Laserfiche WebLink
be/shiire 25971 Towne Centre Drive <br /> Foothill Ranch,CA 92610 <br /> environmental services,Inc. (949)460.5200 <br /> Turbine/Piping Sump Integrity Testing <br /> Hydrostatic Testing Method <br /> Facility: Kaiser Manteca Date: 4/24/2019 <br /> Address: 1777 W, Yosemite Avenue Testing Company: Belshire Environmental Services, Inc. <br /> City, State,Zip: Manteca, CA 95337 Tester Name: Saul Gonzalez <br /> This test is performed in accordance with PEI/RP1200. See Section 6.5 for the test method and procedures. <br /> Containment Sump ID DSL PS <br /> Exempt from Testing No <br /> Containment Sump Total <br /> manufacturer Containment <br /> Containment Sump Fiberglass <br /> material <br /> Liquid and debris Yes <br /> removed from sump?" <br /> Visuallnspection# Pass <br /> Containment Sump 43.5" <br /> Depth <br /> Height From Bottom to <br /> Top of Highest 21" <br /> Penetration <br /> Test Start Time 08:03 AM <br /> Starting Water Level 5.2388 <br /> Test End Time 08:18 AM <br /> Ending Water Level 5.2388 <br /> Water Level Change 0.0000 0.0000 0.0000 0.0000 0.0000 <br /> Test Period 15 Minutes 15 Minutes 15 Minutes 15 Minutes 15 Minutes <br /> Pass/fail criteria:Must pass visual inspection.Water level drop of less than 0.002 inches. <br /> Tact results P st Dl 1 �1{"f� i t D Pait ❑P ssO)Fail D PassD7 Fail D PaSSC.21 ail <br /> Comments: <br /> *All liquids and debris must be disposed of properly. <br /> #No cracks,loose parts or separation of the containment sump. <br /> Technician Signature: �. Date: 4/24/2019 <br /> 1 <br />