Guide Specifications for Xerxes Underground Petroleum Storage Tanks <br /> Short form: A.General <br /> The contractor shall provide a double-wall or triple-wall fiberglass reinforced 1.Tank shall be continuously monitored with the TRUCHEK® <br /> plastic(FRP)UL-listed underground storage tank as shown on the drawings. hydrostatic leak monitoring system. <br /> The tank size,fittings and accessories shall be as shown on the drawings. 2.The continuous monitoring system shall include monitoring fluid <br /> The fiberglass tank shall be manufactured by Xerxes Corporation, factory-installed in the interstitial space and within a fiberglass <br /> tank-top mounted reservoir. <br /> The tank shall be tested and installed according to the Xerxes Installation 3.The monitoring system shall be recognized by the National <br /> Manual and Operating Guidelines for Fiberglass Underground Storage Tanks Work Group on Leak Detection Evaluations(NWGLDE)as <br /> in effect at time of installation. continuous leak detection and as a precision tank test. <br /> Long form: 4.The monitoring system shall be independently tested by a <br /> Part I:General qualified third party and verified to be capable of detecting <br /> 1.01 Quality Assurance leaks as small as.05 gallons per hour when TRUCHEK <br /> A.Acceptable Manufacturer:Xerxes Corporation tank-tightness test procedures are followed. <br /> B.Governing Standards,as applicable: B.Design <br /> 1.Underwriters Laboratories(UL)Standard for Safety 1316 1.The continuous monitoring system shall be designed to detect <br /> Glass-Fiber-Reinforced Plastic Underground Storage Tanks for a leak in either the primary or secondary wall at all times, <br /> Petroleum Products,Alcohols,and Alcohol-Gasoline Mixtures. regardless of the water-table conditions at the installation site. <br /> A UL label shall be attached to each tank. 2.The interstice of the tank shall be designed for a 5:1 safety factor <br /> 2.National Fire Protection Association(NFPA)Standards:NFPA 30: beyond normal hydrostatic operating pressure to ensure structural <br /> Flammable and Combustible Liquids Code,NFPA 30A:Code for integrity and to prevent false leak alarms. <br /> Motor Fuel Dispensing Facilities and Repair Garages,NFPA 31: 2.03 Accessories <br /> Standard for the Installation of Oil-Burning Equipment. A.Tank Anchoring <br /> 3.City of New York Department of Buildings M.E.A., #161-89-M. 1.Anchor straps shall be as supplied by tank manufacturer and <br /> 4.American Concrete Institute(ACI)standard ACI 318-11,Building designed for a maximum load of 25,000 lbs. <br /> Code Requirements for Structural Concrete. 2.Galvanized turnbuckles(two per anchor strap)shall be supplied <br /> C.Submittals by the tank manufacturer. <br /> 3.Prefabricated concrete anchors shall be supplied by the tank <br /> 1.Contractor shall submit_copies of shop drawings, manufacturer,designed to the ACI 318-11 standard, <br /> manufacturer's product brochures,and Installation Instructions. manufactured with 4,000 psi concrete,and shall have <br /> Part II:Products B.Manways adjustable anchor points. <br /> 2.01 Double-Wall and Triple-Wall Fiberglass Reinforced Plastic(FRP) 1.The standard manway shall be flanged,22"I.D.and complete <br /> Underground Storage Tanks: <br /> A.Loading Conditions-Tank shall meet these design criteria: with UL listed gaskets,bolts and covers as shown on tank <br /> 1.Interstitial Pressure-The interstitial space of the tank shall drawings. <br /> withstand a minimum 20-prig pressure test. C.Threaded Fittings <br /> 2.Internal Load-Tank shall withstand a 5-psig air-pressure test 1.All threaded fittings shall be NPT half or full couplings,in 2",4" <br /> with a 5:1 safety factor. or 6"diameters. <br /> 3.Surface Loads-Tank shall withstand surface H-20 and HS-20 2.Fittings shall be installed on the tank-top centerline or in the <br /> axle loads when properly installed according to Xerxes'current cover of the manway as shown on the tank drawings. <br /> Installation Manual and Operating Guidelines. D.Containment Collars&Sumps <br /> 4.External Hydrostatic Pressure-Tank shall be designed for 7' 1.The tank shall have factory-installed 42"-or 48"-diameter <br /> of overburden over the top of the tank,the hole fully flooded containment collars as shown on the tank drawings. <br /> and a safety factor of 5:1 against general buckling. 2.Containment sumps in 42"-or 48"-diameter,provided by the <br /> B.Product Storage: tank manufacturer and designed for mounting on the <br /> 1.The primary compartment of double-wall and triple-wall tanks containment collars,shall be supplied as shown on the tank <br /> shall be vented and operated at atmospheric pressure only. drawings. <br /> 2.Tank shall be capable of storing liquids with a specific gravity up 3.Adhesive shall be provided by the tank manufacturer <br /> to 1.1. with each containment collar and sump. <br /> 3.Tank shall be capable of storing products identified in the 4.Containment collars and sumps shall be designed and supplied <br /> manufacturer's standard limited warranty in effect at the time as a containment system.Only sumps provided by the <br /> of purchase. manufacturer shall be allowed. <br /> C.Materials: Part III:Testing and Installation <br /> 1.The primary and secondary walls of the tank shall be 3.01 Testing <br /> manufactured with 100%premium resin and glass-fiber A.Testing-Tank shall be tested according to the Xerxes Installation Manual <br /> reinforcement. No sand or silica fillers shall be added to the and Operating Guidelines in effect at time of installation. <br /> resin. 3.02 Installation <br /> 2.The interstitial space between the primary and secondary walls A.installation-Tank shall be installed according to the Xerxes Installation <br /> shall be constructed with a glass reinforcement material such as Manual and Operating Guidelines in effect at time of installation. <br /> Parabeame,which provides a structural bond between the two <br /> tank walls,while creating a defined interstice that allows for Part IV:Limited Warranty <br /> free flow of liquid. 4.01 Limited Warranty <br /> D.Tank Dimensions(Refer to Xerxes literature on gallonage): A.Limited Warranty-Warranty shall be manufacturer's standard limited <br /> 1.Tank shall have nominal capacity of gallons. warranty in effect at time of purchase. <br /> 2.Tank shall have nominal outside diameter of feet. <br /> 3.Tank shall have a nominal overall length of feet/inches. <br /> 2.02 Tank Monitoring System <br /> 10 ZCL Composites Inc. • Xerxes Corporation <br />