Laserfiche WebLink
DCR-1006A Level Controller Rev. B2, 7/15 <br /> 4-2OmA Settings <br /> NOTE: The 4-20mA Set Points must be entered in the units being displayed. <br /> For example if the display is setup to read in gallons, then the 4mA and 20mA <br /> Set Points would be set in gallons. <br /> SET4MA (4mA Set Point): <br /> Sets the reading to be associated with a 4mA output. <br /> SET20M (20mA Set Point): <br /> Sets the reading to be associated with a 20mA output. <br /> CAL4MA (4mA Calibration): <br /> Used to adjust the output current at the low end of the analog range (4mA <br /> endpoint). Increasing/decreasing the parameter value will increase/decrease <br /> the output current. <br /> CAL20M (20mA Calibration): <br /> Used to adjust the output current at the high end of the analog range (20mA <br /> endpoint). Increasing/decreasing the parameter value will increase/decrease <br /> the output current. <br /> P i <br /> 34 <br />