Laserfiche WebLink
Rev. B2, 7/15 DCR-1006A Level Controller <br /> CUSTOM (Custom Units): <br /> Allows the user to define a custom alphanumeric label for the Curve Fit and <br /> Linear Calculation Application Types. <br /> VOLUNI (Volume Units): <br /> Determines the unit of measure for the volumetric Application Types. Options: <br /> Cubic Feet, Million Cubic Feet, Gallons, Cubic Meters, Liters, Cubic Inches, Bar- <br /> rels. <br /> IN SEL (Input Select): <br /> Selects the sensor input used by the controller. <br /> DST: Standard DST sensor <br /> LR DST: Long Range DST (DST-3434) <br /> RS485: (MNU or MPX sensors only) <br /> NOTE: when connecting a new RS-485 sensor to the DCR-1006A, set the Input <br /> Select to DST (with the new RS-485 sensor connected), then switch the Input <br /> Select to RS485. This will initiate the DCR-1006A to upload and configure the <br /> parameter settings in the RS-485 sensor for proper operation with the DCR- <br /> 1006A. <br /> dECIML (Decimal Place): <br /> Sets the decimal place position in the Calculated Reading. <br /> Example: a reading of 26.573 (gallons, etc.) will be displayed as follows: <br /> Decimal Place = OVolume = 27 <br /> Decimal Place = 1Volume = 26.6 <br /> Decimal Place = 2Volume = 26.57 <br /> Decimal Place = 3Volume = 26.573 <br /> NOTE: the decimal place in all dimensional parameters is fixed based on the <br /> unit of measure selected (see Units on previous page) <br /> SENS N (Sensor Number): <br /> Sets the Modbus address number for the DCR-1006A when its interfacing with <br /> an RST-5003 module or the APG Modbus software. <br /> Automation Products Group, Inc. ON:.: <br /> APG,..i <br /> 1 <br /> 17 <br />