Laserfiche WebLink
UNDERGROUNDSTORAGETANK <br /> OVERFILL PREVENTION EQUIPMENT INSPECTION REPORT FORM (Pagel of 1) <br /> Type of Action ❑ Installation Inspection ❑ Repair Inspection ❑x 36 Month Inspection <br /> I. FACILITY INFORMATION <br /> CERS ID Date of Overfill Prevention Equipment Inspection <br /> 10180567 6/24/2019 <br /> Business Name(Same as Facility Name or DBA-Doing Business As) <br /> EMILS <br /> Business Site Address City ZIP Code <br /> 1405 CALIFORNIA ST ESCALON 95320 <br /> II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION <br /> Name of UST Service Technician Performing the Inspection(Print as shown on the ICC Certfcation.) Phone# <br /> David Winkler 1 (209) 744-0112 <br /> Contractor I Tank Tester License# ICC Certification# ICC Certification Expiration Date <br /> 08-1739 Ex.3/31/2020 8883059-UT 1/29/2020 <br /> Overfill Prevention Equipment Inspection Training and Certifications(List applicable certifications.) <br /> FF- EBW , Phil-Tite &EVR Phase 1 1009853708 Ex 11/29/20 OPW 104-633 Ex 3-14-2020 <br /> Emco #3207 Ex. 11/16/20 ATG: VR: B34975 ATG: 2/8/20 INCON 1009853708 Ex.11/30/2020 <br /> 111. OVERFILL PREVENTION EQUIPMENT INSPECTION INFORMATION <br /> Inspection Method ❑x Manufacturer Guidelines(Specify): <br /> Used: REMOVED OPW DROP TUBES <br /> ❑Industry Code or Engineering Standard(Specify): <br /> ❑Engineered Method(Specify): <br /> Attach the inspection procedures and all documentation required to determine the results. #of Attached Pages 5 <br /> TANK ID:(By tank number,stored product,etc.) 87 91 DSL <br /> What is the tank inside diameter?(Inches) 128 128 128 <br /> Is the fill piping secondarily contained? ❑Yes ❑x No ❑Yes 0 No ❑Yes E No ❑Yes ❑No <br /> Is the vent piping secondarily contained? ❑Yes ❑x No ❑Yes 0 No ❑Yes Z No ❑Yes ❑No <br /> Overfill Prevention Equipment Manufacturer(s) DPW DPW DPW <br /> 61so 61so 61so <br /> What is the overfill prevention equipment response ❑x Shuts Off Flow ❑x Shuts Off Flow ❑x Shuts Off Flow ❑Shuts Off Flow <br /> when activated? <br /> ❑ <br /> (Check all that apply.) Restricts Flow El Restricts Flow El Restricts Flow El Restricts Flow <br /> ❑A/V Alarm ❑A/V Alarm ❑A/V Alarm ❑A/V Alarm <br /> Are flow restrictors installed on vent piping? ❑Yes 0 No ❑Yes 0 No ❑Yes ❑x No ❑Yes [:1 No <br /> At what level in the tank is the overfill prevention set <br /> to activate?(Inches from bottom of tank.) 112 1/2 1121/2 124 <br /> What is the percent capacity of the tank at which the <br /> overfill prevention equipment activates? 93 93 99 <br /> Is the overfill prevention in proper operating condition ❑x Yes Yes ❑Yes ❑Yes <br /> to respond when the substance reaches the <br /> E]appropriate level? No(Specify in V.) [INo(Specify in V.) ❑Q No(Specify in V.) ElNo(Specify in V.) <br /> IV. SUMMARY OF INSPECTION RESULTS <br /> Overfill Prevention Inspection Results ❑Q Pass ❑ Fail 11 ❑Q Pass ❑ Fail ❑Pass ❑x Fail ❑ Pass ❑Fail <br /> V. COMMENTS <br /> Any items marked"Fail'must be explained in this section. Any additional comments may also be provided here. <br /> DSL FAILED TO HIGH NEEDS NEW DROP TUBE AND RETEST ASAPF `­11' <br /> ** Donlee To repair and retest DIE OF RECER, <br /> 1111 1 R '�0.10 <br /> VI. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS INSPEC"I''ION <br /> I hereby certify that the overfill prevention equipment was inspected in accordance with California Code of Regulations,Title 23, <br /> Division 3, Chapter 16,Section 2637.2 and all the information contained herein is accurate. riONMEN : __-; <br /> UST Service Technician Signature DEPARTMENT <br /> If the facility has more components than this form accommodates,additional copies of this page may be attached. <br /> CERS=California Environmental Reporting System,ID=Identification,UST=Underground Storage Tank,ICC=International Code Council,AW=Audible and Visual <br />