Laserfiche WebLink
1115000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2342147 Date : 9/11 /2019 <br /> Site Name / ID : 7- ELEVEN 14113 , MKT 2368 / 14113 <br /> Address : 3040 BENJAMIN HOLT DR @ GRIGSBY <br /> City: STOCKTON State : CA Zip : 95219 <br /> Tank ID T 1 T2 <br /> Product REGULAR SUPREME <br /> Product Line 1 1 <br /> Tested From 4 4 <br /> Existing/New Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-2000T18 <br /> 00 <br /> Serial No . 09081368 <br /> Pump Operating Pressure ( psi) 30 . 00 <br /> Calibrated Leak (mllmin ) 189 . 0 <br /> Calibrated Leak (gph) 3 . 00 3 . 00 <br /> Holding PSI 30 . 00 30 . 00 <br /> ' NIA for Electronic LD's <br /> Resiliency (ml) 140 . 00 290 . 00 <br /> ` NIA for Electronic LD's <br /> Metering PSI 17 20 <br /> ' NIA for Electronic LD's <br /> Opening Time (sec) 9 8 <br /> ' NIA for Electronic LD's <br /> est Results Pass Pass <br /> Technician Comments : <br /> Technician Name : JesusSaldivar Certification # : 115237 <br /> Technician Signature : 4w 444 Expire Date : 1 /27 /2022 <br /> Environmental Compliance for Petroleum Systems <br /> © 2019 Tank nology Inc., Austin, TX. All rights reserved. tanknology.com <br />