Laserfiche WebLink
S b N J 0 A Q U I N Environmental Health Department <br /> COUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> Colonial Energy CE 40135(DBA Power Mart) 192 Lathrop Rd, Lathrop January 03, 2019 <br /> Item# Remarks <br /> 103 HSC 25292.2,25299.30 Failure to submit and maintain complete and current financial responsibility documents. <br /> current Financial responsibility documents have not been submitted to the EHD. Current financial responsibility <br /> documents are required to be submitted annually. Immediately log into the California Environmental Reporting <br /> System (CERS)at http://cers.calepa.ca.gov/, and upload the required documents. <br /> This is a repeat violation, Class II. <br /> 104 CCR 2711 UST operating permit application for facility and tank information not submitted or current. <br /> UST Tank Information forms for the all four tanks are not current in CERS. The under tank construction for overfill <br /> protection it states YES for"audible and visual alarm" however there was no annunciator found on site. Any change <br /> of information must be updated in CERS within 30 days of the changes. Immediately log into CERS, update the <br /> required information, and submit for review by the EHD. <br /> This is a Class II violation. <br /> 211 CCR 2715(c)(2) No employee present that were trained in the operation and maintenance of the UST system by a <br /> DO. <br /> The designated operator employee training for Casey Smith was not performed . The designated operator shall <br /> train facility employees for which he or she is responsible in the proper operation and maintenance of the UST <br /> system once every 12 months. The training shall include, but is not limited to: <br /> 1. Operation of the UST system in a manner consistent with the facility's best management practices <br /> 2. Employee's role with regard to monitoring equipment as specified in the facility's monitoring plan <br /> 3. Employee's role with regard to spills and overfills as specified in the facility's response plan <br /> 4. Name of the contact person(s)for emergencies and monitoring equipment alarms <br /> Ensure that employees have been trained by the designated operator, maintain the list on site, and submit a copy of <br /> the training records to the EHD. <br /> The designated operator that was on site, trained Casey Smith while the inspector was on site to correct this on site. <br /> This was corrected on site. <br /> This is a repeat violation, Class II. <br /> 301 HSC 25292.1(a)UST system is not operated to prevent unauthorized release, including spills and overfills. <br /> A seepage was observed the fuel filter and meter located in dispenser 11.The underground storage tank system <br /> shall be operated to prevent unauthorized releases. Immediately Immediately repaired or replaced by a properly <br /> licensed, trained, and certified contractor under permit and inspection of the EHD, if needed and provide proof of <br /> repair to EHD. <br /> This was corrected on site. <br /> This is a repeat violation, Class II. <br /> FA0007059 PR0505867 SCO01 01/03/2019 <br /> EHD 23-01 Rev.09/28/2018 Page 4 of 6 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />