Rev. B2, 7/15 DCR-1006A Level Controller <br /> • Always mount above the highest anticipated target level by at least the <br /> published minimum blanking distance. If a target enters into the blanking <br /> area, error in the detection will occur. It is always advisable to allow for <br /> sufficient headroom to ensure that the target does not enter the blanking <br /> area. <br /> • Generally it is advisable to mount the sensor away from any vessel fill <br /> spouts. However, if heavy foam is expected, it is often helpful to mount the <br /> Sensor near a fill spout where the foam is being dispersed. <br /> • Avoid mounting the sensor in the direct center of a tank with a significantly <br /> domed top. A domed top can act as parabolic dish, amplifying small <br /> undesired signals that may be present inside the tank. <br /> • Avoid mounting the sensor in close proximity to tank walls, especially on <br /> tanks with corrugated walls or in applications where product buildup on <br /> the tank walls may occur. <br /> r'r IL Low Sensitivity'Det2etitSri Area - }�i$Nh3 ��i�tl�� t�Piladigf���y <br /> A RC3 <br /> 7 <br />