Laserfiche WebLink
LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2339109 Date : 1 /8/2019 <br /> Site Name / ID : CHEVRON 201761 / 201761 <br /> Address : 1103 S . MAIN ST. PERMIT NUMB . N-3315 <br /> City: MANTECA State : CA Zip : 95337 <br /> Tank ID T1 Supreme T2 Regular 2 <br /> Product SUPREME REGULAR <br /> Product Line 1 1 <br /> Tested From 11 11 <br /> Existing/New Existing Existing <br /> Mechanical/Electronic Electronic Electronic <br /> Manufacturer/Model Veeder Root PLLD Veeder Root PLLD <br /> Serial No . 404907 unreadable <br /> Pump Operating Pressure (psi ) 40 . 00 45 . 00 <br /> Calibrated Leak (ml/min ) 189 . 0 189 . 0 <br /> Calibrated Leak (gph) 3 . 00 3 . 00 <br /> Holding PSI <br /> ' N/A for Electronic Lo's <br /> Resiliency (ml) <br /> ' N /A for Electronic LD's <br /> Metering PSI <br /> ' NIA for Electronic Lo's <br /> Opening Time (sec) <br /> ' N/A for Electronic Lo's <br /> Test Results Pass Pass <br /> Technician Comments : <br /> Technician Name : Jesus Saldivar Certification # : 115237 <br /> Technician Signature : e`° 6 Expire Date : 12/27/2018 <br /> Environmental Compliance for Petroleum Systems <br /> © 2019 Tanknology Inc, Austin, TX. All rights reserved. tanknology.com <br />