Laserfiche WebLink
TABLE 9 <br /> Scope and Frequency of AST Container Inspections and Tests <br /> TEC EQUIPMENT INC. <br /> 2050 East Louise Avenue, Lathrop, California <br /> Tank ID <br /> Diesel 6,000 New Oil Two New and Used <br /> Inspection/Test Gal <br /> Manifolded 1,000 and one Motor Oil <br /> ASTs 120 Gal. ASTs Drums <br /> Visual inspection by Facility personnel M &A M &A M &A <br /> as per checklist of Appendix C <br /> External inspection by certified <br /> inspector(as per STI Standard SP- 20 yrs. NA NA <br /> 001 <br /> Internal inspection by certified <br /> inspector(as per STI Standard SP- 20 yrs. NA NA <br /> 001 <br /> Tank tightness test meeting NA NA NA <br /> requirements of 40 CFR 280 <br /> To initiate the program,ASTs will be inspected by the following dates: <br /> AST IL Implementation of Testing Date <br /> Two 6,000-gallon Diesel AST's Manifolded together Following shell repairs or as directed by local <br /> enforcement agency <br /> Legend: AST:aboveground storage tank <br /> STI:Steel Tank Institute <br /> SP 001:standard and number designation <br /> M:Monthly <br /> A:Annual <br /> Or earlier,as recommended by the certified inspector based on findings from an external inspection. <br /> t Internal inspection may be recommended by the certified inspector based on findings from the external <br /> inspection. <br /> CFR:code of federal regulations <br />