Laserfiche WebLink
SANJ OA U I Environmental Health Department <br /> COUNTY <br /> — <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> J & L MARKET 8115 S EL DORADO ST FRENCH CAMP May 22 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 209 CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br /> The designated operator failed to check and note all required items on the visual inspection reports. The incorrect and <br /> missing information included the following from the inspection reports: <br /> -Section V was left blank. <br /> -The owner/operator printed name was left blank. <br /> -Tank and line tightness testing was left blank. <br /> -The follow up action question was left blank. <br /> -The NA answers were not included in section III. <br /> During the visual inspection, the designated operator shall check that all required testing and maintenance for the UST <br /> system have been completed and shall check all required items on the report. Ensure that designated operators <br /> performing visual inspections at this facility are including all of the required information on the reports. <br /> A designated operator inspection for the following months was performed more than 30 days: <br /> -Conducted 12/14/18, next conducted 1/17/19 (34 days) <br /> -Conducted 3/11/19, next conducted 4/11/19 (31 days) <br /> The designated operator visual inspections shall be conducted within 30 days or less of the previous inspection. <br /> Ensure that all designated operator inspections are performed within the required time frames. <br /> The designated operator failed to check and note the correct test dates for the secondary containment testing on the <br /> designated operator inspection reports. The previous test date of 8/16/17 is written on all reports. Secondary <br /> containment testing was conducted on 2/28/19. During the monthly inspection, the designated operator shall check <br /> that all required testing and maintenance for the UST system have been completed and document the dates they were <br /> done. Ensure that designated operators performing monthly inspections at this facility are including all of the required <br /> information on the reports. <br /> This is a repeat violation, Class II. <br /> 320 CCR 2635, 2637.2, 2665, 2712 Failure to comply with the installation, inspection, or record keeping of the overfill <br /> prevention. <br /> Overfill prevention testing was conducted on January 25, 2019. This testing was required to be conducted by October <br /> 13, 2018. Ensure all future testing is conducted within required time frames. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by June 21, 2019. <br /> Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate ($152). To schedule an <br /> appointment, please call (209) 468-3420. <br /> FA0000110 PR0231563 SCO01 05/22/2019 <br /> EHD 23-01 Rev.09/28/2018 Page 6 Of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />