Laserfiche WebLink
J" LDT 5000 Field Test Apparatus Page 1 of 1 <br /> ,411110 Tanknology Line Leak Detector Test <br /> Work Order: 2342150 Date : 9/20/2019 <br /> Site Name / ID : 7- ELEVEN # 17334 MKT 2368 ( N -747 ) / 17334 <br /> Address : 4501 N . PERSHING AVE . @ ROSEMARIE LN , <br /> City: STOCKTON State : CA Zip : 95207 <br /> Tank ID T- 1 T-2 <br /> Product RUL PUL <br /> Product Line 1 1 <br /> Tested From 3 3 <br /> Existing /New Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical <br /> Manufacturer/Model Red Jacket FXIV Vaporless LD-2000 <br /> Serial No. 41200- 1960 15021404 <br /> Pump Operating Pressure ( psi ) 29 . 00 21 . 00 <br /> Calibrated Leak (mllmin ) 189 . 0 189 . 0 <br /> Calibrated Leak (gph ) 3 . 00 3 . 00 <br /> Holding PSI 17 . 00 18 . 00 <br /> ' N/A for Electronic Lo 's <br /> Resiliency (ml ) 120 . 00 100 . 00 <br /> ' N/A for Electronic Lo's <br /> Metering PSI 10 17 <br /> ' NIA for Electronic LD's <br /> pening Time (sec) <br /> k3 1 <br /> ' NIA for Electronic LD's <br /> est Results Pass Pass <br /> Technician Comments : <br /> Technician Name : Clint Fuhrman Certification # : 96737 <br /> ///�� Expire Date : 2/4/2022 <br /> Technician Signature : <br /> Environmental Compliance for Petroleum Systems <br /> © 2019 Tanknology Inc., Austin, TX. All rights reserved. tanknology.wnn <br />