Laserfiche WebLink
UNDERGROUND STORAGE TANK <br /> SECONDARY CONTAINMENT TESTING REPORT FORM ( Page s of 6) <br /> XVII , FILL RISER SUMP TESTING INFORMATION <br /> Manufacturer Identify Tank ID from Section III for each Manufacturer <br /> N/A AX❑ B ❑ I C ❑ D ❑ <br /> A ❑ I B ❑ I C ❑ I D ❑ <br /> Test Method Used : ❑ Manufacturer Guidelines (Specify) : <br /> Hydostatic <br /> N Industry Code or Engineering Standard (Specify) : PEI RP1200 <br /> ❑ Engineered Method (Specify): <br /> # of Attached Pages <br /> Attach the testing procedures and all documentation required to determine the results. <br /> Fill Riser Sump Testing Training and Certifications (List applicable certifications.) Expiration Date <br /> Franklin Fueling L4 - 1032363709 09-20-2019 <br /> XVIII , COMMENTS <br /> Provide any additional comments here. <br /> UE0460002 Fill Sump - <br /> 9: 00am to 9 : 15am , 4 . 0054" START to 4 . 0053" STOP , 0 . 0001 " Difference - PASSED <br /> 9: 16am to 9 : 31am , 4 . 0053" START to 4 . 0052" STOP , 0 . 0001 " Difference - PASSED <br /> XIX. VENT / TRANSITION SUMP TESTING INFORMATION <br /> Manufacturer Identify Vent t Transition Sump ID from Section III for each Manufacturer <br /> a ❑ I b ❑ c ❑ j d ❑ <br /> a ❑ I b ❑ c ❑ I d ❑ <br /> Test Method Used : ❑ Manufacturer Guidelines (Specify): <br /> ❑ Industry Code or Engineering Standard (Specify): <br /> ❑ Engineered Method (Specify): <br /> # of Attached Pages <br /> Attach the testing procedures and all documentation required to determine the results. <br /> Vent / Transition Sump Testing Training and Certifications (List applicable certifications.) Expiration Date <br /> XX. COMMENTS <br /> Provide any additional comments here. <br /> ID = Identification <br /> i <br />