Laserfiche WebLink
SANJ OA U I Environmental Health Department <br /> COUNTY <br /> — <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> EI Dorado Gas & Mart 1 1605 S EL DORADO ST STOCKTON May 31 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 211 CCR 2715(c)(2) No employee present that were trained in the operation and maintenance of the UST system by a DO. <br /> The designated operator employee training for Parvez Akhtar was not performed. Mr. Akhtar was the only employee <br /> on site at the time of inspection. The designated operator shall train facility employees for which he or she is <br /> responsible in the proper operation and maintenance of the UST system once every 12 months. The training shall <br /> include, but is not limited to: <br /> 1. Operation of the UST system in a manner consistent with the facility's best management practices <br /> 2. Employee's role with regard to monitoring equipment as specified in the facility's monitoring plan <br /> 3. Employee's role with regard to spills and overfills as specified in the facility's response plan <br /> 4. Name of the contact person(s)for emergencies and monitoring equipment alarms <br /> Ensure that employees have been trained by the designated operator, maintain the list on site, and submit a copy of <br /> the training records to the EHD. <br /> This is a minor violation. <br /> 215 CCR 2712(1) Failure to retain a copy of the permit to operate at the facility. <br /> A copy of the 2019 UST operating permit was not found on site. A copy of the UST operating permit and all <br /> attachments and conditions shall be retained at the facility. Immediately obtain a copy of the permit and retain it on <br /> site. <br /> This is a minor violation. <br /> 320 CCR 2635, 2637.2, 2665, 2712 Failure to comply with the installation, inspection, or record keeping of the overfill <br /> prevention. <br /> Overfill prevention testing was conducted on May 31, 2019. This testing was required to be conducted by October 13, <br /> 2018. Ensure all future testing is conducted within required time frames. <br /> This is a Class II violation. <br /> Overall Inspection Comments: <br /> The monitoring system certification was conducted today and was not witnessed by EHD in its entirety. Looked <br /> inside all sumps and UDCs. Verified sensor locations and piping communication. According to the technician, all <br /> equipment passed, including overfill prevention flappers. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by June 30, 2019. <br /> Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate ($152). To schedule an <br /> appointment, please call (209) 468-3420. <br /> Documents provided: Return to Compliance Certification form, schedule of free CUPA classes <br /> FA0006185 PRO504388 SCO01 05/31/2019 <br /> EHD 23-01 Rev.09/28/2018 Page 6 Of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />