Laserfiche WebLink
LDT 5000 Field Test Apparatus Page 1 of 1 <br /> LA Tanknology Line Leak Detector Test <br /> Work Order: 2339111 Date : 1 / 17/2019 <br /> Site Name / ID : CHEVRON 208118 N -4087- 1 -3 / 208118 <br /> Address : 3355 E . HAMMER LANE @ HOLMAN RD <br /> City: STOCKTON State : CA Zip : 95212 <br /> Tank ID T1 T2 <br /> Product SUPREME REGULAR <br /> Product Line 1 1 <br /> Tested From 1 1 <br /> ExistinglNew Existing Existing <br /> Mechanical/ Electronic Electronic Electronic <br /> Manufacturer/Model Veeder Root PLLD Veeder Root PLLD <br /> Serial No . 005877 038145 <br /> Pump Operating Pressure (psi ) 30 . 00 30 . 00 <br /> Calibrated Leak (ml /min ) 189 . 0 189 . 0 <br /> Calibrated Leak (gph ) 3 . 00 3 . 00 <br /> Holding PSI <br /> ' NIA for Electronic LD's <br /> Resiliency (ml) <br /> ' NIA for Electronic Lo's <br /> Metering PSI <br /> ' N/A for Electronic Lo 's <br /> Opening Time (sec) <br /> ' NIA for Electronic Lo' s <br /> Test Results Pass Pass <br /> Technician Comments : <br /> Technician Name : Brent Bowen Certification # : 99937 <br /> Expire Date : 8/8/2019 <br /> Technician Signature : <br /> Environmental Compliance for Petroleum Systems <br /> © 2019 Tanknology Inc., Austin, Tx. All rights reserved. tanknology.com <br />