Laserfiche WebLink
FedEx Ground 4953, Tracy, CA Alarm Log <br /> Sensor and location Alarm Date Work Order Notes: <br /> 375419 - Technician investigated issue on site, could not find any problems <br /> with the sensors or any penetration points. Alarms cleared, continue to <br /> L2 UDC 1 brine sensor 9/23/201719/25/2017, 9/27/2017 375419 monitor. <br /> 378678 - Technician replaced breakaway on disp #1, replaced leaking filters on <br /> L3 UDC 1 sump sensor 12/7/2017 378678 #2, and pressure tested both dispensers with a driver card. <br /> L6 UDC 3 brine sensor 10/3/2017 375750 375750 - work order closed 10/3/2018 - Tech adjusted brine level in UDC. <br /> 375419 - Technician investigated issue on site, could not find any problems <br /> with the sensors or any penetration points. Alarms cleared, continue to <br /> 375419 monitor. <br /> L12 UDC 5/6 brine sensor 9/25/2017,10/2/2017, 10/3/2017 375750 375750 - work order closed 10/3/2018 - Tech adjusted brine level in UDC. <br /> 375419 - Technician investigated issue on site, could not find any problems <br /> with the sensors or any penetration points. Alarms cleared, continue to <br /> 375419 monitor. <br /> L14 UDC 14 brine sensor 9/22/2017, 10/3/2017 375750 375750 - work order closed 10/3/2018 - Tech adjusted brine level in UDC. <br /> L19 Diesel 1 fill brine sensor 1/15/2018 380031 jAddressed while tech was on site for sensor L28 same day. <br /> L21 Diesel 1 STP brine 10/21/2017 376538 Addressed while tech was on site for sensor L16 same day. <br /> L30 Bio Heat brine 10/21/2017 376538 lAddressed while tech was on site for sensor L16 same day. <br /> ill <br /> �I, <br />