Laserfiche WebLink
LDT 5000 Field Test Apparatus Page 1 of 1 <br />1: Tanknology Line Leak Detector Test <br />Work Order: <br />Site Name / ID: <br />Address: <br />City: <br />2339816 <br />CHEVRON 307709 / 307709 <br />10858 TRINITY PKWY <br />STOCKTON <br />Date: 3/20/2019 <br />State: CA <br />Zip: 95219 <br />Tank ID <br />T1 <br />T-2 <br />T-3 <br />Product <br />UNLEADED <br />PREMIUM <br />Diesel <br />Product Line <br />1 <br />1 <br />1 <br />Tested From <br />11 <br />11 <br />11 <br />Existing/New <br />Existing <br />Existing <br />Existing <br />Mechanical/Electronic <br />Electronic <br />Electronic <br />Electronic <br />Manufacturer/Model <br />Veeder Root PLLD <br />Veeder Root PLLD <br />Veeder Root PLLD <br />Serial No. <br />303074 <br />303057 <br />303058 <br />Pump Operating Pressure (psi) <br />38.00 <br />38.00 <br />42.00 <br />Calibrated Leak (ml/min) <br />189.0 <br />189.0 <br />189.0 <br />Calibrated Leak (gph) <br />3.00 <br />3.00 <br />3.00 <br />Holding PSI <br />'N/A for Electronic Lo's <br />Resiliency (ml) <br />NIA for Electronic LD's <br />Metering PSI <br />NIA for Electronic LD's <br />Opening Time (sec) <br />N/A for Electronic Lo's <br />est Results <br />Pass <br />Pass <br />Pass <br />Technician Comments: <br />Technician Name: Jesus Saldivar <br />Technician Signature: <br />Environmental Compliance for Petroleum Systems <br />©2019 Tankndogy Ina, Austin, TX. All rights reserved. tanknology.com <br />Certification #: 115237 <br />Expire Date: 1 /27/2022 <br />