Laserfiche WebLink
UNDERGROUND STORAGE TANK <br /> MONITORING SYSTEM CERTIFICATION FORM <br /> XII . LINE LEAK DETECTOR TESTING <br /> ❑ Check this box if line leak detectors ( LLD ) are NOT installed . (Do not complete this section .) Y N N/A <br /> This section must be completed if LLDs are installed. <br /> Was a leak simulated to verify LLD performance ? ® ❑ ❑ <br /> (Check all that apply. ) Simulated leak rate verified : ® 3 GPH ❑ 0 . 1 GPH ❑ 0. 2 GPH <br /> Was the test apparatus properly calibrated ? FE <br /> 11El <br /> emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected ? El <br /> For mechanical LLDs, does the LLD restrict the flow through the pipe when a leak is detected ? FlE <br /> For electronic LLDs, does the turbine automatically shut off when a leak is detected ? ❑ ElFor electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or ❑ ❑ <br /> disconnected? <br /> For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a ® ❑ ❑ <br /> test? <br /> For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? E ❑ ❑ <br /> Were all items on the equipment manufacturer' s maintenance checklist completed ? E ❑ I ❑ <br /> Were all LLDs confirmed operational within regulatory requirements? E ❑ ❑ <br /> For any answer of "N" above, describe in Section X111 how and when these issues were or will be corrected. <br /> XIII . COMMENTS <br /> XIV. VACUUM/ PRESSURE/ HYDROSTATIC MONITORING EQUIPMENT TESTING <br /> ❑ Check this box if VPH Monitoring is NOT used . (Do not complete this section.) <br /> This section must be completed if VPH monitoring is used to perform leak detection monitoring. <br /> System Type ( Mark all that apply. ) ® Vacuum ❑ Pressure ❑ Hydrostatic <br /> Sensor ID Component) s) Monitored By This Sensor Sensor Functionality Interstitial <br /> Test Communication Test <br /> S1 87 Product ® Pass ❑ Fail ® Pass ❑ Fail <br /> 52 87 Annular ® Pass ❑ Fail ® Pass ❑ Fail <br /> S3 87 Vent ® Pass ❑ Fail ® Pass ❑ Fail <br /> S4 91 Product ® Pass ❑ Fail ® Pass ❑ Fail <br /> S5 91- DSL Annular ® Pass ❑ Fail 1 ® Pass ❑ Fail <br /> 56 DSL Product ® Pass ❑ Fail ® Pass ❑ Fail <br /> ❑ Pass ❑ Fail I ❑ Pass ❑ Fail <br /> ❑ Pass ❑ Fail I ❑ Pass ❑ Fail <br /> ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> How was interstitial communication verified ? ® Simulated Leak at Far Ends of the Interstitial Space ❑ Visual Inspection <br /> ❑ Other (Describe the method in Section XV below. ) ❑ Gauge <br /> Was the vacuum or pressure restored to operating levels in interstitial spaces? ® Yes ❑ No ( Describe the reason in section XV below . ) <br /> For any answer of "Fail" above, describe in Section XV how and when these issues were or will be corrected. <br /> XV . COMMENTS <br /> r <br /> HE <br /> E <br /> r HIPAH IL <br /> . . <br />