Laserfiche WebLink
Time In: <br /> Time Out: <br /> opQ.�tN. San Joaquin County <br /> .X Environmental Health Department <br /> 1868 East Hazelton Avenue, Stockton, CA 95205-6232 <br /> • �... P Telephone: (209)468-3420 Fax:(209)464-0138 Web:www.sigov.org/ehd <br /> �<<FORtN <br /> Underground Storage Tank Program Service Request Inspection Report <br /> Name of Facility: MAIN STREET ARCO AM PM" Date: 11/26/2019 <br /> Address: 1100S MAIN ST , MANTECA 95337 <br /> Requestor: GUADALUPE SANCHEZ, DIAMOND PETROLEUM SERVICES INC Telephone: (925)470-0803 <br /> Program Element: 2308-UST RETROFIT Request#: SR0081170 <br /> Inspection Type: 298-UST RETROFIT REPAIR INSPECTION <br /> Onsite Service Technician: Guadalupe Sanchez ICC Service Tech/Installer Exp. Date: 04/05/2021 <br /> Manufacturer training: OPW, 06/07/21 <br /> OVERALL INSPECTION NOTES AND COMMENTS <br /> NOTES <br /> On site for the following inspections: <br /> -Verified overfill prevention measurements for the 87 west, 87 east, 89, and 91 tanks.Verified all were less than 95%. <br /> -Verified removal of ball floats in all tanks. <br /> -Observed start of spill container testing for the 91 tank spill container. <br /> Facility is approved to receive fuel. <br /> The person in charge is responsible for ensuring that the above mentioned facility is in compliance with all applicable sections of the California Health and <br /> Safety Code.If a reinspection is required,fees will be assessed at the current hourly rate. <br /> Received by: Name and Title: Guadalupe Sanchez, Service Technic <br /> EH Specialist: SHEWIT WOLDEAREGAY Phone: (209)468-0216 <br /> FA0007464 SR0081170 SC298 11/26/2019 <br /> EHD 23-01 Rev.06/30/15 Page 1 of 1 Underground Storage Tank Program Service Request Inspection Report <br />