Laserfiche WebLink
SANJ OA U I Environmental Health Department <br /> COUNTY <br /> — <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> Trinity Parkway AMPM ARCO#183819 10715 Trinity Pkwy, Stockton Aril 26 2019 <br /> Other Violations <br /> 2010 1 See below Unlisted General violation ❑V ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 104 CCR 2711 UST operating permit application for facility and tank information not submitted or current. <br /> UST Tank Information form for the diesel tank is not current in CERS. <br /> -The vapor recovery primary and secondary containment were left blank. <br /> Any change of information must be updated in CERS within 30 days of the changes. Immediately log into CERS, <br /> update the required information, and submit for review by the EHD. <br /> This is a Class II violation. <br /> 107 CCR 2632(d)(1)(C) Plot plan/site map not submitted or failed to completely show where monitoring is performed. <br /> An accurate UST Monitoring Site Plan was not submitted. <br /> -The map did not include the 91 or diesel leak detectors. <br /> A site plan must be submitted identifying the locations where monitoring will be performed. Immediately log into the <br /> California Environmental Reporting System (CERS) at http://cers.calepa.ca.gov/and upload a copy of the UST <br /> Monitoring Site Plan. <br /> This is a minor violation. <br /> 111 CCR 2638(a) & (b), 26410) Failed to test monitoring and leak detection equipment annually. <br /> Annual monitoring system certification and leak detector testing were last performed in March 2018 and was <br /> completed on April 26, 2019 , one month past due. These tests are required once every 12 months. Take all <br /> necessary precautions to ensure testing is performed in a timely manner. <br /> This is a Class II violation. <br /> 113 CCR 2638(c), 2638(d) Failure to submit"Monitoring System Certification Form"within 30 days of completion of the <br /> test. <br /> A monitoring system certification, leak detector testing, and spill container testing were performed in March 2018. <br /> Alarm logs indicate all sensors were tested on March 23, 2018. A test report has not been submitted to the EHD or <br /> the California Environmental Reporting System (CERS). A copy of the test report must be submitted within 30 days <br /> of the test. Immediately provide this report to the EHD. <br /> This is a minor violation. <br /> FA0023650 PRO541281 SCO01 04/26/2019 <br /> EHD 23-01 Rev.09/28/2018 Page 4 Of 6 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />