SAN.JOAQUIN Environmental Health Department <br />.—COUNTY— <br />Underground Storage Tank Program Inspection Report <br />Facility Name: <br />Facility Address: <br />Date: <br />DART CONTAINER CORP <br />1400 E VICTOR RD, LODI <br />December 18, 2018 <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />Item # <br />Remarks <br />319 <br />CCR 2635, 2637.1, 2665, 2712 No spill bucket, failed to contain 5 gallons, no means to keep it empty, or failed to be <br />tested. <br />The Diesel direct -bury spill container failed when tested. All spill containers shall have a minimum capacity of five <br />gallons and be capable of containing a spill or overfill until it is detected or cleaned up. Immediately discontinue <br />deposition of petroleum into this tank until the component is repaired or replaced by a properly licensed, trained, and <br />certified contractor under permit and inspection of the EHD. If the spill container can't be replaced immediately, <br />there is a possibility that the Diesel UST system may be red tagged to prevent fuel inputs. <br />This is a repeat violation, Class II. <br />320 <br />CCR 2635, 2637.2, 2665, 2712 Failure to comply with the installation, inspection, or record keeping of the overfill <br />prevention. <br />Owners or operators of underground storage tanks that do not meet California Code of regulations, title 23 division <br />3, chapter 16 section 2635(c)(2) shall test overfill prevention equipment once by October 13th, 2018 and every 36 <br />months thereafter; and within 30 days of the date of a repair. The site did not performed the testing by October 13th, <br />2018. Ensure to conduct overfill prevention equipment inspection within the time frame provided by the regulation <br />and submit test results within 30 days of performing the inspection. Ensure a 48 hour notification is provided to EHD <br />prior to conducting the inspection. <br />This is a Class II violation. <br />Overall Inspection Comments: <br />An inspection checklist was provided to the facility operator at the time of inspection. The EHD will generate <br />and provide a complete report to the facility operator. <br />Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br />documenting the corrective actions that have been or will be taken for each violation, and any supporting <br />paperwork, within 30 days of receiving the complete inspection report. <br />On site to witness the monitoring system certification. No paperwork was inspected during the inspection. EHD <br />will return on 12/20/18 at 9 -.am to complete the routine inspection. <br />AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br />THIS FACILITY BACK INTO COMPLIANCE. <br />THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br />Received by: Date: December 18, 2018 <br />Inspector: <br />Inspector Phone: <br />4-tO4 Printed Name and Title: <br />ZUNA BARKER, EH Specialist <br />(209) 953-7311 <br />—xfto <br />Gloria Suarez, SAfety Leader <br />FA0003704 PR0231951 SCO01 12/18/2018 <br />EHD 23-01 Rev. 09/28/2018 Page 4 of 4 Underground Storage Tank Program OIR <br />1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />