My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2019
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
E
>
ELM
>
124
>
2300 - Underground Storage Tank Program
>
PR0231866
>
COMPLIANCE INFO_2019
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
12/15/2020 2:49:24 PM
Creation date
9/14/2020 11:25:19 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2019
RECORD_ID
PR0231866
PE
2361
FACILITY_ID
FA0003957
FACILITY_NAME
AT&T California - UE020
STREET_NUMBER
124
Direction
W
STREET_NAME
ELM
STREET_TYPE
St
City
Lodi
Zip
95240
CURRENT_STATUS
01
SITE_LOCATION
124 W Elm St
P_LOCATION
02
P_DISTRICT
004
QC Status
Approved
Scanner
KBlackwell
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
19
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
S A N J O A Q U I N Environmental Health Department <br /> COUNTY— <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> AT&T California-UE020 124 W Elm St, Lodi February 11, 2019 <br /> Item# Remarks <br /> 209 CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br /> The designated operator failed to document the following: <br /> On the 10/25/18 designated operator(DO)inspection report under <br /> -Section III <br /> The DO failed to add a description to all the components marked N/A or N from section VII through XI. <br /> -Section VI <br /> The OWNER/OPERATOR failed to provide a name, signature, and date within 48 hours of receiving the DO report <br /> under the ACKNOWLEDGMENT OF COMPLIANCE ISSUES section.The report was signed on January 8th, 2019. <br /> On the 11/20/18 designated operator(DO)inspection report under <br /> -Section III <br /> The DO failed to add a description to all the components marked N/A or N from section VII through XI. <br /> -Section VI <br /> The OWNER/OPERATOR failed to provide a name, signature, and date within 48 hours of receiving the DO report <br /> under the ACKNOWLEDGMENT OF COMPLIANCE ISSUES section.The report was signed on January 8th, 2019. <br /> On the 12/21/18 designated operator(DO)inspection report under <br /> The designated operator failed to print the complete alarm history since the previous inspection. The designated <br /> operator failed to print Cl-Belly tank annular. <br /> -Section III <br /> The DO failed to add a description to all the components marked N/A or N from section VII through XI. <br /> -Section V <br /> The owner/operator failed to provide explanation of follow-up actions that will be taken for the statement provided by <br /> the DO in section III. <br /> -Section VI <br /> The OWNER/OPERATOR failed to provide a name, signature, and date within 48 hours of receiving the DO report <br /> under the ACKNOWLEDGMENT OF COMPLIANCE ISSUES section.The report was signed on December 26th, <br /> 2019. <br /> On the 1/21/19 designated operator(DO)inspection report under <br /> -Section III <br /> The DO failed to add a description to all the components marked N/A or N from section VII through XI. <br /> This is a minor violation. <br /> 320 CCR 2635, 2637.2, 2665, 2712 Failure to comply with the installation, inspection, or record keeping of the overfill <br /> prevention. <br /> The automatic tank gauge used as the overfill prevention system was set at 91.6%and not at or below 90%as <br /> require per the regulation. The service technician adjusted the tank diameter in the Veeder Root system to the <br /> correct tank diameter to ensure that the audible and visual alarm activated at 90%.The service technician retested <br /> the overfill prevention equipment with passing results while the inspector was on site. <br /> This was corrected on site. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> FA0003957 PR0231866 SC001 02/11/2019 <br /> EHD 23-01 Rev.09/28/2018 Page 4 of 5 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />
The URL can be used to link to this page
Your browser does not support the video tag.