Laserfiche WebLink
MORRIS <br /> SHAFFER <br /> E N G I N E E R I N G Page 8 of 15 <br /> Tank Assessment Checklist: CIX-T1 System Feed Tank <br /> Tank Name : CIX- T1 System Feed Tank <br /> Approximate Date of Construction : 2015 <br /> Indust Practice at time of original construction <br /> Design Standards : I <br /> Industry - — — <br /> Approximate Dimensions : F64 " diameter by 104 " Height to Top of Vertical Wall <br /> _._ <br /> Tank Configuration : Vertical Flat Bottom Tank <br /> ' mate Gross Ca acity: 1500 Gallons <br /> Approximate roxi p <br /> Material of Construction : FPolyethylene <br /> Approximate Tank Wall Thickness : 3/8" <br /> Tank System Piping: PVC Piping <br /> Internal / External Pumps : External pumps <br /> Leak Detection Equipment: Visual Observation <br /> Corrosion Protection Equipment: F N/A <br /> Spill Prevention Equipment: <br /> Anchor Cables <br /> Secondary Containment: Epoxy-coated concrete berm <br /> Hazardous Characteristics of Waste : [ Acidic wastewater <br /> sides <br /> did not show any <br /> Description of Structural Damage : sign of damage.cylindrical tank was <br /> inside of the tank k was not observed. The tank <br /> is new and appeared to be in good order. <br /> Results of Leak Test: No leak test was performed but tank was in use during our visit. No <br /> visual signs of leaking were present <br /> Tank installed on an epoxy- coated concrete slab- on -grade. There <br /> Foundation : <br /> were no signs of settlement around the tank. <br /> Seismic Anchors : Seismic anchor brackets are anchored to the epoxy- coated concrete <br /> slab- on -grade. Stainless steel cables are attached to the top of the <br /> I brackets and wrap around the top of the tank. <br /> Estimated Remaining Service Life : _ 125+ years _ <br /> Comments : This tank is new and appears to be in good condition. <br /> 1300 INDUSTRIAL ROAD , SUITE 14 , SAN CARLOS , CA 94070, ( 650 ) 595 -2973 FAX ( 650 ) 595-2980 <br />