Laserfiche WebLink
I� I ►i ' A ll ' ii ' <br /> anuic io nn ui .: uuicl 12131 S . Dupont Drive , Anuhvirn , CA 928011 <br /> l , 714 ' 50016222 : . r. orn <br /> SUMMARY TEST REPORT FOR USE WITH LEIGHTON O ' BRIEN PM2 LINE TESTER <br /> CLIENT: AT &T UE042 DATE : 7109/2019 <br /> LOCATION : 345 North San Joaquin St . Stockton California 95202 <br /> Street city State <br /> REASON FOR TEST: AT&T Request. Due diligence test. <br /> SPECIAL INSTRUCTIONS : Above ground pressurized line . Leighton O' Brian Diagnostic Report Number TA1 2420 . <br /> I declare under penalty of perjury that I am a licensed tank tester in the State of <br /> California and that the information contained in this report is true and correct to the <br /> best of my knowledge . <br /> TECHNICIAN : Pat Banbury / 90 - 1413 <br /> Name Signature License Number <br /> MAKE AND TYPE OF PUMP OR DISPENSERS Transfer Pump <br /> COVER OVER LINES Above Ground APPROX . BURIAL DEPTH NA <br /> Product Name Line Test Wet Test Start Test End Test Cert No . Test Results <br /> or Dry Time Time Pressure <br /> Diesel UE0420001 / WET 9 : 00 AM 9 : 35 AM 51 . 80 PSI 110815 Pass <br /> UE042AO05 0 . 013 gal /hr. <br /> COMMENTS : Test conducted from UE0420001 above ground transfer pump to UE042AO05 roof top belly tank . <br /> Note : These results need to be submitted with the final Leighton O ' Brien UPSS Test Report. <br />