Laserfiche WebLink
fjc <br /> Line Leak Detector Test Data Sheet <br /> Station # Arco 2093 Date 8/30/2018 20 <br /> Address 3425 Tracy Blvd . Tracy , CA 95378 <br /> Test Information <br /> I 2 3 4 5 <br /> Product 87 91 <br /> Manufacturer VR VR <br /> Model 848480 848480 <br /> Full Operating Pressure (psi ) 38 3 $ <br /> Line Bleed Back ( ml ) NA NA <br /> Trip Time (sec ) NA NA <br /> Metering Pressure (psi) NA NA <br /> F/E Holding Pressure ( psi) 34 32 <br /> Test Leak Rate (ml/min)( gph) 18 9ML 18 9ML <br /> PASS or FAIL pass pass <br /> Comments & <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct . The mechanical leak test detector test passirail is determined using a low <br /> flow threshold trip rate of 3 gph at 10 PSI . <br /> Inspected By : Contractor Gettler Ryan Inc <br /> Technician David Rouse Lic# 220793 <br /> Signature <br />