED. 13. REFERENCE AIR BALANCE SCHEDULE ON M2.0 FOR AIRFLOWS. <br /> 14. PROVIDE FAN WITH SIDE INLET. <br /> PROJECT NAME <br /> IN-N-OUT <br /> BURGER <br /> AIR CURTAIN SCHEDULE <br /> UNIT MANUFACTURER LOCATION DIMENSIONS SOUND ELECTRICAL OPER. WT. REMARKS LATH RO P <br /> NO. & MODEL NO. (dBA) VOLTS/PH/HZ AMPS (LBS) CALIFORNIA <br /> FAC SAVE-T REAR DOOR 53 208/230/1/60 5.0 130 1,3,4,5 16514 GOLDEN VALLEY PKWY <br /> 1 IBD-2-48-1-SS 10"H X 8.5"D X 48"W <br /> LATHROP, CA 95330 <br /> FAC <br /> SAVE <br /> 2T25-1-SS PAY/PICK-UP 10"H X 8.5"D X 25"W 49 115/1/60 2.4 24 2,3,4,5 <br /> 2&3 WINDOWS <br /> REMARKS 3. PROVIDE ALL HARDWARE AND ACCESSORIES NECESSARY FOR OPERATION. <br /> 1. PROVIDE DOOR LIMIT SWITCH AND MOTOR CONTROL PANEL. MOUNT SWITCH TO TURN AIR CURTAIN ON AS DOOR OPENS. 4. INSTALL UNITS WITHOUT OBSTRUCTION TO AIRFLOW. <br /> 2. PROVIDE WITH NORMALLY CLOSED LIMIT SWITCH. MOUNT SWITCH TO TURN AIR CURTAIN ON AS DOOR BEGINS TO OPEN. 5. AIR CURTAINS ARE SUPPLIED BY KITCHEN SUPPLIER FOR INSTALLATION BY CONTRACTOR. <br /> MoNmOUT <br /> FAN COIL UNITS IkBVRGER@ <br /> CAPACITY © DESIGN CONDITIONS ELECTRICAL GOD BLESS AMERICA <br /> UNIT ZONE/AREA MANUFACTURER LOCATION AIRFLOW (CFM) SOUND DIMENSIONS S.E.E.R OPER. REMARKS <br /> NO. SERVED & MODEL NO. LO-MID-HI (DBA) WXDXH (INCHES) COOLING HEATING VOLT/PH/HZ M.C.A MOCP (® ARI CONDITIONS) WEIGHT (LBS) <br /> KBTU H KBTU H <br /> FC MIS DAIKIN MIS 39X11-5/8X10-3/8 * * * PROJECT NUMBER <br /> 1 491-579-713 39-45-5124.0 25.2 15.0 27 1,3,4,6,7 <br /> ROOM FTXN24NMVJU ROOM <br /> 180641.001 <br /> _CU MIS DAIKIN ROOF 2609 59 37-9/16X14-1/4X28-15/16 <br /> 1 ROOM RXN24NMVJU N/A N/A 208/1/60 18.3 20 N/A 97 1,2,4,5,6,7 SHEET TITLE <br /> REMARKS 5. PROVIDE LOW AMBIENT KIT IN CLIMATES WITH 99.6% ASHRAE DESIGN HEATING TEMPERATURE BELOW 407. * INDOOR UNITS RECEIVE POWER FROM OUTDOOR UNITS THROUGH MECHANICAL <br /> E 1 . UNITS RATED AT CONDITIONS OF 807 DRY-BULB (DB)/67°F WET-BULB (WB) AND OUTDOOR CONDITIONS OF 957 DB/75°F 6. PROVIDE ALL HARDWARE AND ACCESSORIES NECESSARY FOR PROPER INSTALLATION. FIELD-SUPPLIED INTERCONNECTED WIRING. EQUIPMENT <br /> WB (COOLING), AND 70°F DB/607 WB AND OUTDOOR CONDITIONS OF 47°F DB/43°F WB (HEATING) 7. PIPING INSTALLATION: REFRIGERANT PIPING MATERIAL: FACTORY CLEANED AND CHARGED, ACR COPPER TUBING (TYPE L) WITH <br /> 2. PROVIDE SEACOAST PROTECTION (OPTION BS) ON OUTSIDE UNITS LOCATED WITHIN 2 MILES OF A COAST. ENDS CAPPED TO PROTECT CLEANLINESS OF INTERIOR, CONFORMING TO ASTM B 280. FITTINGS: WROUGHT-COPPER JOINTS <br /> SCHEDULES <br /> 3. PROVIDE WALL-MOUNTED TEMPERATURE DISPLAY AND TEMPERATURE CONTROLLER. MAY BE FLARED UNLESS PROHIBITED BY AHJ. IF NOT PERMITTED, USE BRAZED JOINTS. BRAZING FILLER METALS: AWS A5.8, <br /> Z N 4. SIZE AND INSTALL REFRIGERANT PIPING PER MANUFACTURER'S RECOMMENDATIONS. SUITABLE FOR ACR PIPING. SUPPORT PIPING PER MSS STANDARD SP-69. PROVIDE ADDITIONAL SUPPORT AT ELBOWS AND F <br /> a; ITTINGS. INSULATE WITH 1/2" ARMSTRONG "ARMAFLEX" CLOSED CELL, ELASTOMERIC INSULATION. PROTECT INSULATION AT SHEET NUMBER <br /> HANGER SUPPORTS WITH SHIELDS. <br /> M o <br /> mCjM2mO <br /> a o <br /> z z <br /> Q- 0- <br />