GENERAL NOTES LEGEND AND NOTES <br /> 1 . BEFORE SUBMITTING BID, THE ELECTRICAL CONTRACTOR SHALL VISIT THE �{ WALL MOUNTED OCCUPANCY SENSOR. SINGLE LINE NOTES : <br /> JOB SITE AND FULLY ACQUAINT HIMSELF WITH THE JOB CONDITION, IV <br /> SERVICE REQUIREMENTS BY UTILITY COMPANY AND CONNECTIONS, AND S. SINGLE POLE TOGGLE SWITCH 20 AMP, 120 V, @ 44" AFF 1. THIS DRAWING INDICATES EXISTING CONDITIONS <br /> OTHER CONDITIONS INCLUDING TRANSFORMER PAD, ALL NECESSARY PULL Sz DOUBLE POLE TOGGLE SWITCH 20 AMP, 120 V, @ 44" AFF WHICH WERE TAKEN FROM RECORD DRAWINGS. ° O <br /> BOXES, JUNCTION BOXES, SIZE AND NUMBER OF CONDUITS AND CONDUCTORS, THE ENGINEER ASSUMES NO RESPONSIBILITY FOR <br /> CONDUIT FITTINGS, SERVICE COMPONENTS, PANELBOARDS, ETC., WHETHER S3 THREE WAY SWITCH 20 AMP, 120 V, @ 44" AFF THE COMPLETENESS OR ACCURACY OF THESE <br /> SHOWN ON DRAWINGS OR NOT, TO MAKE A COMPLETE AND OPERABLECONDTIONS. THE CONTRACTOR IS TO VERIFY ALL <br /> ELECTRICAL SYSTEM WITHOUT ADDITIONAL COST TO OWNER. D DIMMER SWITCH 1800 WATTS, 15 AMP MINIMUM, 120 V, @ 44" AFF EXISTING CONDITIONS AND TO EXERCISE CAUTION O <br /> 2. ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF ALL LOCAL LAWS, Sm MOTOR RATED SWITCH, HP RATED IN THE DEMOLITION PROCESS AND PROMPTLY <br /> RULES AND REGULATIONS OF ALL LEGALLY CONSTITUTED PUBLIC NOTIFY THE ARCHITECT OF ANY DISCREPANCIES <br /> AUTHORITIES HAVING JURISDICTION. IN CASE OF CONFLICT BETWEEN SINGLE RECEPTACLE, NEMA RATING AS NOTED ENCOUNTERED. SJB Brands, LLC <br /> REQUIREMENTS, THE MOST RESTRICTIVE SHALL APPLY. FOLLOW THE LOCAL 491 DUPLEX RECEPTACLE 20 AMP, 120 V GROUNDING TYPE, @ 15" AFF 17915 SKY PARK CIRCLE, SUITE J, <br /> LAWS, RULES AND REGULATIONS FOR ANY CONFLICTS BETWEEN THE 2. BEFORE COMMENCING WORK, THE CONTRACTOR IS <br /> CONTRACT DRAWINGS AND THE LAWS, RULES AND REGULATION. DUPLEX RECEPTACLE 20 AMP 120V GROUNDING TYPE, @ CEILING TO REVIEW COMPLETE SET OF DEMOLITION IRVINE, CA 92614 <br /> 3. THIS CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED PERMITSDOUBLE DUPLEX RECEPTACLE 20 AMP 120V GROUNDING TYPE, @ 15" AFF WORKING DRAWINGS FOR ADDTIONAL INFORMATION, TEL: (949)475-0146 <br /> AND ARRANGE ALL REQUIRED INSPECTIONS FOR THE EXECUTION OF THE 00- TELEPHONE OUTLET WITH 3/4" CONDUIT TO TELEPHONE BACKBOARD DISCONNECT AND REMOVE ALL ELECTRICAL WORK FAX:(949)475-0137 <br /> WORK UNDER THIS CONTRACT. HE SHALL FURNISH ALL INSTRUMENTSASSOCIATED WITH EQUIPMENT BEING REMOVED, <br /> AND PERFORM ALL TESTS REQUIRED BY THE AUTHORITIES HAVING TEL. OUTLET & DATA OUTLET WITH (2) 3/4" CONDUIT COORDINATE ALL ELECTRICAL DEMOLITION WORK <br /> JURISDICTION. HE SHALL ALSO CORRECT ALL FAILURES AND REPLACE D DATA OUTLET WITH 3/4" CONDUIT WITH OTHER DISCIPLINES. <br /> THESE DRAWINGS AND SPECIFICATIONS AND IDEAS, DESIGNS AND <br /> ANY DAMAGED PORTIONS OF THE WORK RESULTING FROM THESE TESTS. JUNCTION BOX TO SUIT THE FIELD CONDITIONS 3. EXISTING EQUIPMENT NOT INDICATED TO BE ARRANGEMENTS REPRESENTED THEREBY ARE AND SHALL REMAIN <br /> THE COST OF THE FOREGOING ITEMS SHALL BE PAID BY THE THE PROPERTY OF GARY WANG & ASSOCIATES; AND NO PART <br /> CONTRACTOR. MOTOR OUTLET REMOVED OR ABANDONED IS TO REMAIN IN USE THEREOF SHALL BE COPIED, DISCLOSED TO OTHERS OR USED IN <br /> AND CIRCUIT CONTINUITY SHOULD BE MAINTAINED CONNECTION WITH ANY WORK OR PROJECT OTHER THAN THE <br /> 4. THE CONTRACTOR SHALL COORDINATE CLOSELY WITH THE OWNER ANDSPECIFIC PROJECT FOR WHICH THEY HAVE BEEN PREPARED AND <br /> OTHER TRADES FOR ALL PHASES AND SCHEDULING OF WORK, AND NOTES: 1. SUBSCRIPT LETTER NEXT TO THE ABOVE SYMBOLS INDICATES DEVICE AT ALL TIMES. DEVELOPED WITHOUT THE WRITTEN CONSENT OF GARY WANG & <br /> AUTHORIZED IN WRITING BY THE OWNER AT LEAST ONE WEEK PRIOR CONTROLLED ASSOCIATES. VISUAL CONTACT WITH THESE DRAWINGS AND <br /> 2. DEVICES AND COVER PLATE COLOR AS SELECTED BY ARCHITECT, SEE 4. NEW WORK, INDICATED ON THIS DRAWING WITH SPECIFICATIONS SHALL CONSTITUTE CONCLUSIVE EVIDENCE OF <br /> TO THE EXECUTION OF ANY WORK. ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF OUTLET, UNLESS HEAVIER SOLID LINES AND REFERENCE NOTES, THESE RESTRICTIONS. WRITTEN DIMENSIONS ON THESE DRAWINGS <br /> 5. ALL MATERIAL FURNISHED AND INSTALLED UNDER THIS CONTRACT SHALL SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS; <br /> NOTED. COORDINATE REFRIGERATION OUTLET REQUIREMENT WITH HILLS SHALL BE PERFORMED BY PHASE PRIOR TO OR CONTRACTORS SHALL VERIFY, AND BE RESPONSIBLE FOR ALL <br /> BE NEW AND UL LISTED, FREE FROM ALL DEFECTS, AND SHALL BE REFRIGERATION PLAN. IN CONJUNCTION WITH DEMOLITION WORK. DIMENSIONS AND CONDITIONS ON THE JOB, AND THIS OFFICE <br /> GUARANTEED FOR A PERIOD OF ONE (1) YEAR FROM DATE OF 3. RECEPTACLES IN BATHROOM, LAUNDRY ROOM, AND KITCHEN MUST BE NOTIFIED OF ANY VARIATIONS FROM THE DIMENSIONS <br /> ACCEPTANCE OF THE WORK. DCONDITIONS SHOWN <br /> SINK AND EXTERIOR LOCATIONS SHALL BE GROUND FAULT TYPE (GFI) BED <br /> SUBMITT TOSTHESE BY DRAWINGS. <br /> THIS OFFICE REVIEWBEFORE PROCEEDING <br /> 6. THE ELECTRICAL DRAWINGS, CONDUIT RUNS, WIRING AND ELECTRICAL LEGENDS WITH THE FABRICATION. <br /> INFORMATION ARE DIAGRAMMATIC ONLY. DO NOT SCALE THE e EMERGENCY CIRCUIT. LOCK ON DEVICE FOR BREAKER SERVING <br /> ELECTRICAL DRAWINGS TO DETERMINE THE LOCATION OF EQUIPMENT OR NEW WORK <br /> OUTLETS. SL CIRCUIT BREAKER ARCHITECT <br /> 7. REFER TO THE ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT EXISTING TO REMAIN, U.O.N. <br /> LOCATIONS OF ALL LIGHTING FIXTURES, CEILING MOUNTED OUTLETS -�� SWITCH AND FUSES <br /> AND EQUIPMENT. ❑p DISCONNECT SWITCH 7z7z7z7z-, DEMOLITION <br /> 8. ALL RECEPTACLES AND OUTLET MOUNTING HEIGHTS AND EXACT LOCATION <br /> SHALL BE COORDINATED WITH ARCHITECTURAL, DRAWINGS ELEVATIONS ZP COMBINATION MAGNETIC STARTER & FUSED DISCONNECT (E): EXISTING. FIELD TO VERIFY. GARY WANG <br /> PRIOR TO ROUGH-IN WORK. z MANUAL MOTOR STARTER 3-P, W / OVER LOAD PRETECTION (EF): EXISTING FEEDER. FIELD TO VERIFY. &ASSOCIATES, INC. <br /> 9. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO VERIFY TYPES OF a <br /> CEILING SYSTEMS AND TO FURNISH APPROVED LIGHTING FIXTURES OF WATT/HOUR METER SOCKET (N): NEW <br /> THE TYPE REQUIRED FOR MOUNTING IN RELATED CEILINGS. FIXTURES (R): EXISTING TO BE RELOCATED. 1000 Corporate Center Dr., Suite 550 <br /> SHALL BE COMPLETE WITH NECESSARY MOUNTING HARDWARE AND ❑T TRANSFORMER Monterey Park, CA 91754 <br /> ACCESSORIES. FIXTURES LOCATED IN DAMP OR WET LOCATIONS SHALL TEL: (626)288-6898 FAX: (626) 768-7101 htt //www. ar <br /> BE LABELED FOR USE IN SUCH LOCATIONS. CURRENT TRANSFORMER p: 9 ywan 9 <br /> com <br /> 10. ALL RECESSED LIGHTING FIXTURES, SPEAKERS, PANELBOARDS, SWITCHES, ® SWITCHBOARD KEY NOTES: <br /> ETC., MOUNTED IN FIRE RATED STRUCTURES SHALL BE ENCLOSED WITH PANELBOARD <br /> AN APPROVED ENCLOSURE CARRYING THE SAME FIRE RATING AS THE ALL NEW CIRCUIT BREAKERS IN PANEL "A" SHALL MATCH <br /> STRUCTURE. ® TELEPHONE CABINET WITH BACKBOARD <br /> 11. ELECTRICAL OUTLETS ON OPPOSITE SIDES OF FIRE RATED WALLS AND THE HIGHEST EXISTING AIC RATING IN PANEL "A". STAMP <br /> PARTITIONS MUST BE SEPARATED BY DISTANCE OF 24 INCHES HORIZONTAL, NOTES: 1 . BREAKERS, SWITCHES, FUSES, METER SOCKETS, AND CURRENT CARRYING <br /> U.B.C. 4304 OPENINGS IN FIRE RATED WALLS GREATER THAN 16 SQ. DEVICES SHALL BE DESIGNED TO WITHSTAND MAXIMUM AVAILABLE FAULT INSPECTOR TO VERIFY AT SITE. <br /> INCHES MUST BE FIRE STOPPED. CURRENT (AFC) ESTABLISHED BY SERVING UTILITY FIELD TO VERIFY EXACT LOCATION. RELOCATED AS REQUIRED. <br /> 12. SEAL ALL PENETRATIONS THROUGH FIRE RATED WALLS, CEILINGS, FLOORS, 2• SWITCHBOARDS AND PANELBOARDS BUSSING SHALL BE BRACED TO WITH- <br /> ETC., TO MAINTAIN THE FIRE RATING. FURNISH AND INSTALL FIRE STAND MAXIMUM AVAILABLE FAULT D ARC <br /> RATED ENCLOSURE FOR ALL EQUIPMENT PENETRATING INTO FIRE RATED A-1-3-5 <br /> ENVELOPES, SPACES ETC. CONDUIT HOME RUN TO SOURCE INDICATING PANEL "A" CIRCUITS #1 , 3 8c 5 <br /> 13. PORTIONS OF THE CEILING SYSTEMS MAY BE INACCESSIBLE. THEREFORE, CONDUITRUN CONCEALED IN CEILING SPACE OR IN WALL EXISTING <br /> THE CONTRACTOR SHALL STRATEGICALLY LOCATE ACCESS BOXES, ETC., MAIN SWITCHBOARD - MS * N . C32569 �r <br /> WHICH SHALL BE READILY ACCESSIBLE. ALL LIGHTING FIXTURE WIRING, CONDUIT RUN BELOW FLOORS OR IN GRADE RE .04- - 019 <br /> BALLASTS, J-BOXES, ETC. SHALL BE ACCESSIBLE FROM FIXTURE OPENING. �E) 120/208V, 34, 4W BUS 65KAIC _.�--- CP <br /> 14. ALL WIRING AND ELECTRICAL EQUIPMENT INSTALLED FOR MECHANICALS HASH MARKS INDICATE QUANTITY OF CONDUCTORS. NO HASH MARK INDICATES q <br /> AND PLUMBING EQUIPMENT SHALL BE IN ACCORDANCE WITH DIVISION 15 #10 2 #12 AWG. U.O.N. (#10 INDICATES #10 AWG. CONDUCTORS) SIZE OF CONDUIT SHALL r # <br /> AND ASSOCIATED DRAWINGS. CONTRACTOR TO OBTAIN THE REQUIRED BE BASED ON TABLE 1 , CHAPTER 9 OF N.E.C. AMD TABLE 3A AND 3B SHALL �Il SOF CAL��� <br /> MECHANICAL AND PLUMBING DRAWINGS AND PROVIDE ALL EQUIPMENT, DETERMINE THE CONDUIT SIZES. MINIMUM CONDUIT SIZE SHALL BE 1/2". <br /> RACEWAYS, WIRING, ETC., AS INDICATED THEREON AS PROVIDED T TELEPHONE CABLE IN 3/4" CONDUIT <br /> UNDER THE ELECTRICAL WORK. <br /> 15. ALL FINAL CONNECTIONS TO OWNER FURNISHED EQUIPMENT SHALL BE TV TELEVISION ANTENNA CABLE IN 3/4" CONDUIT 200AS-3P <br /> MADE BY THE CONTRACTOR UNLESS OTHERWISE NOTED. VERIFY S CONDUIT RUN FOR SPEAKER SYSTEM. 3/4" C. U.O.N. EXISTING <br /> ELECTRICAL CHARACTERISTICS AND U.L. LISTING PRIOR TO CONNECTION. 20OAF PROJECT NAME/ADDRESS: <br /> 16. THE CONTRACTOR SHALL VERIFY THE LOAD INPUT VOLTAGE OF ALL - F- CONDUIT RUN FOR FIRE ALARM SYSTEM. 3/4" C. U.O.N. - - - - - - - - <br /> EQUIPMENT PRIOR TO INSTALLATION. ACCEPTING ANY EQUIPMENT r <br /> RESULT IN LOAD INCREASE SHALL BE THE RESPONSIBILITY OF D. NOTES: 1. <br /> TELEPHONE AND TELEVISION OMPANY <br /> LES MAY BE PREWIRED BY LOCAL <br /> CONTRACTORTEL/COMM/CABLE T.V � JUICE IT UPI <br /> 17. PROVIDE AN ADDITIONAL JUNCTION BOX (SIZE AS REQUIRED) WHERE 2. ALL CONDUIT SHALL BE RIGID STEEL OR EMT. FLEXIBLE CONDUIT SHALL RIPON TOWN SQUARE <br /> THE NUMBER OF CONDUCTORS EXCEEDS THE MAXIMUM ALLOWED FOR BE LIMITED TO 72" FOR FINAL CONNECTION TO LIGHTING FIXTURES OR (E) <br /> A GIVEN JUNCTION POINT OR OUTLET. MOTORS, INCLUDE GROUNDING CONDUCTOR. P.V.C. CONDUIT SHALL BE <br /> USED ONLY FOR UNDERGROUND. 2"C-4#3/0 + 1#6G 1201 W. MAIN ST., <br /> 18. CONDUCTORS SHALL BE THHN/THWN 600 VOLT INSULATION COPPER UNLESS RIPON, CA 95366 <br /> OTHERWISE NOTED. USE PROPER TEMPERATURE RATING OF CONDUCTORS L=1150' VD=0.8% <br /> BASED ON THE AMBIENT AIR TEMPERATURE WHERE CONDUCTORS ARE BEING <br /> USED. HIGHER AMPACITY CONDUCTORS AND LARGER RACEWAY SHALL BE <br /> PROVIDED TO OFFSET THE AMPACITY CORRECTION FACTORS AS INDICATED <br /> IN NEC TABLE 310 AND ELSEWHERE IN CODE. REVISIONS: <br /> 19. DO ALL DRILLING, CUTTING, CHANNELING AND PATCHING REQUIRE TO (E) PNL "A" <br /> ELECTRICAL WORK AND INDICATED OR HEREIN SPECIFIED. ALL HOLES, VOLTAGE(V) 120Z 208 1 3 PH 4 W BUS 225 (A) MAIN CB MLO AIC VERIFY (A) MTD. FLUSH -1 0 - <br /> CURBS, ETC., IN FLOORS, CEILINGS AND WALLS SHALL BE PATCHED, DESCRIPTION LOAD(VA) LOAD OUTLETS CB CIR GR CB OUTLETS LOAD LOAD(VA) DESCRIPTION Q - <br /> UNLESS INDICATED OTHERWISE. PAINT ALL EXPOSED ELECTRICAL A B C CODE LTG REC MISC AIP No NO AIP MS REC LTO CODE A B C © _ <br /> RACEWAYS, CABINETS, ENCLOSURES AND FITTINGS TO MATCH IN LTG 378 L 7 1 2011 1 • 2 12011 1 1 L 1200 SIGN PANEL"A" ® _ <br /> COLOR ADJACENT SURFACES IN FINISHED AREAS. LTG 572 L 13 2011 3 ® 4 2011 1 R 1600 SHOWVNNDOW (E) <br /> 20. EMERGENCY LIGHTING SHALL BE PROVIDED PER U.B.C. OR LOCAL CODE D AND SHALL BE DESIGN TO PROVIDE MINIMUM REQUIRE FOOTCANDLES SPARE 120/11 5 • 6 2011 1 R 16W SHOWVMNDOW L - J - <br /> AND LUMENS. SPARE 1 2011 7 ■ 8 2011 1 K 1 936 COLDTABLE <br /> 21 . BRANCH CONTROL CIRCUITING MAY NOT BE INDICATED ON THESE PLANS. SPARE 1 2011 9 10 2011 1 K 1800 BLENDER#1 109(A) 8 - <br /> CONTRACTOR IS RESPONSIBLE TO COMPLETE THE BRANCH CIRCUIT WIRING SPARE 2011 11 0 12 2011 1 K 1800 BLENDER#2 <br /> IN ACCORDANCE WITH PLAN NOTES AND AS PERMITTED BY LATEST NATIONAL ROOF REC. 360 R 1 2011 13 14 2011 1 K 1800 BLENDER#3 <br /> ELECTRICAL CODE (N.E.C.) AND ANY LOCAL SUPPLEMENT. CONTRACTOR COMPUTER 180 R 1 2011 .15 • 16 2011 1 K 1800 BLENDER#4 ISSUE DATE: <br /> SHALL SUBMIT FINISH DRAWINGS AS A PART OF SHOP DRAWING SUBMITTAL MA NA GER ST. 360 R 2 2011 17 ® 18120/11 1 K 1380 ICE VIA KER 1ST - <br /> TO ARCHITECT AND AUTHORITY HAVING JURISDICTION. SPARE 2011 19 20 2011 1 K 1000 W.I.COOLER SINGLE LINE DIAGRAM <br /> 2ND <br /> SPARE 20/1 21 • 22 2012 1 K 1040 COOLER COMP <br /> 3RD - <br /> AIR CURTAINICONV. 1200 K 1 ..20/l ..23 + 24 K 1040 1. <br /> NO SCALE <br /> OVEN 1500 K 1 2011 25 • 26 20/1 1 K 500 W.I.FREEZER 4TH - <br /> JUICE TOVUER 1380 K 2 2011 27 ® 28120/2 1 K 1040 FREEZER COMP. 5TH <br /> JUICER 1270 K 2 2011 29 • 30 K 1040 1 1. 6TH <br /> JUICER/REF. 1176 K 3 2011 31 ■ 32 2011 2 R 360 CASH REGISTER <br /> CONY. 1080 R 1 6 20/1 33 ® 34 2011 1 1 1 K 1920 MERCHANDISER <br /> CONY. 180 R 1 20/1 35 + 36 20/1 1 K 1500 BLENDER JOB NUMBER <br /> HP;1 3840 L 1 50/3 37 ■ 38 <br /> 3840 L 39 • 40 <br /> 3840 L 41 ■ 42 ARCH PROJECT#: 18-287 <br /> 7254 7052 6850 5796 9200 1 8360 <br /> TOTAL CONN.LOAD 44512 (VA) <br /> L.C.L.&L.M 13670 x1_25 17088 (VA) LOAD CODE K KITCHEN <br /> KIT.EQUIP 25122 16329 (VA) (K=> 5 65%) L LONG CONT. LOAD/ <br /> DRAWN BY CHECKED BY <br /> RFC.<=I DKVA 5720 5720 (VA) (1ST 10 KVA x 100 %) L.ARGEST MOTOR J R ADR <br /> REC,RH7VfAINDER 0 x0.5 0 (VA) O OTHERS <br /> OTHERS LOAD 0 x1 0 (VA) R RECEPTACLE <br /> SHEET CONTENT <br /> TOTAL LOAD 39137 (VA) 109 (A) <br /> NOTES <br /> SHEET NO <br />