Laserfiche WebLink
W . O . # NW 1 - 2338728 Cust Ref # : COCO - 0015297489 <br /> 2. To determine lower tube distance from tank <br /> bottom to bottom of cut; <br /> Subtract valve length (IM from distance to tank <br /> bottom (B) � ' �s <br /> M = ($) twi <br /> Cast lug <br /> Note. Lower tube clearance must meet tank manu- In , , 5o <br /> facturer requirements and all AHJ, local, state, and na- body <br /> tional codes. Typical clearance is about 4" if lower Float direction <br /> tube clearance is not met valve must be removed and <br /> adjusted to meet these requirements. <br /> 3 . To determine lower tube distance from tank <br /> bottom to top of tut% <br /> Subtract valve length (U) from distance to tank <br /> bottom (B) <br /> M (B) — (Lit = � <br /> View Pato drop tubi from above <br /> Note: Lower tube distance from tank bottom to top <br /> of cut must meet all AM, local, state, and national <br /> codes. For reference per 40 CFR 63 subpart CCCCCC / <br /> NESHAP the lower tube can be no more than 6° from <br /> the bottom of the tank If lowertube distance is not <br /> met valve must be removed and adjusted to meet these <br /> requirements, <br /> i <br /> 4 . To determine float alignment <br /> Looking Into upper tube (see figure) the float should be <br /> F aligned along the length of the tank If float is not <br /> aligned properly adjustments need to be made. <br /> I <br /> 21 <br /> I <br />