Laserfiche WebLink
SAN J O A Q U I N Environmental Health Department <br />.—COUNTY— <br />Underground Storage Tank Program Inspection Report <br />Facility Name: <br />Facility Address: <br />Date: <br />DART CONTAINER CORP <br />1400 E VICTOR RD, LODI <br />December 18, 2018 <br />Item # <br />Remarks <br />209 <br />CCR 2716(a -e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br />The designated operator failed to document the following: <br />On the 10/22/18 designated operator (DO) inspection report under <br />- Section I <br />The DO failed to write the CERS ID and zip code <br />- Section III <br />The DO failed to add a description to all the components marked N/A from section VII through XI. <br />-Section VII <br />The DO fail to mark yes or No for the question " Has each follow-up action of section III from the previous inspection <br />been completed appropriately?" <br />IX <br />The DO failed to mark Yes, No, or N/A to the question "Are all sensors in under -dispenser containment located to <br />detect a leak at the earliest opportunity?" <br />-Section X <br />The DO failed to mark NO under the question "Has the overfill prevention equipment inspection been completed <br />within the past 36 months?' The overfill prevention equipment inspection has not been completed. <br />The DO failed to mar YES, NO or N/A under the question " Has the line tightness testing been completed within the <br />required timeframes?" <br />The designated operator failed to include the complete alarm history since the previous inspection. <br />On the 11/30/18 designated operator (DO) inspection report under <br />- Section I <br />The DO failed to write the CERS ID and zip code <br />- Section III <br />The DO failed to add a description to all the components marked N/A from section VII through XI. <br />-Section VII <br />The DO fail to mark yes or No for the question " Has each follow-up action of section III from the previous inspection <br />been completed appropriately?" <br />IX <br />The DO failed to mark Yes, No, or N/A to the question "Are all sensors in under -dispenser containment located to <br />detect a leak at the earliest opportunity?" <br />-Section X <br />The DO failed to mark YES, NO or N/A under the question " Has the line tightness testing been completed within the <br />required timeframes?" <br />The designated operator failed to include the complete alarm history since the previous inspection. <br />Furthermore the DO did not conduct an inspection with 30 days of the previous inspection. The DO inspected the <br />facility on 10/22/18 and on 11/30/18. The DO report was conducted 39 days after the 10/22/18 inspection and not 30 <br />days as stated by regulation. <br />During the monthly inspection, the designated operator shall review the alarm history for the previous month, check <br />that each alarm was documented and responded to appropriately, and attach a copy of the alarm history with <br />documentation taken in response to any alarms to the monthly report. Ensure that designated operators performing <br />inspections at least once every 30 days at this facility and are including all of the required information on the reports. <br />This is a repeat violation, Class II. <br />FA0003704 PR0231951 SCO01 12/18/2018 <br />EHD 23-01 Rev. 09/28/2018 Page 4 of 5 Underground Storage Tank Program OIR <br />1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />