Laserfiche WebLink
13 <br /> Hilti PROFIS Engineering 3.0.56 <br /> www.hilti.com <br /> Company: Page: 10 <br /> Address: Specifier: <br /> Phone I Fax: E-Mail: <br /> Design: Shear Loading Date: 2/13/2020 <br /> Fastening point: <br /> 8 Alternative fastening <br /> 8.1 Alternative fastening data <br /> Anchor type and diameter: HVU2+HAS B7 HDG 7/8 <br /> Return period(service life in years): 50 <br /> Item number: 68661 HAS-E B 7/8"x10"(element)/not available <br /> (capsule) <br /> Effective embedment depth: haf,act=6.625 in., hnom=6.625 in. <br /> Material: ASTM A 193 Grade B7 <br /> Evaluation Service Report: ESR-4372 <br /> Issued I Valid: 6/1/2019 16/1/2020 <br /> Proof: Design Method ACI 318-14/Chem <br /> Stand-off installation: eb=0.000 in.(no stand-off);t=0.500 in. <br /> Anchor plate : Ix x ly x t=10.000 in.x 10.000 in.x 0.500 in.;(Recommended plate thickness:not calculated) <br /> Profile: Rectangular plates and bars(AISC), 1/4-3/16;(L x W x T)=0.250 in.x 0.188 in. <br /> Base material: cracked concrete,3000,fc'=3,000 psi;h= 12.000 in.,Temp.short/long: 150/110 OF <br /> Installation: hammer drilled hole,Installation condition: Dry,Installation direction:vertical downward <br /> Reinforcement: tension:condition A,shear:condition A; no supplemental splitting reinforcement present <br /> edge reinforcement:>No.4 bar with stirrups <br /> Seismic loads(cat.C, D, E,or F) Tension load:yes(17.2.3.4.3(d)) <br /> Shear load:yes(17.2.3.5.3(c)) <br /> Max. Utilization with HVU2 + HAS 137 HDG 7/8: 49 % <br /> Fastening meets the design criteria! <br /> Input data and results must be checked for conformity with the existing conditions and for plausibility! <br /> PROMS Engineering(c)2003-2019 Hilti AG,FL-9494 Schaan Hilti is a registered Trademark of Hilti AG,Schaan <br /> 10 <br />