Laserfiche WebLink
SEQUENCE OF OPERATION <br />SAF <br />G <br />X <br />D <br />OSA <br />GENERAL: <br />EA <br />KEF-A1 <br />C/T <br />WHEN KITCHEN HOOD EXHAUST FAN KEF-A1 IS SWITCHED ON, THEN AC-A2 SHALL BE ENABLED BY IT'S OWN INTERNAL <br />CONTROLS TO PROVIDE TEMPERED MAKE-UP AIR. INTERNAL CONTROLS SHALL OPEN THE OUTSIDE AIR DAMPER TO 100% <br />AND STAGE MECHANICAL HEATING OR COOLING AS REQUIRED TO MAINTAIN DISCHARGE AIR TEMPERATURE SETPOINT <br />(70 degF IN HEATING, 76 degF IN COOLING). WHEN KEF-A1 IS SWITCHED OFF, THEN AC-A2 SHALL BE DISABLED BY IT'S <br />OWN INTERNAL CONTROLS. THE OUTSIDE AIR DAMPER SHALL MODULATE FULLY CLOSED WHENEVER AC-A2 IS DISABLED. <br />S <br />PWR (E)120V PWR.(E)ETHERNET DATA DROP. <br />120V PWR, BY DIV. 26 <br />PCM COMMUNICATION WITH "PELICAN" <br />WIRELESS GATEWAY, SEE 1 / M6.1. <br />"PELICAN" #PM5-230 WIRELESS POWER <br />CONTROL MODULE, COMPRISED OF TWO <br />COMPONENTS; A WIRELESS CONTROL BOX <br />TRANSMITTER/RECEIVER, AND A POWER <br />RELAY MODULE. BOTH COMPONENTS ARE <br />WALL MOUNTED. WIRELESS POWER <br />CONTROL MODULE USED TO SCHEDULE <br />ON/OFF UP TO FIVE AUXILIARY PIECES <br />OF EQUIPMENT, SUCH AS EXHAUST FANS, <br />PUMPS, ETC. INSTALL POWER RELAY <br />MODULE COMPONENT IN DEDICATED <br />CONTROL PANEL. INSTALL BOTH <br />TO AUX. EQUIP, <br />TYP. <br />COMPONENTS IN ANY OF THE FOLLOWING <br />TYPES OF ROOMS, BASED ON LOCATIONS <br />OF AUXILIARY EQUIPMENT BEING <br />CONTROLLED: ELECTRICAL, IDF OR MDF, <br />CUSTODIAN, OR STORAGE.(E)"PELICAN" WIRELESS GATEWAY <br />WIRELESS COMMUNICATION WITH <br />EXISTING AND NEW "PELICAN" <br />CONTROLS PRODUCTS. <br />COMMUNICATION HUB, LOCATED IN <br />MP BUILDING AT STAGE AREA. <br />SEQUENCE OF OPERATION <br />OUTDOOR SECTION <br />INDOOR SECTION <br />PWR <br />T <br />FACTORY <br />THERMOSTAT <br />ALL LOW VOLTAGE CONDUIT <br />& CONDUCTOR INTERLOCKS <br />(I.E. VOLTAGE < 120V)BETWEEN INDOOR UNIT AND <br />OUTDOOR UNIT BY TCC <br />CONTROL HARDWARE AND LOGIC FOR THE SPLIT SYSTEM SHALL BE THE RESPONSIBILITY <br />OF THE UNIT MANUFACTURER. TCC SHALL INSTALL THE FACTORY PROVIDED CONTROL <br />PACKAGE AS REQUIRED FOR PROPER UNIT OPERATION. <br />KEF-A1 <br />DEDICATED WALL SWITCH, INSTALLED BY DIV. 26. <br />WHEN KEF-A1 IS SWITCHED ON, AC-A2 SHALL BE <br />ENABLED TO PROVIDE TEMPERED MAKE-UP AIR. <br />SEE 4 / M6.1 FOR AC-A2 CONTROL DIAGRAM. WHEN <br />KEF-A1 IS SWITCHED ON,(E)AC-A1 SHALL ALSO BE <br />ENABLED, IF NOT ALREADY RUNNING, TO PROVIDE <br />ADDITIONAL KITCHEN HOOD EXHAUST MAKE-UP AIR, <br />VIA DUCTED TRANSFER. <br />RESPECTIVE OUTSIDE AIR FAN SHALL BE INTERLOCKED TO RUN WITH SPLIT SYSTEM. SEE <br />SPLIT SYSTEM AC UNIT SCHEDULE FOR SPECIFIC INTERLOCKS. <br />INSTALLED BY DIV. 26 <br />SWITCH PROVIDED & S <br />PWR <br />EF INTERLOCK BY DIV. 26 <br />LIGHT <br />PWR <br />EF CONTROL W/ LIGHTS <br />EF INTERLOCK W/ AC UNIT <br />PWR <br />J-BOX PROVIDED & <br />INSTALLED BY DIV. 26 <br />CONNECTION & WIRING OF <br />INTERLOCK RELAY PROVIDED <br />AND INSTALLED BY DIV. 23 <br />INTERLOCK TO RUN W/ AC UNIT. <br />SEE EXHAUST FAN SCHEDULE <br />FOR SPECIFIC INTERLOCKS. <br />PWR <br />SEE 2 / M6.1 FOR <br />CONTINUATION. <br />AQUASTAT <br />TEMP SENSOR <br />DOMESTIC HOT WATER <br />IN-LINE CIRCULATING <br />PUMP, REFER TO <br />PLUMBING DRAWINGS. <br />SET AQUASTAT TO SHUT OFF PUMP WHEN <br />RETURN WATER TEMPERATURE REACHES 105 <br />DEG. F (ADJUSTABLE). HVAC CONTROL SYSTEM <br />SHALL DISABLE CIRC PUMP OPERATION DURING <br />UNOCCUPIED HOURS, AS SCHEDULED BY OWNER <br />THRU THE HVAC CONTROL SYSTEM. <br />SHEETSOF730 Howe Avenue, Suite 450Sacramento, CA 95825Phone: 916.921.2112Fax: 916.921.2212KITCHEN RENOVATIONJOE SERNA SCHOOLSHEET NO. <br />CONSULTANT <br />UPDATED <br />CADFILE <br />CHECKED <br />DRAWN <br />SCALE <br />PROJECT NO. <br />DATE <br />REVISIONS BY <br />19-32-050 <br />RL <br />TD <br />AS NOTED <br />L:\2019\191009.00\1200 Drawings\1205 AutoCAD Project Files\M6.1.dwg - April 10, 2020 01:39 PM - Richard Lingo04/10/2020 <br />FILE NO. 39-50 APP NO. 02-118041 <br />M6.1 MECHANICAL CONTROLS