Laserfiche WebLink
L D T 5000 Field Test Apparatus Page 1 of 1 <br /> L` Tanknology Line Leak Detector Test <br /> Work Order: 2342789 Date: 11/12/2019 <br /> Site Name/ID: CHEVRON#99840 (N31)/99840 <br /> Address: 4344 E WATERLOO RD @ 99 <br /> City: STOCKTON State: CA Zip: 95215 <br /> Tank ID T1 T2 <br /> Product SUPREME REG UNLEAD <br /> Product Line 1 1 <br /> Tested From 4 4 <br /> Existing/New Existing Existing <br /> Mechanical/Electronic Electronic Electronic <br /> Manufacturer/Model Veeder Root PLLD Veeder Root PLLD <br /> Serial No. 012388 327320 <br /> Pump Operating Pressure(psi) 33.00 34.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 <br /> Holding PSI <br /> 'NIA for Electronic LD's <br /> Resiliency(ml) <br /> 'NIA for Electronic Lo's <br /> Metering PSI <br /> for Electronic LD's <br /> Opening Time(sec) <br /> 'N/A for Electronic LD's <br /> Test Results Pass Pass <br /> Technician Comments: <br /> Technician Name: Jarrod Cooke Certification#: 2081 <br /> Technician Signature: <br /> Expire Date: 4/11/2021 <br /> Environmental Compliance for Petroleum Systems <br /> ©2019 Tanknology Inc.,Austin.Tx. All rights reserved. tanknology.ccm <br />