Laserfiche WebLink
LDT 5000 Field Test Apparatus Page 1 of 1 <br /> ,j Tanknology Line Leak Detector Test <br /> Work Order: 2346945 Date : 9/9/2020 <br /> Site Name / ID : 7-ELEVEN 14113 , MKT 2368 / 14113 <br /> Address : 3040 BENJAMIN HOLT DR @ GRIGSBY <br /> City: STOCKTON State : CA Zip : 95219 <br /> Tank ID T1 T2 <br /> Product REGULAR SUPREME <br /> Product Line 1 1 <br /> Tested From 2 2 <br /> Existing /New Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-2000 Vaporless LD-2000 <br /> Serial No . 09081368 09071276 <br /> Pump Operating Pressure (psi ) 29 . 00 30 . 00 <br /> Calibrated Leak (ml/min ) 189 . 0 189 . 0 <br /> Calibrated Leak (gph ) 3 . 00 3 . 00 <br /> Holding PSI 29 . 00 30 . 00 <br /> ' N/A for Electronic Lo's <br /> Resiliency (ml ) 125 . 00 125 . 00 <br /> N/A for Electronic Lo' s <br /> Metering PSI 19 16 <br /> ' NIA for Electronic LD' s <br /> Opening Time (sec) 6 10 <br /> ' NIA for Electronic LD's <br /> Test Results Pass Pass <br /> Technician Comments : <br /> Technician Name : Jesus Saldivar Certification #: 115237 <br /> Technician Signature : e`° � � Expire Date : 1 /27/2022 <br /> Environmental Compliance for Petroleum Systems <br /> © 2020 Tankndogy Ina, Austin, TX. All rights reserved. tanknology,mm <br />