bona <br /> Poly Tank System Specifications <br /> Anchor System <br /> Lugs Four(4) Linear Low Density Polyethylene <br /> Anchor Bolts Eight(8) Hilti HIT-RE 500-V3, 7/8-inch diameter threaded rod <br /> anchor to conform to ASTM A193 GR. B7 and hot dip <br /> galvanized per ASTM A153, 9 inch minimum embed <br /> Cables 3/16-inch diameter, breaking strength 3,210 pounds <br /> The Poly Tank System has been provided with Zone 4 seismic restraints to prevent permanent <br /> displacement in any direction by lateral motion, overturning, or uplift. The following Poly Tank <br /> System specifications and documentation are included in the indicated appendices. <br /> • Poly Tank Dimensions: Appendix B <br /> • Poly Tank Appurtenances and Restraint System: Appendix C <br /> • Poly Tank Foundation and Anchor System Design: Appendix D <br /> • Poly Tank Certified Structural Analysis: Appendix E <br /> • Poly Tank Certified Foundation and Anchorage Structural Calculations: Appendix F <br /> • Poly Tank Anchor Pull Test Results: Appendix G <br /> • Poly Tank Leak Detection System Instruction Manual: Appendix H <br /> • Poly Tank Ultrasonic Level Controller Operator's Manual: Appendix I <br /> • Poly Tank System Photographs: Appendix J <br /> 6. Hazardous Characteristics of <br /> Poly Tank Wastewater <br /> The Poly Tank System holds wastewater generated from machine parts cleaning, which takes place <br /> on the second floor of the adjacent building in the hot vat and steam cleaning room. The wastewater <br /> consists of water, oil, and a sodium hydroxide cleaning solution that the parts are soaked in prior to <br /> steam cleaning. Analytical results from sample collected from the Poly Tank contents on <br /> September 25, 2018 are presented below. <br /> GHD I Engineering Assessment and Certification of Integrity of the 1,550-Gallon Polyethylene Waste Tank System 111189093(2)1 Page 5 <br />