SAN ) O A Q U I N Environmental Health Department <br /> _ COUNTY -- - - s <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address : Date: <br /> ORLANDOS 18754 E HWY 26 , LINDEN July 02 , 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I, CLASS II, or MINOR - Notice to Comply) <br /> Item # Remarks <br /> 318 CCR 2666(c) , 2643(c) ( 1 ) Leak detector failed to detect a 3 . 0 gallons per hour leak at 10 pounds per square inch . <br /> The 87 and 91 product VMI line leak detectors failed to detect a leak when tested . All line leak detectors shall be <br /> capable of detecting a 3-gallon per hour leak at 10 psi . The service technician adjusted the leak detector, retested <br /> it, and it passed . <br /> This was corrected on site. <br /> This is a minor violation . <br /> 320 CCR 2635 , 2637 . 21 2665 , 2712 Failure to comply with the installation , inspection , or record keeping of the overfill <br /> prevention . <br /> This facility does not have an approved overfill prevention system . According to the site's tank form , the site is <br /> using audible/visual alarms and ball float as their overfill protection . The site's Overfill Prevention Equipment <br /> Inspection Report Form dated 9/28/2019 , stated that there are no ball floats. The site has single walled vent piping <br /> and was installed in 2001 , therefore, the site cannot use audible/visual alarms only as the only means of overfill <br /> protection . Verify the presence of ball floats , if the site has existing ball floats , have them inspected for the 36 <br /> months testing and submit test results. Immediately schedule these tests and provide 48 hours notification to the <br /> EHD . <br /> This is a Class II violation . <br /> Overall Inspection Comments : <br /> An inspection report was provided to the facility operator on the day of inspection . The report was amended by <br /> the EHD . The amended report replaces the initial report. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation , and any supporting <br /> paperwork , within 30 days of receiving the amended inspection report. <br /> Starting September 1 , 2018 , all in-office CERS help will be provided at EHD hourly rate ($ 152) . To schedule an <br /> appointment , please call (209) 468-3420 . <br /> Documents provided : <br /> - Return to compliance certification <br /> - Designated Understanding Storage Tank Operator Identification Form <br /> -Statement of Understanding and Compliance Form <br /> - EHD class schedule <br /> FA0007722 PRO507164 SCO01 07/02/2019 <br /> EHD 23-01 Rev. 09/28/2018 Page 5 of 6 Underground Storage Tank Program OIR <br /> 1868 E . Hazelton Avenue I Stockton , California 95205 1 T 209 468-3420 1 F 209 464-0138 I www. sjcehd . com <br />