Laserfiche WebLink
GAS METER <br />NOTES: <br />A. GAS COMPANY TO PROVIDE 2700 MBH AT 2 PSI <br />DOWNSTREAM OF METER TO SERVE BUILDING. <br />B. GAS PIPING SIZED PER LONGEST LENGTH METHOD PER <br />TABLES 1216.2(1) AND 1216.2(4) OF THE CPC. <br />C. MAXIMUM EQUIVALENT LENGTH FROM METER TO THE MOST <br />REMOTE OUTLET OF 400'. <br />D. 11 IN. W.C. PIPING SIZED DOWNSTREAM OF THE EACH <br />REGULATOR AT THE MAXIMUM EQUIVALENT LENGTHS <br />SHOWN NEAR EACH REGULATOR. <br />E. ALL GAS CONNECTIONS TO EQUIPMENT TO BE PROVIDED <br />WITH A SEDIMENT TRAP WITH EXCEPTION TO CLOTHES <br />DRYERS INSTALL ALL GAS CONNECTIONS TO APPLIANCES <br />PER MANFUCTURERS RECOMMENDATIONS AND LOCAL <br />JURISDICTION REQUIREMENTS. <br />F. PROVIDE ACCESS TO ALL VALVES AND REGULATORS. <br />G. PROVIDE VALVED FINAL CONNECTION TO ALL GAS FIRED <br />EQUIPMENT. <br />H. VENT ALL REGULATORS TO BUILDING EXTERIOR PER LOCAL <br />JURISDICTION REQUIREMENTS. <br />EMERGENCY <br />SHUTOFF <br />VALVE <br />SEISMIC ACUATED <br />SHUTOFF VALVE TO BE <br />MOUNTED RIGIDLY ON <br />EXTERIOR WALL PER <br />LOCAL JURISDICTION <br />REQUIREMENTS. <br />2"ø <br />WH-1 <br />399.9 MBH <br />WH-2 <br />399.9 MBH <br />WH-3 <br />399.9 MBH <br />40 FT <br />1 1/4"ø <br />1 1/4"ø <br />1 1/4"ø <br />DRYER <br />225 MBH <br /> DRYER <br />270 MBH <br />30 FT <br />DOAS-1 <br />405 MBH <br />50 FT <br />1 1/2"ø <br />POOL & SPA <br />600 MBH <br />30 FT <br />1 1/2"ø <br />1"ø <br />1"ø <br />1"ø <br />2"ø <br />2"ø <br />1 1/4"ø <br />1"ø1"ø <br />1 1/4"ø 1 1/4"ø1 1/4"ø <br />DHWR-120° <br />DHW-165°F <br />DHW-120° <br />U-DCW <br />WH-3 WH-2 WH-1 <br />ET-1 <br />MV-1 <br />CP-1 <br />TO BUILDING <br />SDCW <br />WS-1 <br />4"ø <br />2"ø <br />2"ø <br />4"ø <br />3"ø <br />2"ø <br />4"ø <br />4"ø <br />4"ø <br />4"ø <br />3"ø <br />3"ø <br />4"ø <br />3"ø <br />2"ø <br />3"ø <br />4"ø <br />4"ø <br />3"ø <br />FROM BP-1 <br />3"ø <br />2"ø 2"ø 2"ø 2"ø 2"ø 2"ø <br />SOLAR PIPING TO <br />ROOF SEE P1.1B <br />AND P1.4 FOR <br />CONTINUATION <br />FUTURE <br />SOLAR <br />TANK <br />1"ø <br />PROVIDE BALL <br />VALVE ON VERTICAL <br />PIPE <br />N.O. <br />N.C. <br />N.O. <br />3"ø <br />TO LAUNDRY <br />TO BUILDING <br />TO BUILDING <br />TO BUILDING <br />NOTES: <br />1. NC: NORMALLY CLOSE <br />2. NO: NORMALLY OPEN <br />A. ONE UNSOFTENED DOMESTIC WATER LINE <br />TO RUN TO SILLCOCKS, POOL, JUICE AND <br />COFFEE DISPENSERS, AND DRINKING <br />FOUNTAINS. SOFTENED DOMESTIC COLD <br />WATER LINE TO RUN TO ALL OTHER <br />FIXTURES. <br />B. WATER SOFTENER IS SHOWN AS ONE TANK <br />FOR CLARITY. REFER TO FLOOR PLANS AND <br />WATER SOFTENER SCHEDULE ON SHEET <br />P6.1 FOR WATER SOFTENER SIZE. <br />N.C. <br />2"ø <br />2"ø <br />2"ø <br />2"ø <br />2"ø <br />4"ø <br />CP-2 <br />DHWR-165° <br />2"ø <br />3/4"ø <br />2"ø <br />3"ø <br />STANDARD ABBREVIATIONS <br />PLUMBING SHEET INDEX <br />SHEET NO.SHEET TITLE REVISION <br />P0.1 GENERAL NOTES, SHEET INDEX, ABBREVIATIONS AND SYMBOLS <br />P1.1A PLUMBING FLOOR PLAN - LEVEL 1 (WASTE, VENT & GAS)4 <br />P1.1B PLUMBING FLOOR PLAN - LEVEL 1 ( DOMESTIC COLD WATER) <br />P1.1C PLUMBING FLOOR PLAN - LEVEL 1 (DOMESTIC HOT WATER) <br />P1.2 PLUMBING FLOOR PLAN - LEVEL 2 <br />P1.3 PLUMBING FLOOR PLAN - LEVEL 3 <br />P1.4 PLUMBING ROOF PLAN <br />P2.1 RISER DIAGRAMS <br />P5.1 PLUMBING DETAILS <br />P6.1 PLUMBING SCHEDULES 4 <br />(E) EXISTING <br />AFF ABOVE FINISHED FLOOR <br />AI ANALOG INPUT <br />ALT ALTERNATE <br />AO ANALOG OUTPUT <br />CAP. CAPACITY <br />CTG CLEANOUT TO GRADE <br />CV CONSTANT VOLUME <br />CWFU COLD WATER FIXTURE UNITS <br />DFU DRAINAGE FIXTURE UNITS <br />DI DIGITAL INPUT <br />DIA OR <br />Ø <br />DIAMETER <br />DO DIGITAL OUTPUT <br />DSN DOWNSPOUT NOZZLE <br />DW DISHWASHER <br />EFF EFFICIENCY <br />ELEV ELEVATION <br />EWT ENTERING WATER TEMPERATURE <br />FA FREE AREA <br />FCO FLOOR CLEANOUT <br />FD FLOOR DRAIN <br />FPM FEET PER MINUTE <br />FS FLOOR SINK <br />FT FEET <br />FW FRESH WATER <br />GA GAUGE <br />GAL GALLON <br />GD GARAGE DRAIN <br />GPM GALLONS PER MINUTE <br />HP HORSEPOWER <br />HR HOUR <br />HT HEIGHT <br />HWFU HOT WATER FIXTURE UNITS <br />IAQ INDOOR AIR QUALITY <br />IN. INCH <br />INWC INCHES OF WATER COLUMN <br />INWG INCHES OF WATER GAUGE <br />LBS POUNDS <br />LWT LEAVING WATER TEMPERATURE <br />MAX MAXIMUM <br />MBH THOUSAND BRITISH THERMAL UNITS/HOUR <br />MECH MECHANICAL <br />MIN MINIMUM <br />NC NOISE CRITERIA <br />NIC NOT IN CONTRACT <br />NO. NUMBER <br />NOM NOMINAL <br />NTS NOT TO SCALE <br />OD OVERFLOW DRAIN <br />OSA OUTSIDE AIR <br />PD PRESSURE DROP <br />PRV PRESSURE REDUCING VALVE <br />PSI POUNDS PER SQUARE INCH <br />PSIG POUNDS PER SQUARE INCH GAUGE <br />RD ROOF DRAIN <br />RPBP REDUCED PRESSURE BACKFLOW PREVENTER <br />SL SEA LEVEL <br />SP STATIC PRESSURE <br />SQ FT SQUARE FEET <br />SR STORY RISER <br />SS SERVICE SINK OR STAINLESS STEEL <br />TSP TOTAL STATIC PRESSURE <br />VAV VARIABLE AIR VOLUME <br />VFD VARIABLE FREQUENCY DRIVE <br />VOL VOLUME <br />VTR VENT THROUGH ROOF <br />W/ WITH <br />W/O WITHOUT <br />WCO WALL CLEANOUT <br />WPD WATER PRESSURE DROP <br />WT WEIGHT <br />ALL EQUIPMENT SELECTED AT SITE ELEVATION (150') UNLESS NOTED OTHERWISE. <br />SHEET# <br />SEC# <br />PLUMBING LEGEND <br />(TEMP)°F <br />CD <br />RD <br />OD <br />STORM DRAIN SD <br />FS <br />NG <br />CHS <br />CHR <br />CWS <br />CWR <br />HWS <br />HWR <br />S <br />RL <br />RS <br />GATE VALVE <br />OVERFLOW DRAIN <br />BALL VALVE <br />BUTTERFLY VALVE <br />MOTORIZED VALVE OPERATOR <br />CHECK VALVE (SWING OR LIFT AS REQ'D) <br />SOLENOID VALVE <br />AUTOMATIC CONTROL VALVE (2-WAY) <br />AUTOMATIC CONTROL VALVE (3-WAY) <br />PRESSURE REDUCING VALVE <br />P & T RELIEF VALVE <br />AIR VENT (AUTOMATIC) <br />STRAINER <br />CALIBRATED BALANCING VALVE <br />VENTURI FLOW METER <br />REDUCER VALVE <br />PET COCK OR GAUGE COCK <br />PRESSURE GAUGE W/GAUGE COCK <br />THERMOMETER <br />TEMPERATURE & PRESSURE TEST PLUG <br />PUMP <br />FLOW SWITCH <br />TEMPERATURE SENSOR <br />HOSE BIB OR SILLCOCK <br />YARD HYDRANT/ROOF HYDRANT <br />FLOOR DRAIN <br />FLOOR SINK <br />WALL CLEANOUT (WCO) <br />FLOOR CLEANOUT (FCO) <br />EXPANSION JOINT <br />FLEXIBLE PIPE CONNECTION <br />REDUCED PRESSURE BACKFLOW PREVENTER <br />DOUBLE CHECK BACKFLOW PREVENTER <br />WATER HAMMER ARRESTOR <br />ELBOW DOWN <br />ELBOW UP <br />PIPE CAP <br />TEE DOWN <br />UNION <br />DOMESTIC COLD WATER (DCW) <br />DOMESTIC HOT WATER (DHW) <br />DOMESTIC HOT WATER RECIRC. (DHWR) <br />DOMESTIC HOT WATER (SPECIFIED TEMP.) <br />SANITARY VENT (VT) <br />SANITARY SEWER ABOVE GRADE (SS) <br />SANITARY SEWER BELOW GRADE (SS) <br />CONDENSATE DRAIN <br />ROOF DRAIN OR EXTERIOR DRAIN <br />SECTION CUT LINE <br />FIRE SPRINKLER SERVICE <br />NATURAL GAS <br />HEAT TRACING <br />CHILLED WATER SUPPLY <br />CHILLED WATER RETURN <br />CONDENSOR WATER SUPPLY <br />CONDENSOR WATER RETURN <br />HEATING WATER SUPPLY <br />HEATING WATER RETURN <br />STEAM <br />REFRIGERANT LIQUID <br />REFRIGERANT SUCTION <br />POINT OF REMOVAL FROM EXISTING <br />POINT OF CONNECTION TO EXISTING <br />DETAIL TAG <br />KEYED NOTE <br />F <br />T <br />4 <br />P5.1 <br />P## <br />NOT ALL <br />SYMBOLS MAY BE <br />USED <br />LP LIQUID PROPANE <br />M <br />CLEANOUT TO GRADE (COTG) <br />GLOBE VALVE <br />PIPING BELOW GRADE (**SYS. ABR.)** <br />UNSOFTENED DOMESTIC COLD WATER (UDCW) <br />DOMESTIC HOT WATER RECIRC.DHWR (TEMP)°F <br />UDCW <br />(DHWR-SPECIFIED TEMP.)0 1/2"1/4" 1" 2"IF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT - SCALE ACCORDINGLYThis drawing, printed or otherwise, is the copyrighted property of RED Inc Architects . The drawing may not be used, reproduced or copied without the permission of RED Inc Architects.REVISIONS: <br />BA PROJECT #161010CONSTRUCTION DRAWINGS FOR:DATE: <br />DRAWN:LODICHECKED: <br />PLN PROJECT #17077 <br />MARRIOTT #4476 <br />PERMIT #-CALIFORNIAAPN #058-66-012 <br />SHEET TITLE: <br />SHEET NO.: <br />SEAL: <br />CONSULTANT: <br />RED INC ARCHITECTS <br />1217 J STREET, MODESTO, CA 95354 <br />209.522.890030" x 42"JOB NUMBER: <br />THESE PLANS, DRAWINGS AND DESIGNS ARE THE EXCLUSIVE PROPERTY OF ENGINEERING <br />SYSTEM SOLUTIONS AND SHALL NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN <br />CONSENT. ALL RIGHTS ARE RESERVED. COPYRIGHT 2018 ENGINEERING SYSTEM SOLUTIONS <br />4943 NORTH 29TH EAST, STE A <br />IDAHO FALLS, IDAHO 83401 <br />PHONE: (208) 552-9874 <br />ENGINEERING SYSTEM SOLUTIONS <br />STRUCTURAL • MEP • BUILDING COMMISSIONING <br />www.es2eng.com <br />BUILDING RELATIONSHIPS <br />EXCEEDING EXPECTATIONS <br />17.1019 <br />This drawing, printed or otherwise, is the copyrighted property of Burkett Architect PC . The drawing may not be used, reproduced or copied without the permission of Burkett Architect PCIF THIS SHEET IS NOT 30"x42", IT IS A REDUCED PRINT -SCALE ACCORDINGLY2"1"1/4"1/2"030" x 42"4/12/19 <br />P0.1 <br />GENERAL NOTES, <br />SHEET INDEX, <br />ABBREVIATIONS AND <br />SYMBOLS <br />ACS <br />HS <br />MINIMUM PLUMBING PIPING INSULATION THICKNESS <br />SYSTEM TYPES FLUID OPERATING TEMPERATURE <br />RANGE AND USAGE (°F) <br />CONDUCTIVITY <br />(BTU*IN/(h*FT²*°F)) <br />MEAN RATING <br />TEMPERATURE (°F)< 1 1 TO < 1 1/2 1 1/2 TO < 4 4 TO < 8 ≥ 8 <br />DHW (165°F), DHWR (165°F) 141 - 200 0.25 - 0.29 125 1.5 1.5 2.0 2.0 2.0 <br />DHW (120°F, 140°F), DHWR <br />(120°F, 140°F)105 - 140 0.21 - 0.28 100 1.0 1.0 1.5 1.5 1.5 <br />DCW 40 - 60 0.21 - 0.27 75 0.5 0.5 1.0 1.0 1.0 <br />NOTES: <br />1. BASED ON THE 2016 CALIFORNIA ENERGY CODE (CEC). <br />2. PROVIDE ALUMINUM JACKETS ON ALL PIPING INSULATION LOCATED EXTERIOR OF THE BUILDING. PROVIDE PVC JACKET ON ALL EXPOSED PIPING INSULATION IN <br />MECHANICAL ROOM. <br />3. INSULATE ALL ROOF DRAIN PIPING WITH MINIMUM 1/2" INSULATION. INSULATE ALL ROOF DRAIN AND OVERFLOW DRAIN BOWLS WITH MINIMUM 1"INSULATION. INSULATION <br />TO BE 0.27 BTU*IN/(H*FT2*°F). <br />4. PROVIDE PROTECTIVE SHIELDING PIPE COVERS ON ALL PIPES EXPOSED AT ADA PLUMBING FIXTURES. PROTECTIVE SHIELDING PIPE COVERS TO COMPLY WITH ADA <br />REQUIREMENTS. <br />5. REFER TO SPECIFICATIONS FOR ADDITIONAL INSULATION REQUIREMENTS. <br />FIXTURE FLOW RATE <br />FIXTURE MAX FLOW RATE <br />(LOW FLOWS) <br />KITCHEN FAUCET 1.8 GPM <br />RESIDENTIAL FAUCET 1.2 GPM <br />METERED COMMON AND PUBLIC <br />AREA FAUCETS 0.20 GAL/CYCLE <br />GENERAL SINK 2.2 GPM <br />SHOWERHEAD 2.0 GPM <br />FLUSH VALVE WATER CLOSET 1.28 GAL/FLUSH <br />FLUSH TANK WATER CLOSET 1.28 GAL/FLUSH <br />URINAL 0.125 GAL/FLUSH <br />NOTES: <br />A. EXCLUDES SERVICE SINKS <br />NOTES: <br />1. REFER TO SPECIFICATIONS FOR ADDITIONAL PIPING REQUIREMENTS. <br />2. PROVIDE DIELECTRIC FITTINGS FOR ALL DISSIMILAR METALS. <br />PLUMBING PIPING MATERIAL SCHEDULE <br />DOMESTIC WATER <br />BELOW GRADE ASTM B 88 TYPE K SOLDERED COPPER <br />ABOVE GRADE ASTM B 88 TYPE L SOLDERED COPPER <br />GUESTROOMS COPPER MANIFOLDS, 1/2" PEX-A TUBING FROM MANIFOLD TO FIXTURES <br />WASTE <br />BELOW GRADE ASTM D 2665 PVC SCHEDULE 40, SOCKET FITTINGS DWV <br />ABOVE GRADE ASTM A 888 CAST IRON, NO HUB SYSTEM <br />KITCHEN - EXPOSED ASTM B 88 TYPE L SOLDERED COPPER <br />GREASE WASTE <br />ALL ASTM A 88 CAST IRON WITH EPOXY COATING, NO HUB SYSTEM <br />VENT <br />ALL ASTM A 88 CAST IRON, NO HUB SYSTEM <br />GAS <br />BELOW GRADE ASTM D 2513 POLYETHYLENE <br />ABOVE GRADE SCHEDULE 40 STEEL TO COMPLY WITH EITHER ASME B36.10, ASTM A 53, <br />OR ASTM A 106 <br />CONDENSATE <br />INDOORS ASTM D 2665 PVC SCHEDULE 40, SOCKET FITTINGS DWV <br />OUTDOORS ASTM B 88 TYPE L COPPER <br />CATEGORY IV ASTM D 2665 PVC SCHEDULE 40, SOCKET FITTINGS DWV <br />A. INSTALL ALL PLUMBING SYSTEMS IN ACCORDANCE WITH THE ADOPTED VERSION OF THE ENERGY EFFICIENCY STANDARDS, CALIFORNIA <br />BUILDING CODE, CALIFORNIA MECHANICAL CODE, AND CALIFORNIA PLUMBING CODE AND ALL OTHER LOCAL CODES AND ADOPTED <br />ORDINANCES. <br />B. CLOSELY COORDINATE ALL PLUMBING WITH ELECTRICAL, ARCHITECTURAL, AND STRUCTURAL. COORDINATE FIRE LINE STUB <br />REQUIREMENTS IN FIRE RISER ROOM WITH GENERAL CONTRACTOR/FIRE PROTECTION CONTRACTOR. PIPING IS APPROXIMATE AND <br />DIAGRAMMATIC AND IS NOT TO BE SCALED. PROVIDE ALTERNATE ROUTING, OFFSETS, AND TRANSITIONS AS REQUIRED FOR <br />COORDINATION OF ALL WORK WITHOUT ADDITIONAL COST TO THE OWNER. <br />C. FIELD VERIFY ALL PLUMBING PRIOR TO COMMENCING NEW WORK. DO NOT FABRICATE OR INSTALL ANY PLUMBING BEFORE VERIFYING <br />DIMENSIONS AND ROUTING WITH BUILDING CONDITIONS AND ALL OTHER TRADES. <br />D. INSTALL ALL EQUIPMENT AND DEVICES PER MANUFACTURER'S RECOMMENDATIONS. PROVIDE ONE YEAR PARTS AND LABOR WARRANTY <br />ON INSTALLATION. <br />E. CONTRACTOR IS RESPONSIBLE FOR ALL APPLICABLE PERMITS AND FEES. <br />F. CAULK AND SEAL ALL PENETRATIONS THROUGH CEILINGS, WALLS, AND FLOORS. PROVIDE ESCUTCHEON COVERS OR SHEET METAL <br />FLANGES ON ALL VISIBLE PENETRATIONS. <br />G. PROVIDE SEISMIC RESTRAINTS FOR PLUMBING EQUIPMENT AND PIPING TO COMPLY WITH SEISMIC DESIGN CRITERIA LISTED IN THE <br />STRUCTURAL GENERAL NOTES. IF NOT AVAILABLE PROVIDE RESTRAINTS IN ACCORDANCE WITH ASCE/SEI 7-10 AND CALIFORNIA BUILDING <br />CODE WITH SEISMIC DESIGN CATEGORY D, SITE CLASS D, RISK CATEGORY II, SHORT PERIOD DESIGN SPECTRAL RESPONSE <br />ACCELERATION COEFFICIENT SDS=0.606, ONE SECOND PERIOD DESIGN SPECTRAL RESPONSE ACCELERATION COEFFICIENT SD1=0.362, <br />AND IMPORTANCE FACTOR 1.0. PIPING SUPPORTED WITHIN 12" OF STRUCTURE DOES NOT REQUIRE SEISMIC BRACING. <br />H. IF DISCREPANCIES EXIST BETWEEN BUILDING CODES, DRAWINGS, NOTES, AND SPECIFICATIONS, THE MOST STRINGENT REQUIREMENT <br />WILL BE REQUIRED UNLESS CLARIFIED BY PROJECT ENGINEER IN AN OFFICIAL ADDENDUM OR SUPPLEMENTAL INSTRUCTION. <br />I. ALL DETAILS INCLUDED IN DESIGN DRAWINGS MUST BE APPLIED TO ALL RELEVANT INSTALLATIONS REFERRED TO IN THE DETAIL. EACH <br />DETAIL WILL NOT BE SPECIFICALLY REFERENCED ON THE DRAWINGS. <br />DOMESTIC WATER <br />A. PROVIDE AND INSTALL WATER METER PER LOCAL JURISDICTION REQUIREMENTS. COORDINATE LOCATION WITH CIVIL. INSTALL WATER <br />METER READING DEVICE PER LOCAL JURISDICTION REQUIREMENTS. <br />B. PROVIDE AND INSTALL UL LISTED DOUBLE CHECK BACKFLOW PREVENTER OR REDUCED PRESSURE BACKFLOW PREVENTER PER LOCAL <br />JURISDICTION ON DOMESTIC WATER SERVICE. WHERE WATER MAIN PRESSURE EXCEEDS 80 PSI PROVIDE AND INSTALL ASSE 103 <br />APPROVED PRESSURE REDUCING VALVE AND STRAINER. <br />C. ALL DOMESTIC WATER PIPING ROUTED BELOW SLAB TO HAVE MINIMAL TO NO JOINTS OR FITTINGS BELOW SLAB. <br />D. PROVIDE WATER HAMMER ARRESTOR IN EACH BRANCH LINE SERVING FIXTURES AND EQUIPMENT WITH AUTOMATIC VALVE OPERATORS. <br />SIZE AND INSTALL PER MANUFACTURER'S RECOMMENDATIONS. <br />E. INSULATE ALL DOMESTIC HOT WATER PIPING AND RECIRCULATION PIPING AND DOMESTIC COLD WATER PIPING PER INSULATION TABLE. <br />PROVIDE ALUMINUM JACKET ON ALL INSULATION LOCATED OUTDOORS. <br />F. ROUTE WATER PIPING IN HEATED AREAS ONLY. DO NOT ROUTE PIPING IN NON-INSULATED ATTIC, CEILING AND WALL SPACES. <br />G. DISINFECT DOMESTIC WATER PIPING. <br />H. PRESSURE TEST ALL DOMESTIC WATER PIPING PER PLUMBING CODE REQUIREMENTS. <br />I. ALL INSTALLATIONS OF PEX PIPE INSTALLED SHALL BE FLUSHED TWICE OVER A PERIOD OF AT LEAST ON WEEK. THE PIPE SYSTEM SHALL <br />BE FIRST FLUSHED FOR AT LEAST 10 MIN. AND THEN FILLED AND ALLOWED TO STAND FOR NO LESS THAN 1 WEEK, AFTER WHICH ALL THE <br />BRANCHES OF THE PIPE SYSTEM SHALL BE FLUSHED LONG ENOUGH TO FULLY EMPTY THE CONTAINED VOLUME. AT THE TIME OF FILL, <br />EACH FIXTURE SHALL HAVE A REMOVABLE TAG APPLIED STATING: “THIS NEW PLUMBING SYSTEM WAS FIRST FILLED AND FLUSHED ON <br />_______ (DATE) BY ________ (NAME). THE STATE OF CALIFORNIA REQUIRES THAT THE SYSTEM BE FLUSHED AFTER STANDING AT LEAST <br />ONE WEEK AFTER THE FILL DATE SPECIFIED ABOVE. IF THIS SYSTEM IS USED EARLIER THAN ONE WEEK AFTER THE FILL DATE, THE WATER <br />MUST BE ALLOWED TO RUN FOR AT LEAST TWO MINUTES PRIOR TO USE FOR HUMAN CONSUMPTION. THIS TAG MAY NOT BE REMOVED <br />PRIOR TO THE COMPLETION OF THE REQUIRED SECOND FLUSHING, EXCEPT BY THE BUILDING OWNER OR OCCUPANT.” CONTRACTOR TO <br />PROVIDE WRITTEN CERTIFICATION THAT THEY WILL COMPLY WITH THE FLUSHING PROCEDURES SET FORTH IN THIS CPC SECTION 604.1.2. <br />ANY CONTRACTOR OR SUBCONTRACTOR FOUND TO HAVE FAILED TO COMPLY WITH THE PEX FLUSHING REQUIREMENTS SHALL BE <br />SUBJECT TO THE PENALTIES IN HEALTH AND SAFETY CODE, DIVISION 13, PART 1.5, CHAPTER 6 (SECTION 17995 ET SEQ.). REFER TO CPC <br />604.1.2 FOR ADDITIONAL INFORMATION. <br />J. INSTALL HYDRONIC TRAP PRIMERS ON ALL FLOOR DRAINS AND FLOOR SINKS UNLESS NOTED OTHERWISE. INSTALL TRAP PRIMERS <br />COMPLYING WITH ALL MANUFACTURER REQUIREMENTS. PROVIDE ACCESS PANEL FOR ALL TRAP PRIMERS AND COORDINATE LOCATIONS <br />WITH GENERAL CONTRACTOR/ ARCHITECT. ALL TRAP PRIMERS TO BE INSTALLED ON BRANCH PIPING SERVING REGULARLY USED FIXTURE <br />TO ENSURE CORRECT OPERATION. <br />K. PROVIDE AND INSTALL BACKFLOW DEVICES PER LOCAL JURISDICTION REQUIRMENTS ON ALL CLOTHESWASHER & ICE MAKERS DCW AND <br />DHW SUPPLY LINES. <br />EQUIPMENT AND FIXTURES <br />A. COORDINATE ALL ELECTRICAL AND CONTROL REQUIREMENTS WITH ELECTRICIAN. <br />B. PROVIDE SUBMITTALS ON ITEMS LISTED IN SCHEDULES TO ENGINEER FOR REVIEW PRIOR TO ORDER, PURCHASE, OR INSTALLATION. ALL <br />REQUIRED SUBMITTALS TO BE SUBMITTED IN A SINGLE TABBED BINDER. PROVIDE ALL HVAC AND PLUMBING CONSTRUCTION COSTS FOR <br />ENGINEER DATA BASE AS PART OF SUBMITTALS. <br />C. ALL MANUFACTURER SUBSTITUTIONS MUST BE SUBMITTED THROUGH ARCHITECT AND APPROVED THROUGH AN ADDENDUM. PRIOR <br />APPROVALS MUST BE SUBMITTED 10 DAYS PRIOR TO BID DATE. <br />D. PROVIDE OPERATIONS AND MAINTENANCE MANUAL INCLUDING ALL PLUMBING EQUIPMENT. <br />E. PROVIDE TRAPPED CONDENSATE DRAINS PIPED FULL SIZE TO FLOOR DRAIN FOR ALL AIR CONDITIONING EQUIPMENT AND HIGH <br />EFFICIENCY FURNACES AND BOILERS. <br />F. REFER TO ARCHITECTURAL FLOOR PLANS FOR EXACT FIXTURE LOCATIONS AND MOUNTING HEIGHTS. <br />G. PROVIDE BALANCE VALVES TO ALLOW COMPLETE BALANCE OF PLUMBING SYSTEMS AND ISOLATION VALVES FOR MAINTENANCE ON EACH <br />PIECE OF EQUIPMENT. <br />H. PROVIDE ISOLATION VALVES FOR ALL BRANCH LINES SERVING THREE OR MORE FIXTURES. PROVIDE BALANCING VALVES FOR EACH <br />DOMESTIC HOT WATER RETURN PIPING OF TWO BRANCHES OR MORE. <br />I. INDIRECT DRAIN T&P RELIEF VALVE TO FLOOR DRAIN. <br />J. SET ALL FIXTURE TEMPERATURE LIMIT STOPS TO 110°F UNLESS INDICATED OTHERWISE. <br />K. INSULATE HANDICAP LAVATORY TAIL PIECE, P-TRAP, TRAP ARM, HOT AND COLD WATER SUPPLY WITH HANDI LAV-GUARD. <br />L. ALL DISHWASHERS TO BE PROTECTED AGAINST BACKFLOW BY AN AIR GAP OR BACKFLOW PREVENTER. <br />M. PROVIDE ADEQUATE COMBUSTION, VENTILATION, AND DILUTION AIR FOR ALL GAS FIRED EQUIPMENT PER INTERNATIONAL FUEL GAS <br />CODE [CALIFORNIA PLUMBING CODE] AND IN ACCORDING TO MANUFACTURER'S RECOMMENDATIONS. <br />N. PROVIDE CONCRETE HOUSEKEEPING PAD (MIN 3" ABOVE GROUND LEVEL) FOR ALL WATER HEATERS. <br />O. GAS FIRED ROOFTOP UNITS TO BE TESTED IN ACCORDANCE WITH ANSIZ21.40.1 OR ANSIZ21.40.2. <br />P. CONTRACTOR MUST COORDINATE ALL ELECTRICAL REQUIREMENTS FOR ALL EQUIPMENT WITH ELECTRICAL CONTRACTOR ONCE <br />APPROVED SUBMITTALS ARE RECEIVED. <br />GAS PIPING <br />A. PRIME AND PAINT ALL GAS PIPING LOCATED ON ROOF. ALL PIPING TO BE INSTALLED 4" MINIMUM ABOVE ROOF. <br />B. NEW OR MODIFIED GAS PIPING TO BE TESTED AND INSPECTED PER INTERNATIONAL FUEL GAS CODE OR CALIFORNIA MECHANICAL CODE <br />AND LOCAL JURISDICTION PRIOR TO INITIAL OPERATION. THE TEST PRESSURE TO BE NOT LESS THAN 1-1/2 TIMES THE PROPOSED <br />MAXIMUM WORKING PRESSURE, AND NOT LESS THAN 3 PSIG. TEST DURATION TO BE A MINIMUM 10 MINUTES OR NOT LESS THAN 1/2 HOUR <br />FOR EACH 500 FT³ OF PIPE VOLUME. AREAS OF PIPING WHERE LEAKS OR OTHER DEFECTS ARE LOCATED TO BE REPLACED OR REPAIRED <br />AND RETESTED. <br />C. GAS CONNECTION TO APPLIANCE TO BE CSST AND GAS CONNECTION TO COMMERCIAL COOKING APPLIANCE TO COMPLY WITH ANSI <br />Z21.69. CONNECTORS FOR RANGES AND DOMESTIC CLOTHES DRYER TO HAVE A MAXIMUM LENGTH OF 6 FEET. CONNECTORS FOR ALL <br />OTHER APPLIANCES TO HAVE A MAXIMUM LENGTH OF 3 FT. SHUTOFF VALVES TO BE INSTALLED AHEAD OF CONNECTORS. CONNECTOR <br />INSTALLATION TO COMPLY WITH MANUFACTURER REQUIREMENTS. <br />GENERAL PIPING <br />A. PIPING AND EQUIPMENT HANGERS CENTERED ON STEEL I-BEAMS (CONCENTRIC HANGERS) ARE PREFERRED OVER HANGERS SUPPORTED <br />FROM A SINGLE SIDE OF THE BOTTOM I-BEAM FLANGE. IF USING HANGERS SUPPORTED FROM A SINGLE SIDE OF THE BOTTOM FLANGE, <br />THE MAXIMUM WEIGHT LIMIT PER HANGER IS 200 POUNDS UNLESS DIRECTED OTHERWISE BY THE PROJECT STRUCTURAL ENGINEER. <br />B. CONCEALED VENTS, DUCTS, AND ALL PIPING INSTALLED THROUGH FRAMING MEMBERS MUST BE PROTECTED FROM FASTENER <br />PENETRATION BY A STEEL SHIELD PLATE (MINIMUM THICKNESS OF 1/16") UNLESS THE DISTANCE FROM THE FACE EDGE OF THE FRAMING <br />IS NOT LESS THAN 1.5". <br />C. CLOSE ENDS OF PIPING AND COVER FLOOR DRAINS DURING CONSTRUCTION. CLEAN ALL EQUIPMENT AND PIPING AT COMPLETION OF <br />PROJECT. <br />D. COORDINATE ALL STRUCTURAL AND TOP PLATE PENETRATIONS FOR PIPING WITH GENERAL CONTRACTOR AND STRUCTURAL ENGINEER. <br />E. PROVIDE DRAIN PANS UNDER ALL PIPING LOCATED OVER ELECTRICAL PANELS AND UNDER ALL WATER HEATERS. <br />F. PROVIDE AND INSTALL EXPANSION JOINTS FOR ALL PIPING SYSTEMS PER CODE AND LOCAL JURISDICTION REQUIREMENTS. AT A <br />MINIMUM, PROVIDE EXPANSION JOINTS WHEN JOINING SEPARATE PIPING MATERIAL AND FOR ALL DWV AND ROOF DRAIN STACKS SERVING <br />MORE THAN TWO FLOORS. <br />SANITARY SEWER, VENT, AND DRAIN <br />A. WASTE PIPING SMALLER THAN 4" IS TO BE SLOPED AT 1/4" PER FOOT UNO. ALL WASTE PIPING 4" AND LARGER MAY BE INSTALLED AT 1/8" <br />SLOPE PER FOOT UPON RECEIVING WRITTEN APPROVAL BY LOCAL JURISDICTION. VERIFY INVERT BEFORE INSTALLATION. <br />B. ALL SANITARY WASTE AND VENT AND STORM DRAINAGE PIPING LOCATED IN A RETURN AIR PLENUM TO BE CAST IRON SV NO HUB SYSTEM. <br />C. PROVIDE CLEANOUTS ON INTERIOR SANITARY AND STORM PIPING A MINIMUM OF EVERY 50 FEET AND EVERY 100 FEET ON EXTERIOR <br />PIPING. <br />D. PROVIDE GRADE CLEANOUT WHERE BUILDING SEWER CONNECTS TO SEWAGE SYSTEM. <br />E. PROVIDE VENT FOR EVERY TRAP AND TRAPPED FIXTURE. ALL VTR'S TO BE 2" MINIMUM AND TERMINATE MINIMUM 10" ABOVE ROOF AND <br />MINIMUM 24" FROM ROOF EDGE OR PARAPET, AND 25' FROM OUTSIDE AIR INTAKE INTO BUILDING. <br />F. PRESSURE TEST ALL SANITARY SEWER AND VENT AND STORM PIPING TO PLUMBING CODE REQUIREMENTS. <br />G. DRAINAGE CONNECTIONS SHALL NOT BE MADE INTO A DRAINAGE PIPING SYSTEM WITHIN 8' OF ANY VERTICAL TO HORIZONTAL CHANGE <br />OF DIRECTION OF A STACK CONTAINING SUDS. STACKS CONTAINING SUDS ARE IDENTIFIED ON THE RISER DIAGRAMS. <br />GENERAL PLUMBING NOTES <br />NO SCALEP0.1 <br />GAS PIPING SCHEMATIC1 <br />NO SCALEP0.1 <br />WATER SCHEMATIC2 <br />E <br />IN <br />ARSESIOFNO <br />L <br />OIFCALOF <br />R <br />D <br />SIERGERETT <br />S <br />A <br />ET <br />P <br />EXP. 9-30-18 <br />M37119 NREEIGN <br />AMECHA N I C A LHU G H STAIN. <br />G <br />E <br />REXP.9-30-2020 <br />04/12/2019