SAN J O A Q U I N Environmental Health Department <br /> COUNTY <br /> 6 . A valid California Department of Tax and Fee Administration ( CDTFA) number must be obtained and <br /> provided to EHD prior to fuel drop , and must be uploaded into CERS . <br /> 7 . The following items must be completed prior to scheduling the final inspection : <br /> a . An accurate and drawn to scale as- built drawing , which indicates the location of the UST <br /> system ( underground storage tanks , piping , auxiliary and monitoring equipment) with respect <br /> to buildings or other landmarks , per CCR 2711 ( a) ( 8 ) , must be submitted to EHD . <br /> b . Copies of any required installation checklists ( tank , etc . ) must be submitted to EHD . <br /> c . The designated operator ( DO ) training requirement must be satisfied , per CCR 2715 (f) . <br /> d . Submit to the California Environmental Reporting System ( CERS ) all applicable hazardous <br /> materials , hazardous waste , and UST submittals . The submittal must be approved by EHD . <br /> 8 . The installed UST system must be compliant with all applicable laws , regulations , and industry <br /> standards . All installation and testing shall be in compliance with manufacturer' s instructions and CCR <br /> 2635 and 2636 . All monitoring system components shall be listed in the State Water Resources <br /> Control Board ' s Local Guidance Letter ( LG ) 113 . <br /> 9 . All primary containment including any integral secondary containment system must be certified by an <br /> independent testing organization and labeled as required by the organization ( California Code of <br /> Regulations Title 23 Chapter 16 ( CCR ) 2631 ( b ) ; UL , ULC , ANSI , API , ASTM , etc . See CCR Table B <br /> for complete list . ) . Pursuant to Underwriters Laboratories Inc . ( UL ) listing requirements , only those <br /> products bearing the UL mark will be considered listed . ANY PART/PRODUCT NOT MARKED WITH <br /> THE UL LABEL OR ANOTHER LISTED TESTING ORGANIZATION WILL BE REJECTED . All <br /> secondary containment system which is not an integral part of the primary containment shall be <br /> designed and constructed according to an engineering specification approved by a state registered <br /> professional engineer or according to a nationally recognized industry code or engineering standard , <br /> per CCR 2631 ( d ) . <br /> 10 . All metal components in direct contact with the ground , such as flexible connectors , swing joints , <br /> fittings , clamps , bands , and pumps , shall have adequate corrosion protection . <br /> 11 . Install concrete of sufficient thickness over USTs and around sumps and dispensers , according to the <br /> manufacturer' s written installation instructions and buoyancy calculations . <br /> 12 . All tank top openings that are connected to the primary space of the UST must have secondary <br /> containment , audible/visual alarm , and be vapor tight or terminate at grade . <br /> 13 . Sumps , including UDCs , must be constructed in a manner to prevent vapors from entering the backfill . <br /> 14 . All secondary containment must be constructed to prevent water intrusion and must be continuously <br /> monitored as required under HSC 25290 . 1 . <br /> 15 . Chase piping must be VPH monitored and included in its respective product piping vacuum monitoring <br /> zone . All vacuum zone volumes must be accurately programmed and their volumes adequate for their <br /> respective vacuum sensors . All sensors must be installed to detect a leak at the earliest opportunity . <br /> 16 . All appropriate test ports must be installed to facilitate frequent routine communication testing (e . g . at <br /> the beginning and end of each vacuum zone branch and inside brine filled sumps ) . No additional shut <br /> off valves should be installed between the monitored interstitial spaces and their respective sensors . <br /> 17 . Overfill prevention shall satisfy CCR 2635 ( b) (2 ) ( C ) , pursuant to the permit application . No ball floats <br /> shall be installed on vent lines to comply with overfill prevention requirements ( Code of Federal <br /> Regulations , Title 40 , section 280 . 20 ( c) ) <br /> 3 of 4 <br />