Laserfiche WebLink
SANJ OA U I Environmental Health Department <br /> — 0U NTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> MORADA CHEVRON FAST N EASY#60* 10878 N HWY 99 E , STOCKTON April 11, 2019 <br /> Item# Remarks <br /> 105 CCR 2632(d)(1), 2634(d) Failed to have an approved UST monitoring plan. <br /> The monitoring plan is not current and/or not approved by the EHD. <br /> The monitoring plans for both tanks incorrectly list the monitoring panel for the tank, piping, and UDC monitoring as a <br /> Veeder Root TLS 350. The panel on site is a Veeder Root TLS 350 Plus. <br /> The monitoring plan must be uploaded to the California Environmental Reporting System (CERS).Immediately log <br /> into CERS, make the necessary changes, and submit for review by the EHD. <br /> This is a minor violation. <br /> 115 CCR 2715(a)(1)(B), 2715(a)(3)"Designated Underground Storage Tank Operator Identification Form" not submitted <br /> within 30 days. <br /> A new designated operator Omero Garcia II was hired and has been performing monthly visual inspections. No <br /> notification has been provided to the EHD. Any changes in designated operatos shall be reported to the EHD within <br /> 30 days. Immediately log into the California Environmental Reporting System (CERS) at http://cers.calepa.ca.gov <br /> and upload the notification identifying all the designated operators for this facility. <br /> This is a minor violation. <br /> 201 CCR 2712(b) Failure to maintain monitoring, maintenance, and follow up action records. <br /> Maintenance and monitoring records for the last three years were not found on site. <br /> -The Monitoring system certification for 2016 was not found on site. <br /> -The Secondary containment testing results was not found on site. <br /> -The Overfill prevention testing results were not found on site. <br /> These records shall be maintained on site for at least three years. Monitoring records include: (1)date and time of all <br /> monitoring or sampling; (2) monitoring equipment calibration and maintenance records; (3) results of any visual <br /> observations; (4) results of sample analysis performed a lab or in the field; (5) logs of all readings of gauges or other <br /> monitoring equipment, ground water elevations, or other test results; (6) results of inventory readings and <br /> reconciliations. Immediately locate and maintain all maintenance and monitoring records for the last three years on <br /> site and submit copies to the EHD. <br /> This is a minor violation. <br /> FA0001146 PR0231598 SCO01 04/11/2019 <br /> EHD 23-01 Rev.09/28/2018 Page 4 Of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />