Calculation of Secondary Containment Capacity <br /> TEC EQUIPMENT INC. <br /> 2050 East Louise Avenue, Lathrop, California <br /> AST Containment Capacity: <br /> All ASTs on the facility are double-walled and as such do not require additional containment.Tanks are surrounded by <br /> bollards to prevent accidental collision by vehicles or equipment. <br /> The effective containment capacity is affected by contents within the concrete containment such as: ASTs, ancillary <br /> equipment or other non-necessary items stored within.The berm capacity is also affected by the total largest potential <br /> spill and precipitation that might be held within the containment area. The overall containment capacity calculation <br /> follows and takes the latter items into account. <br /> General containment shape is a rectangle with length (L) of 26 feet and width (W) of 16 feet. The total area (Atot) is <br /> calculated as: <br /> Atot= LXW=26ftX16ft=416ft2 <br /> The total volume of effective containment capacity is based on the minimum height of the concrete containment and is <br /> calculated as: <br /> Vol SC=Anet(416 ft2)X 0.33 ft(minimum height)= 137.3 ft3 <br /> Vol SC gallons= 138.7 ft3 X 7.48 gallons per ft3= 1,026.85 gallons <br /> The secondary containment berm is built to 4 inches and has a retention volume of 1,027 gallons. The tank within is <br /> double-walled, UL Listed and does not require secondary containment. The concrete secondary containment is more <br /> than sufficient to capture minor leaks associated with piping or dispensers within it. <br />