too <br /> Line Leak Detector Test Data Sheet <br /> Station # Arco 7049 Date 12/ 13/2018 20 <br /> Address 800 E Kettleman Lane , Lodi , CA 95240 <br /> Test Information <br /> 1 2 3 4 5 <br /> Product 87 91 <br /> Manufacturer VR VR <br /> Model 848480 848480 <br /> Full Operating Pressure (psi) 36 34 <br /> Line Bleed Back (ml) NA NA <br /> Trip Time (sec) NA NA <br /> Metering Pressure (psi) NA NA <br /> F/E Holding Pressure (psi ) 34 32 <br /> Test Leak Rate (ml/min)(gph) 18 9ML 18 9ML <br /> PASS or FAIL Pass Pass <br /> Comments *• <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The mechanical leak test detector test pass/fail is determined using a low <br /> flow threshold trip rate of 3 gph at 10 PSI . <br /> Inspected By : Contractor .Gettler Ryan Inc. <br /> Technician David RouseLic# 220793 <br /> Signature <br />