Laserfiche WebLink
o Overspill containment has been changed to Phil-Tite Model # M42-2C-1-0- <br /> NPR <br /> o Overfill prevention device has been changed to EBW/ Franklin Fueling <br /> Model #708592902 <br /> Comment #2: <br /> The submitted ELD work plan is not acceptable for the proposed tanks, please provide a <br /> revised ELD work plan. Please refer to the State Water Resources Control Board letter <br /> dated September 14, 2018 for additional information on ELD testing requirements <br /> (attached) <br /> Response to comment #2: <br /> The revised ELD work plan is attached. <br /> Comment #3: <br /> Provide all tank and sump cut sheets, for example Xerxes installation instructions were <br /> provided in your recent submittal in lieu of cut sheets <br /> Response to comment #3: <br /> • Please refer to the following documents from the manufacturer as their cut <br /> sheets and see if they contain the information you seek. Please note that these <br /> are the ONLY cut sheet documents provided by this manufacturer: <br /> o Xerxes 20K split tank drawing 659-546-00 <br /> o Xerxes 20K tank drawing 659-545-00 <br /> o XERXES-Sump-Brochure-web-16 <br /> o XERXES-UST-Fuel-Brochure-sm-1 <br /> Comment #4: <br /> OPW flapper valve calculation sheet was provided, it appears that maybe a Defender <br /> Series flapper valve is being proposed, please clarify, submit the appropriate calculation <br /> worksheet <br /> Response to comment #4: <br /> • Please refer to the following revised overfill calculation documents: <br /> o Overfill caics_20k <br /> o Overfill calcs 8k <br /> o Overfill calcs 12k <br />