<br /> qv MECHANICAL EQUIPMENT CONNECTION SCHEDULE MAIN SWITCHBOARD 'MSB' SCHEDULE . u
<br /> ITEMS BY OTHERS ITEMS BY ELECTRICAL CONTRACTOR VOLTAGE:1201208 AMP: 2000 PHASE: 3 WIRE: 4 , w
<br /> LOCATION:NORTH EXTERIOR AIC: 65,000
<br /> DISCONNECT FEEDER EQUIPMENT CONTROL REMARKS TYPE OF MAIN:MCB MOUNTING: SURFACE
<br /> UNIT DESCRIPTION LOCATION VOLTAGE PHASE MCA MOCP KW HP DESCRIPTION NEMA PANEL&CIRCUIT# ALL CONTROL CONDUIT BY EC MANUFACTURER:SIEMENS ENCLOSURE: NEMA 3R T
<br /> CONDUIT/WIRE TYPE: SENTRON SES 1
<br /> OENCLOSURE ALL CONTROL DEVICES BY MC UNO r 1 N FED FROM:UTILITY PAD MOUNT TRANSFORMER R181109-1656 `.J
<br /> M
<br /> HP-1 HEAT PUMP 1 ROOF 208 1 27 40 30A,2P,NON-FUSED 3R 3H -1,3 SERVES CORRESPONDING INDOOR FAN COIL. PROVIDE 208VAC,1-PHASE CONNECTION TO OUTDOOR HEAT PUMP. P BRKR CKT 1/2"C W/(2)#10 CU+(1)#10 CU GND SEE CORRESPONDING FAN COIL UNIT FOR CONTROL COORDINATE FINAL LOCATION OF UNIT AND ALL CONTROL CONDUITS REQUIRED W/MC PRIOR TO ROUGH-IN CIRCUIT A B C
<br /> DESCRIPTION L AMP NO
<br /> SERVES CORRESPONDING INDOOR FAN COIL. PROVIDE 208VAC,1-PHASE CONNECTION TO OUTDOOR HEAT PUMP. PANEL'lN 3 400 1 39775 39775 39775
<br /> O HP-2 HEAT PUMP 2 ROOF 208 1 14 20 30A,2P,NON-FUSED 3R 3H -5,7 1/2"C W/(2)#12 CU+(1)#12 CU GND SEE CORRESPONDING FAN COIL UNIT FOR CONTROL COORDINATE FINAL LOCATION OF UNIT AND ALL CONTROL CONDUITS REQUIRED WI MC PRIOR TO ROUGH-IN PANEL'l B' 3 400 2 36062 36062 36062
<br /> RED INC ARCHITECTS
<br /> PANEL'l H' 3 400 3 27443 32081 28733
<br /> 1217 J STREET,MODESTO,CA 95354
<br /> HP-3 HEAT PUMP 3 ROOF 208 1 14 20 30A,2P,NON-FUSED 3R 3H -9,11 1/2"C WI(2)#12 CU+(1)#12 CU GND SEE CORRESPONDING FAN COIL UNIT FOR CONTROL SERVES CORRESPONDING INDOOR FAN COIL. PROVIDE 208VAC,1-PHASE CONNECTION TO OUTDOOR HEAT PUMP. PANEL'l K 3 150 4 10038 9824 11414 209.522.8900COORDINATE FINAL LOCATION OF UNIT AND ALL CONTROL CONDUITS REQUIRED W/MC PRIOR TO ROUGH-IN
<br /> PANEL'1L' 3 150 5 7646 5922 7699
<br /> PANEL'l P' 3 150 6 11178 13590 15470
<br /> HP4 HEAT PUMP 4 ROOF 208 1 27 40 30A,2P,NON-FUSED 3R 3H -13,15 1/2"C WI(2)#10 CU+(1)#10 CU GND SEE CORRESPONDING FAN COIL UNIT FOR CONTROL SERVES CORRESPONDING INDOOR FAN COIL. PROVIDE 208VAC,1-PHASE CONNECTION TO OUTDOOR HEAT PUMP. PANEL'lR1' 3 400 7 38908 39692 34715 SEAL:
<br /> >_ COORDINATE FINAL LOCATION OF UNIT AND ALL CONTROL CONDUITS REQUIRED WI MC PRIOR TO ROUGH-IN PANEL'2C' 3 250 8 28691 28691 28691
<br /> SERVES CORRESPONDING INDOOR FAN COIL. PROVIDE 208VAC,1-PHASE CONNECTION TO OUTDOOR HEAT PUMP. PANEL'2D' 3 250 9 25538 25538 25538
<br /> HP-5 HEAT PUMP 5 ROOF 208 1 23 30 - 30A,2P,NON-FUSED 3R 3H -2,4 1/2"C W/(2)#10 CU+(1)#10 CU GND SEE CORRESPONDING FAN COIL UNIT FOR CONTROL COORDINATE FINAL LOCATION OF UNIT AND ALL CONTROL CONDUITS REQUIRED W/MC PRIOR TO ROUGH-IN 10
<br /> PHOTOVOLTAIC SOLAR SYSTEM NOTE 5 3 125 11
<br /> HP-6 HEAT PUMP 6 ROOF 208 1 27 40 - 30A,2P,NON-FUSED 3R 3H -6,8 1/2"C WI(2)#10 CU+(1)#10 CU GND SEE CORRESPONDING FAN COIL UNIT FOR CONTROL SERVES CORRESPONDING INDOOR FAN COIL. PROVIDE 208VAC,1-PHASE CONNECTION TO OUTDOOR HEAT PUMP. 12 QR S�ON9
<br /> COORDINATE FINAL LOCATION OF UNIT AND ALL CONTROL CONDUITS REQUIRED WI MC PRIOR TO ROUGH-IN EV CAPABLE FUTURE EVCS 2 40 13 2080 2080 Q`�p,N J.
<br /> EV CAPABLE FUTURE EVCS 2 40 14 2080 2080 �� c
<br /> - 30A,2P,NON-FUSED 3R 3H -10,12 SERVES CORRESPONDING INDOOR FAN COIL. PROVIDE 208VAC,1-PHASE CONNECTION TO OUTDOOR HEAT PUMP. EV CAPABLE FUTURE EVCS 2 40 15 2080 2080
<br /> HP-7 HEAT PUMP 7 ROOF 208 1 14 20 m
<br /> 1/2"C W/(2)#12 CU+(1)#12 CU GND SEE CORRESPONDING FAN COIL UNIT FOR CONTROL COORDINATE FINAL LOCATION OF UNIT AND ALL CONTROL CONDUITS REQUIRED W/MC PRIOR TO ROUGH-IN EV CAPABLE FUTURE EVCS 2 40 16 2080 2080 No. E 21841 A
<br /> h EV CAPABLE FUTURE EVCS 2 40 17 2080 2080 EXP:03/31/2019
<br /> HP-8 HEAT PUMP 8 ROOF 208 3 28 35 30A,3P,NON-FUSED 3R 3H -14,16,18 SERVES CORRESPONDING INDOOR FAN COIL. PROVIDE 208VAC,3-PHASE CONNECTION TO OUTDOOR HEAT PUMP. EV CAPABLE FUTURE EVCS 2 40 18 2080 2080
<br /> 1/2"C W/(3)#10 CU+(1)#10 CU GND SEE CORRESPONDING FAN COIL UNIT FOR CONTROL kCOORDINATE FINAL LOCATION OF UNIT AND ALL CONTROL CONDUITS REQUIRED WI MC PRIOR TO ROUGH-IN EV CAPABLE(FUTURE EVCS) 2 40 19 2080 2080 s �Q
<br /> m EV CAPABLE FUTURE EVCS 2 40 20 2080 2080 TgTF OF C AC'Vr
<br /> Lu
<br /> EF-1 EXHAUST FAN 1 LEVEL 1 120 1 5.5 20 - 0.17 1-POLE SWITCH 1 1H -18 1/2"C W/(2)#12 CU+(1)#12 CU GND CONTINUOUS PROVIDE 120VAC CONNECTION TO FAN. COORDINATE LOCATION WIMC PRIOR TO ROUGH-IN. 21
<br /> 22 04/15/2019
<br /> m DEDICATED OUTSIDE AIR UNIT DOAS-1) 3 175 23 17535 17535 17535
<br /> EF-2 EXHAUST FAN 2 LEVEL 1 120 1 5.5 20 - 0.17 1-POLE SWITCH 1 1H -20 1/2"C W/(2)#12 CU+(1)#12 CU GND CONTINUOUS PROVIDE 120VAC CONNECTION TO FAN. COORDINATE LOCATION WIMC PRIOR TO ROUGH-IN. ELEVATOR#1 PUBLIC 3 175 24 10555 10555 10555
<br /> PHASE TOTALS 263769 271745 266587
<br /> rz CONSULTANT:
<br /> -2.9%
<br /> EF-3 EXHAUST FAN 3 LEVEL 1 120 1 5.5 20 0.17 1-POLE SWITCH 1 1H -22 1/2"C WI(2)#12 CU+(1)#12 CU GND TIMECLOCK PROVIDE 120VAC CONNECTION TO FAN.SEE NOTE 3.COORDINATE LOCATION W/MC PRIOR TO ROUGH-IN.
<br /> TOTAL VA 802102 1.9%
<br /> F3 TOTAL AMPS 2228.1 -1.1%
<br /> EF-5 EXHAUST FAN 5 LEVEL 1 120 1 5.5 20 - 0.17 1-POLE SWITCH 1 1H -26 1/2"C W/(2)#12 CU+(1)#12 CU GND THERMOSTAT PROVIDE 120VAC CONNECTION TO FAN. COORDINATE LOCATION W/MC PRIOR TO ROUGH-IN.
<br /> 100.0%
<br /> NOEL
<br /> EF-6 EXHAUST FAN 6 LEVEL 1 120 1 5.5 20 - 0.17 1-POLE SWITCH 1 1H -28
<br /> 1/2"C WI(2)#12 CU+(1)#12 CU GND TIMECLOCK PROVIDE 120VAC CONNECTION TO FAN.SEE NOTE 3.COORDINATE LOCATION W/MC PRIOR TO ROUGH-IN. 1. 'MSB'SHALL BE EQUIPPED WITH AN INTEGRAL POWER QUALITY/ENERGY METER
<br /> m SIEMENS'SENTRON'#PAC3200 OR EQUAL
<br /> tp 2. MAIN BREAKER SHALL BE 100%RATED,W/FULLY-ADJUSTABLE,ELECTRONIC TRIP SETTINGS AND [7
<br /> EF-7 EXHAUST FAN 7 LEVEL 1 120 1 5.5 20 - 0.17 1-POLE SWITCH 1 1H -30 1/2"C W/(2)#12 CU+(1)#12 CU GND TIMECLOCK PROVIDE 120VAC CONNECTION TO FAN.SEE NOTE 3.COORDINATE LOCATION W/MC PRIOR TO ROUGH-IN. 3. 'MSB'SHALL BE EQUIPPED WITH AN INTEGRAL 200KA SURGE PROTECTION MODULE AND SURGE COUNTER WI ENGINEERING SYSTEM SOLUTIONS
<br /> LL INTEGRAL DISCONNECT(BASIS OF DESIGN:SIEMENS#TPS3-E05-20X OR APPROVED EQUAL) STRUCTURAL•MEP•BUILDING COMMISSIONIN
<br /> EF-8 EXHAUST FAN 8 LEVEL 1 120 1 5.5 20 - 0.17 1-POLE SWITCH 1 1H -32 1/2"C W/(2)#12 CU+ 1 #12 CU GND CONTINUOUS PROVIDE 120VAC CONNECTION TO FAN. COORDINATE LOCATION W/MC PRIOR TO ROUGH-IN. 4. FOR ELEVATOR SHUNT TRIP DISCONNECT EQUIPPED W/N.O.CONTACTS FOR ELEVATOR CONTROL,FIRE ALARM BUILDING RELATIONSHIPS
<br /> O VOLTAGE MONITORING RELAY,KEY-TO-TEST SWITCH AND PILOT LIGHT. COORDINATE EXACT MOTOR HP&ERAGE EXCEEDING EXPECTATIONS
<br /> REQUIREMENTS W/ELEVATOR CONTRACTOR PRIOR TO ORDERING SWITCH(ESTIMATED AT 30HP) www.es2eng.com
<br /> EF-9 EXHAUST FAN 9 LEVEL 1 120 1 5.5 20 - 0.17 1-POLE SWITCH 1 1H -34 1/2"C WIO 2 #12 CU+ 1 O#12 CU GND THERMOSTAT PROVIDE 120VAC CONNECTION TO FAN. COORDINATE LOCATION W/MC PRIOR TO ROUGH-IN. (BASIS OF DESIGN:BUSSMANN'POWER MODULE'OR APPROVED EQUAL) 4943 NORTH 29TH EAST,STE A
<br /> 5. CIRCUIT BREAKER FOR SOLAR PHOTOVOLTAIC SYSTEM SHALL BE LOCATED AT THE OPPOSITE END OF THE DISTRIBUTION IDAHO FALLS,IDAHO 83401
<br /> BUSSING FROM THE INCOMING UTILITY CONNECTION. PHONE:(208)552-9874
<br /> EF-10 EXHAUST FAN 10 LEVEL 2 120 1 5.5 20 - 0.17 1-POLE SWITCH 1 1H -36 1/2"C WI(2)#12 CU+(1)#12 CU GND TIMECLOCK PROVIDE 120VAC CONNECTION TO FAN.SEE NOTE 3.COORDINATE LOCATION W/MC PRIOR TO ROUGH-IN. JOB NUMBER: 17.1019
<br /> ELECTRICAL DEMAND SUMMARY FOR 'MSB' sE°`"B°" °�'°"s""E IX �"�'"°°�" °`�°M`°TEN
<br /> SYSTEMSOLHTMNSANDSHALLNOTBEREPRODUCEDM FORMWITHOUT WRITTEN
<br /> CONSENT.ALLRbHTS ARE RESERVED.COPYRIGHT 2018 ENGEJEEREJG SYSTEM SOLUTIONS
<br /> EF-11 EXHAUST FAN 11 LEVEL 2 120 1 5.5 20 0.17 1-POLE SWITCH 1 1H -38 1/2"C M(2)#12 CU+(1)#12 CU GND CONTINUOUS PROVIDE 120VAC CONNECTION TO FAN. COORDINATE LOCATION MMC PRIOR TO ROUGH-IN.
<br /> CALCULATED CONTINUOUS LIGHTING LOAD VA 23017
<br /> 125%CONTINUOUS LOAD FACTOR 125%
<br /> EF-12 EXHAUST FAN 12 LEVEL 2 120 1 5.5 20 0.17 1-POLE SWITCH 1 1H -40 1/2"C WI(2)#12 CU+(1)#12 CU GND THERMOSTAT PROVIDE 120VAC CONNECTION TO FAN. COORDINATE LOCATION W/MC PRIOR TO ROUGH-IN. PER'CEC'210.20(A) VA 28771
<br /> AMPS 80.0
<br /> EF-13 EXHAUST FAN 13 LEVEL 1 120 1 5.5 20 0.17 1-POLE SWITCH 1 1P -6 3/4"C W/(2)#8 CU+(1)#8 CU GND CONTINUOUS PROVIDE 120VAC CONNECTION TO FAN. COORDINATE LOCATION W/MC PRIOR TO ROUGH-IN. CONNECTED HOTEL RECEPTACLE LOAD: VA 65178.0
<br /> FIRST 20KVA: 50% O
<br /> 20.001 KVA TO 100KVA 40%
<br /> EF-14 EXHAUST FAN 14 LEVEL 3 120 1 5.5 20 - 0.17 1-POLE SWITCH 1 3H -20 1/2"C WI(2)#12 CU+(1)#12 CU GND WALL SWITCH PROVIDE 120VAC CONNECTION TO FAN. COORDINATE LOCATION W/MC PRIOR TO ROUGH-IN. OVER 100KVA 30% �'
<br /> VA 28071
<br /> EF-15 EXHAUST FAN 15 LEVEL 3 120 1 5.5 20 - 0.17 1-POLE SWITCH 1 3H -22 1/2"C W/(2)#12 CU+(1)#12 CU GND CONTINUOUS PROVIDE 120VAC CONNECTION TO FAN. COORDINATE LOCATION W/MC PRIOR TO ROUGH-IN. PER'CEC'TABLE 220.42 AMPS 78.0 H H o 5 U � 'r IE 5
<br /> CONNECTED HVAC EQUIPMENT LOAD: 332410
<br /> EF-16 EXHAUST FAN 16 LEVEL 3 120 1 5.5 20 - 0.17 1-POLE SWITCH 1 3H -24 1/2"C WI(2)#12 CU+(1)#12 CU GND THERMOSTAT PROVIDE 120VAC CONNECTION TO FAN. COORDINATE LOCATION W/MC PRIOR TO ROUGH-IN. AMPS 923.8 u u u u U u U
<br /> LARGEST MOTOR(30 HP) VA 31666
<br /> EF-17 EXHAUST FAN 17 LEVEL 1 120 1 5.5 20 - 0.17 1-POLE SWITCH 1 1P -8 3/4"C W/(2)#8 CU+(1)#8 CU GND INTERLOCK WITH LIGHTS PROVIDE 120VAC CONNECTION TO FAN. COORDINATE LOCATION W/MC PRIOR TO ROUGH-IN. DEMAND FACTOR: AMPS 125%
<br /> PER'CEC'(430.24) 7916
<br /> AMPS 22.0
<br /> EF-18 EXHAUST FAN 18 LEVEL 1 120 1 5.5 20 0.17 1-POLE SWITCH 1 1H -42 1/2"C WI(2)#12 CU+(1)#12 CU GND CONTINUOUS PROVIDE 120VAC CONNECTION TO FAN. COORDINATE LOCATION W/MC PRIOR TO ROUGH-IN.
<br /> CONNECTED MOTOR LOAD: VA 82818
<br /> EF-19 EXHAUST FAN 19 LEVEL 1 120 1 5.5 20 0.17 1-POLE SWITCH 1 1H -44 1/2"C W/(2)#12 CU+(1)#12 CU GND TIMECLOCK PROVIDE 120VAC CONNECTION TO FAN.SEE NOTE 3.COORDINATE LOCATION W/MC PRIOR TO ROUGH-IN. AMPS 230.2
<br /> CONNECTED KITCHEN EQUIPMENT LOAD: VA 221976
<br /> EF-A EXHAUST FAN 18 GUESTROOMS 120 1 5.5 20 0.17 1-POLE SWITCH 1 SEE GUEST ROOM PANEL DEMAND FACTOR: 65%
<br /> SCHEDULES 1/2"C WI(2)#12 CU+(1)#12 CU GND HUMIDISTAT EC TO PROVIDE HUMIDITY SENSOR SWITCH.SEE NOTE 4.LOCATE ADJACENT TO BATHROOM LIGHT SWITCH.
<br /> (PER'CEC'TABLE 220.56) VA 144284 Q
<br /> AMPS 401.0 z
<br /> EH-1 ELECTRIC WALL HEATER 1 LEVEL 1 208 1 14 20 2.3 INTEGRAL 1 1H -2,4 1/2"C W/(2)#10 CU+(1)#10 CU GND PROVIDE BACK BOX W/MUDRING FOR T-STAT/SENSOR AND 1/2"C W/PULL LINE FOR CONTROL WIRING COORDINATE LOCATION OF BOTH HEATER AND REMOTE T-STAT W/MC PRIOR TO ROUGH-IN O
<br /> (BY MC) ALL OTHER LOADS VA 84619 E_
<br /> AMPS 235.2 J
<br /> EH-2 ELECTRIC WALL HEATER 2 LEVEL 1 208 1 7.25 20 1.1 INTEGRAL 1 1H -6,8 1/2"C WI(2)#12 CU+(1)#12 CU GND PROVIDE BACK BOX W/MUDRING FOR T-STAT/SENSOR AND 1/2"C WIPULL LINE FOR CONTROL WIRING COORDINATE LOCATION OF BOTH HEATER AND REMOTE T-STAT W/MC PRIOR TO ROUGH-IN O U
<br /> (BY MC) TOTAL LOAD VA 700974
<br /> AMPS 1948.0
<br /> EH-3 ELECTRIC WALL HEATER 3 LEVEL 1 208 1 14 20 2.3 INTEGRAL 1 1H -10,12 1/2"C WI(2)#10 CU+(1)#10 CU GND PROVIDE BACK BOX W/MUDRING FOR T-STAT/SENSOR AND 1/2"C W/PULL LINE FOR CONTROL WIRING COORDINATE LOCATION OF BOTH HEATER AND REMOTE T-STAT W/MC PRIOR TO ROUGH-IN
<br /> (BY MC) 'MSB'RATED SIZE: AMPS 2000
<br /> PROVIDE BACK BOX W/MUDRING FOR T-STAT/SENSOR AND 1/2"C W/PULL LINE FOR CONTROL WIRING 'MSB'CONNECTED AMPACITY(100%): 2000
<br /> EH 4 ELECTRIC WALL HEATER 4 LEVEL 1 208 1 7.25 20 1.1 INTEGRAL 1 1 H -14,16 1/2"C W/(2)#12 CU+(1)#12 CU GND (BY MC) COORDINATE LOCATION OF BOTH HEATER AND REMOTE T-STAT WIMC PRIOR TO ROUGH-IN SPARE CAPACITY ON'MSB': AMPS 52
<br /> EH-5 ELECTRIC WALL HEATER 5 LEVEL 1 208 1 7.25 20 1.1 INTEGRAL 1 1 P -20,22 1/2"C WI(2)#12 CU+(1)#12 CU GND PROVIDE BACK BOX W/MUDRING FOR T-STAT/SENSOR AND 112"C W/PULL LINE FOR CONTROL WIRING COORDINATE LOCATION OF BOTH HEATER AND REMOTE T-STAT W/MC PRIOR TO ROUGH-IN
<br /> (BY MC)
<br /> EH-6 ELECTRIC WALL HEATER 6 LEVEL 1 208 1 13.5 20 2.3 INTEGRAL 1 1P -24,26 1/2"C W/(2)#12 CU+(1)#12 CU GND PROVIDE BACK BOX W/MUDRING FOR T-STAT/SENSOR AND 1/2"C W/PULL LINE FOR CONTROL WIRING COORDINATE LOCATION OF BOTH HEATER AND REMOTE T-STAT W/MC PRIOR TO ROUGH-IN
<br /> (BY MC)
<br /> PT-A PACKAGED TERMINAL AC UNIT A GUESTROOMS 208 1 9.7 15 - CORD&PLUG 1 SEE GUEST ROOM PANEL 1/2"C WI(2)#12 CU+ 1 #12 CU GND PROVIDE 4-SQ BACK BOX W/1-GANG MUDRING FOR REMOTE T-STAT(BY MC)&1/2"C W/PULL LINE PROVIDE NEMA 6-15R FOR POWER CONNECTION(VERIFY W/MC FOR UNIT CORD CONFIGURATION). COORDINATE AL
<br /> SCHEDULES ( ) FROM PTAC UNIT TO T-STAT FOR CONTROL WIRING(BY MC) CONTROL CONDUITS WITH MC REQUIRED BEFORE ROUGH-IN
<br /> OVIDE 208VAC,
<br /> AC-1 MINI SPLIT UNIT 1 LEVEL 1 208 1 1 15 2-POLE SWITCH 1 SEE CU-1 PROVIDE 4-SQ BACKBOX WI 1-GANG MUDRING FOR T-STAT NE(BY FROM
<br /> &INDOOR
<br /> R PULL LINE TO UNIT FOR NPHAOSE CONNECTION AND INTERCONNECTIOR MINI SPLIT UNIT POWERED AND N COMPLETE OPERATION.LLED FROM OUTDOOR •COORDINATE ALENSING UNIT. L CONTROL CONDUITS o
<br /> 1/2"C WI(2)#12 CU+(1)#12 CU GND CONTROL WIRING(BY MC). ALSO PROVIDE 1l2"C W/PULL LINE FROM INDOOR UNIT TO OUTDOOR UNIT �
<br /> FOR CONTROL WIRING BY MC W/MC PRIOR TO ROUGH-IN
<br /> PROVIDE 4-SQ BACKBOX W/1-GANG MUDRING FOR T-STAT(BY MC)&1/2"C W/PULL LINE TO UNIT FOR INDOOR MINI SPLIT UNIT POWERED AND CONTROLLED FROM OUTDOOR CONDENSING UNIT. PROVIDE 208VAC,
<br /> AC-2 MINI SPLIT UNIT 2 LEVEL 1 208 1 1 15 2-POLE SWITCH 1 SEE CU-2 1/2"C WI(2)#12 CU+(1)#12 CU GND CONTROL WIRING(BY MC). ALSO PROVIDE 1/2"C W/PULL LINE FROM INDOOR UNIT TO OUTDOOR UNIT 1-PHASE CONNECTION AND INTERCONNECTION FOR COMPLETE OPERATION. COORDINATE ALL CONTROL CONDUITS
<br /> FOR CONTROL WIRING BY MC W/MC PRIOR TO ROUGH-IN a
<br /> OVIDE 208VAC,
<br /> AC-3 MINI SPLIT UNIT 3 LEVEL 1 208 1 1 15 2-POLE SWITCH 1 SEE CU-3 PROVIDE 4-SQ BACKBOX WI 1-GANG MUDRING FOR T-STAT NE(BY FROM
<br /> &INDOOR
<br /> R PULL LINE TO UNIT FOR INPHASE CONNECTION AND INTERCONNECTION OOR MINI SPLIT UNIT POWERED AND OFOR COMPLETE OPERATIONLLED FROM OUTDOOR .000RDINA E AENSING UNIT. L CONTROL CONDUITS
<br /> 1l2"C WI(2)#12 CU+(1)#12 CU GND CONTROL WIRING(BY MC). ALSO PROVIDE 1l2"C W/PULL LINE FROM INDOOR UNIT TO OUTDOOR UNIT
<br /> FOR CONTROL WIRING BY MC W/MC PRIOR TO ROUGH-IN
<br /> FC-1 FAN COIL 1 LEVEL 1 208 1 10 15 _ 2-POLE SWITCH 1 1H -1,3 1/2"C WI(2)#12 CU+(1)#12 CU GND PROVIDE 4-SQ BACKBOX W/1-GANG MUDRING FOR T-STAT(BY MC)&1/2"C W/PULL LINE TO UNIT FOR COORDINATE LOCATION OF THERMOSTAT W/MC PRIOR TO ROUGH-IN.
<br /> CONTROL WIRING(BY MC). COORDINATE ALL CONTROL WIRING LOCATIONS WITH MC.
<br /> O
<br /> FC-2 FAN COIL 2 LEVEL 1 208 1 10 15 _ 2-POLE SWITCH 1 1H -5,7LL
<br /> 1/2"C WI(2)#12 CU+(1)#12 CU GND PROVIDE 4-SQ BACKBOX W/1-GANG MUDRING FOR T-STAT(BY MC)&112"C W/PULL LINE TO UNIT FOR COORDINATE LOCATION OF THERMOSTAT W/MC PRIOR TO ROUGH-IN. LL
<br /> CONTROL WIRING(BY MC). COORDINATE ALL CONTROL WIRING LOCATIONS WITH MC. 0 ULF
<br /> z O
<br /> FC-3 FAN COIL 3 LEVEL 1 208 1 10 15 _ 2-POLE SWITCH 1 1 H -9,11 1/2"C WI(2)#12 CU+(1)#12 CU GND PROVIDE 4-SQ BACKBOX WI 1-GANG MUDRING FOR T-STAT(BY MC)&1l2"C W/PULL LINE TO UNIT FOR COORDINATE LOCATION OF THERMOSTAT WI MC PRIOR TO ROUGH-IN. Q
<br /> m CONTROL WIRING(BY MC). COORDINATE ALL CONTROL WIRING LOCATIONS WITH MC.
<br /> FC4 FAN COIL 4 LEVEL 1 208 1 10 15 2-POLE SWITCH 1 1 H 13,15 1/2"C WI2 #12 CU+ 1 #12 CU GND PROVIDE 4-SQ BACKBOX WI 1-GANG MUDRING FOR T-STAT(BY MC)&112"C W/PULL LINE TO UNIT FOR COORDINATE LOCATION OF THERMOSTAT W/MC PRIOR TO ROUGH-IN. z
<br /> ( ) ( ) CONTROL WIRING(BY MC). COORDINATE ALL CONTROL WIRING LOCATIONS WITH MC. O
<br /> FC-5 FAN COIL 5 LEVEL 1 208 1 10 152-POLE SWITCH 1 1 H -17,19 PROVIDE 4-SQ BACKBOX W/1-GANG MUDRING FOR T-STAT(BY MC)&1/2"C W/PULL LINE TO UNIT FOR COORDINATE LOCATION OF THERMOSTAT W/MC PRIOR TO ROUGH-IN.
<br /> _ 1/2"C WI(2)#12 CU+(1)#12 CU GND CONTROL WIRING(BY MC). COORDINATE ALL CONTROL WIRING LOCATIONS WITH MC. a _
<br /> C/) D
<br /> FC-6 FAN COIL 6 LEVEL 1 208 1 10 15 _ 2-POLE SWITCH 1 1 H -21,23 1/2"C W/(2)#12 CU+(1)#12 CU GND PROVIDE 4-SQ BACKBOX WI 1-GANG MUDRING FOR T-STAT(BY MC)&1l2"C W/PULL LINE TO UNIT FOR COORDINATE LOCATION OF THERMOSTAT W/MC PRIOR TO ROUGH-IN. O
<br /> CONTROL WIRING(BY MC). COORDINATE ALL CONTROL WIRING LOCATIONS WITH MC. U
<br /> FC-7 FAN COIL 7 LEVEL 1 208 1 10 15 2-POLE SWITCH 1 1 H -25,27 1/2"C WI(2)#12 CU+(1)#12 CU GND PROVIDE 4-SQ BACKBOX W/1-GANG MUDRING FOR T-STAT(BY MC)&1/2"C W/PULL LINE TO UNIT FOR COORDINATE LOCATION OF THERMOSTAT W/MC PRIOR TO ROUGH-IN.
<br /> 2- - CONTROL WIRING(BY MC). COORDINATE ALL CONTROL WIRING LOCATIONS WITH MC.
<br /> FC-8 FAN COIL 8 LEVEL 1 208 1 10 15 - 2-POLE SWITCH 1 1 H -29,31 1/2"C WI(2)#12 CU+(1)#12 CU GND PROVIDE 4-SQ BACKBOX W/1-GANG MUDRING FOR T-STAT(BY MC)&1/2"C W/PULL LINE TO UNIT FORCOORDINATE LOCATION OF THERMOSTAT W/MC PRIOR TO ROUGH-IN.
<br /> _ - CONTROL WIRING(BY MC). COORDINATE ALL CONTROL WIRING LOCATIONS WITH MC.
<br /> INDOOR MINI SPLIT UNIT POWERED AND CONTROLLED FROM OUTDOOR CONDENSING UNIT. PROVIDE 208VAC, REVISIONS:
<br /> CU-1 CONDENSING UNIT 1 ROOF 208 1 18 30 30A,2P,NON-FUSED 3R 3H -17,19 1/2"C W/(2)#10 CU+(1)#10 CU GND PROVIDE 1/2"M PULL LINE FROM OUTDOOR UNIT TO INDOOR UNIT FOR CONTROL WIRING(BY MC) 1-PHASE CONNECTION AND INTERCONNECTION FOR COMPLETE OPERATION. COORDINATE ALL CONTROL CONDUITS 1 BLDG DEPT 10/12/18
<br /> W/MC PRIOR TO ROUGH-IN 2 FRANCHISE 11/06/18
<br /> INDOOR MINI SPLIT UNIT POWERED AND CONTROLLED FROM OUTDOOR CONDENSING UNIT. PROVIDE 208VAC,
<br /> CU-2 CONDENSING UNIT 2 ROOF 208 1 18 30 30A,2P,NON-FUSED 3R 3H -21,23 1/2"C W/(2)#10 CU+(1)#10 CU GND PROVIDE 1/2"W/PULL LINE FROM OUTDOOR UNIT TO INDOOR UNIT FOR CONTROL WIRING(BY MC) 1-PHASE CONNECTION AND INTERCONNECTION FOR COMPLETE OPERATION. COORDINATE ALL CONTROL CONDUITS
<br /> W/MC PRIOR TO ROUGH-IN
<br /> INDOOR MINI SPLIT UNIT POWERED AND CONTROLLED FROM OUTDOOR CONDENSING UNIT. PROVIDE 208VAC,
<br /> CU-3 CONDENSING UNIT 3 ROOF 208 1 18 30 30A,2P,NON-FUSED 3R 3H -25,27 1/2"C W/(2)#10 CU+(1)#10 CU GND PROVIDE 1/2"WI PULL LINE FROM OUTDOOR UNIT TO INDOOR UNIT FOR CONTROL WIRING(BY MC) 1-PHASE CONNECTION AND INTERCONNECTION FOR COMPLETE OPERATION. COORDINATE ALL CONTROL CONDUITS
<br /> W/MC PRIOR TO ROUGH-IN
<br /> -a
<br /> m
<br /> L
<br /> EIWH-1 ELEC.INSTANT.WATER HEATER 1 LEVEL 1 120 1 25 40 3 1-POLE SWITCH 1 1P -14 3/4"C W/(2)#6 CU+(1)#6 CU GND PROVIDE 120VAC CONNECTION TO INSTANTANEOUS WATER HEATER
<br /> EIWH-2 ELEC.INSTANT.WATER HEATER 2 LEVEL 1 208 1 64 80 13.3 100A,2P,NON-FUSED 1 1 P -16,18 1"C W/(2)#4 CU+(1)#8 CU GND PROVIDE 208VAC CONNECTION TO INSTANTANEOUS WATER HEATER
<br /> C33 WH-1 GAS-FIRED WATER HEATER 1 LEVEL 1 120 1 4 20 - 1-POLE SWITCH 1 1PL -4 1/2"C W/(2)#12 CU+(1)#12 CU GND PROVIDE 120VAC CONNECTION TO GAS FIRED WATER HEATER BA PROJECT# 161010
<br /> PLN PROJECT# 17077
<br /> 9' WH-2 GAS-FIRED WATER HEATER 2 LEVEL 1 120 1 4 20 1-POLE SWITCH 1 1PL -6 1/2"C W/(2)#12 CU+(1)#12 CU GND PROVIDE 120VAC CONNECTION TO GAS FIRED WATER HEATER MARRIOTT# 4476
<br /> Fcn WH-3 GAS-FIRED WATER HEATER 3 LEVEL 1 120 1 4 20 - 1-POLE SWITCH 1 1PL -8 T1/2"C WI2 #12 CU+ 1 #12 CU GND PROVIDE 120VAC CONNECTION TO GAS FIRED WATER HEATER
<br /> U ( ) ( ) PERMIT# -
<br /> DOAS-1 DEDICATED OUTSIDE AIR SYSTEM 1 ROOF 208 3 146 175 - 200A,3P,NON-FUSED 3R MSB -34 1-1/2"C W/(3)#1/0 CU+(1)#6 CU PROVIDE 4-SQ BACKBOX W/1-GANG MUDRING FOR T-STAT/SENSOR(BY MC)&1/2"C W/PULL LINE TO PROVIDE 208VAC,3-PHASE POWER CONNECTION TO DISCONNECT PROVIDED WIUNIT. ALSO PROVIDE 120VAC APN# 058-66-012
<br /> GND UNIT FOR CONTROL WIRING(BY MC) CONNECTION FROM BRANCH CIRCUIT INDICATED TO CONVENIENCE RECEPTACLE PROVIDED W/UNIT.
<br /> t
<br /> Q CP-1 CIRCULATOR PUMP 1 LEVEL 1 120 1 7.25 20 0.2 1-POLE SWITCH 1 1PL -5 1/2"C W/(2)#12 CU+( )#12 CU GND 1 ROUGH-IN.PROVIDE 120V CONNECTION TO CIRC PUMP.COORDINATE LOCATION W/PLUMBING CONTRACTOR PRIOR TO DATE: 4/15/19
<br /> 0 CP-2 CIRCULATOR PUMP 2 LEVEL 1 120 1 7.25 20 0.2 1-POLE SWITCH 1 1PL -7 1/2"C WI(2)#12 CU+(1)#12 CU GND PROVIDE 120V CONNECTION TO CIRC PUMP.COORDINATE LOCATION W/PLUMBING CONTRACTOR PRIOR TO DRAWN: DWROUGH-IN.
<br /> CHECKED: JC
<br /> WS-1 WATER SOFTENER 1 LEVEL 2 120 1 10 20 1-POLE SWITCH 1 1PL -10 1/2"C W/(2)#12 CU+(1)#12 CU GND PROVIDE 120VAC CONNECTION TO WATER SOFTENER
<br /> BP-1 BOOSTER PUMP 1 LEVEL 1 208 3 82.3 100 (3)@ 100A,3P,NON-FUSED 1 1PL -9,11,13 1-1/4"C W/(3)#3 CU+(1)#8 CU GND COORDINATE ALL CONTROL WIRING WITH MC PRIOR TO ROUGH-IN BOOSTER PUMP TO HAVE A TOTAL OF 3 PUMPS.2 PUMPS SEQUENCED AND 1 PUMP TO BE STANDBY.PROVIDE WITH
<br /> SHEET TITLE:
<br /> 7,5 SINGLE POINT CONNECTION.ELECTRICAL SIZED TO HANDLE LOAD OF 3 PUMPS RUNNING AT THE SAME TIME. ELECTRICAL
<br /> NOTES: SCHEDULES
<br /> 1.VERIFY FINAL LOADS OF ACTUAL EQUIPMENT INSTALLED WITH MECHANICAL CONTRACTOR PRIOR TO PURCHASING AND INSTALLATION OF THE ASSOCIATED ELECTRICAL EQUIPMENT.
<br /> 2.VERIFY FINAL EQUIPMENT LOCATIONS W/OTHER TRADES PRIOR TO ROUGH-IN
<br /> 3: PROVIDE 24-HOUR,DIGITAL PROGRAMMABLE ASTRONOMIC TIMER SWITCH(BASIS-OF-DESIGN:LEGRAND(P&S)#RT24 OR EQUAL).LOCATE SWITCH ADJACENT TO ROOM LIGHTING CONTROL DEVICE.COORDINATE EXACT LOCATION W/GC PRIOR TO ROUGH-IN.
<br /> 4: PROVIDE HUMIDITY SENSOR SWITCH BASIS-OF-DESIGN:LEVITON#IPHS5-lLW OR EQUAL).