Laserfiche WebLink
Environmental Health Department <br /> SAN JOAQUIN a <br /> COUNTY— <br /> Underground <br /> OUNTY Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> Fast Lane Central Valle 116 Roth Rd, LathropJune 05, 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item # Remarks <br /> 105 CCR 2632(d)(1), 2634(d) Failed to have an approved UST monitoring plan. <br /> The monitoring plan is not current and/or not approved by the EHD. <br /> For all tanks: <br /> -Under"Pipe Monitoring is Performed Using the Following Method(s)" it states pressure for"Piping Secondary <br /> Containment' however while the inspector was out on site, vacuum for"Piping Secondary Containment"was <br /> observed. <br /> -The monitoring plan did not list the sensor that is being used to monitor the vacuum of the pipe. For"Under <br /> Dispenser Containment(UDC) Monitoring" pressure is listed as"UDC Secondary Containment Monitoring" however <br /> while the inspector was out in the field the UDCs were observed to have interstitial fluid inside the secondary <br /> containment. <br /> Furthermore the monitoring plan for the Diesel south and Diesel north tank in the truck side: <br /> It states yes for"Leak Alarm Triggers Automatic Pump Shutdown" however while the inspector was on the field <br /> S1-diesel south piping sensor and S3-Diesel North piping high liquid alarm did not triggered an automatic pump shut <br /> down. <br /> The monitoring plan must be uploaded to the California Environmental Reporting System (CERS). Immediately log <br /> into CERS, make the necessary changes, and submit for review by the EHD. <br /> This is a repeat violation, Class ll. <br /> 113 CCR 2638(c), 2638(d) Failure to submit"Monitoring System Certification Form" within 30 days of completion of the <br /> test. <br /> Annual monitoring system certification, leak detector testing, and spill container testing was performed on 6/1/18 <br /> (truck side) and 6/8/18 (auto side) and a test report was submitted on 7/23/18, 22 days and 15 days late. A copy of <br /> the test report must be submitted within 30 days of the tests. Take all necessary precautions to ensure testing and <br /> submittal of test reports are performed in a timely manner. <br /> This is a repeat violation, Class Il. <br /> 123 CCR 2637.1(d), 2637.1(e) Failure to submit the "Spill Container Testing Report Form"within 30 days after the test. <br /> Spill container testing was performed on 6/1/18 (truck side) and 6/8/18 (auto side) and a test report was submitted <br /> on 7/23/18, 22 days and 15 days late. A copy of the test report must be submitted within 30 days of the tests. <br /> Take all necessary precautions to ensure testing and submittal of test reports are performed in a timely manner. <br /> This is a repeat violation, Class II. <br /> 204 CCR 2712(i) Current monitoring plan approved by the EHD not found on site. <br /> An approved copy of the monitoring plans were not available for inspection. A copy of these plans shall be <br /> accessible on site at all times. Immediately locate and retain a copy on site. <br /> This is a repeat violation, Class II. <br /> FA0015977 PR0523684 SCO01 06/05/2019 <br /> EHD 23-01 Rev.09/28/2018 Page 5 of 10 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />