ELECTRICAL POWER SYMBOLS ELECTRICAL LIGHTING SYMBOLS SINGLE LINE DIAL. SYMBOLS ELECTRICAL GENERAL NOTES
<br /> RECEPTACLES
<br /> 20A, 125V SINGLE OUTLET, HUBBELL5361 OR EQUAL FUSE, RATING AS INDICATED 1. ALL ELECTRICAL SHALL BE INSTALLED IN ACCORDANCE WITH 2016 CBC, 2016 CGBC, DOLLAR, GENERAL
<br /> (MOUNT +16" TO BOTTOM AS NOTED)
<br /> # 2016 CEC, ALL APPLICABLE LOCAL CODES, AND AS DIRECTED BY THE PROJECT ENGINEER.
<br /> 2' X 4' LAY-IN FLOURESCENT FIXTURE, VOLTAGE AS INDICATED, 2. ALL ELECTRICAL WORK REQUIRES CITY INSPECTION. ELECTRICAL WORK COVERED OR
<br /> 20A, 125V DUPLEX OUTLET, HUBBELL #5362 OR EQUAL (DRAWN TO SCALE) GROUND WIRE EXTENDED AND CONNECTED TO ENCLOSED PRIOR TO CITY ELECTRICAL INSPECTION SHALL BE UNCOVERED FOR INSPECTION
<br /> (MOUNT +16" TO BOTTOM OR AS NOTED) = APPROVED GROUND (#12 MINIMUM IF NOT SHOWN) AND REPLACED AT NO EXPENSE. STORE # 14661
<br /> 2' X 4' LAY-IN FLOURESCENT FIXTURE CONNECTED TO EMERGENCY
<br /> 20A, 125V DUPLEX OUTLET, HUBBELL #5362 OR EQUAL - INTEGRAL GFCI CIRCUITRY LIGHTING CIRCUIT OR WITH A MIN. OF 90 MINUTES BATTERY BACK-UP, 3. BID ALTERNATE - EXISTING CONDITIONS OBSERVED AND IDENTIFIED DURING THE PREBID
<br /> (MOUNT +16" TO BOTTOM OR AS NOTED) (DRAWN TO SCALE) 1/3 - POLE CIRCUIT BREAKER SITE INSPECTION THAT ARE NOT ACCORDING TO THE LATEST CODE REQUIREMENTS AND 1940 McHENRY AVENUE
<br /> DOUBLE DUPLEX TWO 20A, 125V DUPLEX OUTLETS, HUBBELL #5362 2' X 2' LAY-IN FLOURESCENT FIXTURE, VOLTAGE AS INDICATED, ARE NOT NOTED ON THE DESIGN DRAWINGS SHALL BE INCLUDED WITH THE BID SUBMITTAL
<br /> (MOUNT +16" TO BOTTOM OR AS NOTED) AS AN ALTERNATE. ESCALONE, CA
<br /> (DRAWN TO SCALE) THERMAL OVERLOAD/HEATER ELEMENT
<br /> SINGLE FACE EXIT SIGN, TYPE AS INDICATED, 4. ALL CONDUIT SHALL CONTAIN A CODE SIZE GROUND WIRE (#12 AWG MINIMUM).
<br /> 30A, 120V, 1�, RECEPTACLE � ® SHADED PORTION INDICATES FACE OF THE EXIT SIGN. ARROW INDICATES DIRECTION. �,,
<br /> TRANSFORMER 5. ALL CONDUIT RUNS TO BE MECHANICALLY AND ELECTRICALLY CONTINUOUS AND RUN
<br /> EXIT LIGHT, SINGLE FACE - WALL MOUNTED. ARROW INDICATES DIRECTION. "yr PARALLEL Al PERPENDICULAR TO BUILDING LINES.
<br /> O 30A, 250V, 10, RECEPTACLE � � SHADED PORTION INDICATES FACE OF THE EXIT SIGN.
<br /> CIRCUIT BREAKER, LOW VOLTAGE (AS SPECIFIED), 6. ALL WIRE SPLICES, TAPS AND JOINTS SHALL BE MADE WITH APPROVED COMPRESSION
<br /> ® SPECIAL PURPOSE RECEPTACLE 8 DOUBLE FACE EXIT SIGN, TYPE AS INDICATED DRAW-OUT TYPE TYPE CONNECTORS. "SCOTCH-LOK" TYPE CONNECTORS ARE APPROVED FOR CONNECTION
<br /> (SHADED PORTION INDICATES FACE OF THE EXIT SIGN & ARROW INDICATES DIRECTION) TO LIGHT FIXTURES ONLY.
<br /> �® FUSED DISCONNECT SWITCH
<br /> C 20A, 250V, 10, RECEPTACLE 7. THE CONTRACTOR SHALL REPLACE Al REPAIR ALL WALLS, CEILINGS, DOORS,
<br /> $A 20A, 120/277V, SPST TOGGLE TYPE SWITCH, SMALL LETTER INDICATES EQUIPMENT, WIRING, CONDUIT, ETC., WHICH ARE DAMAGED OR REMOVED BY CONTRACTOR
<br /> SWITCH LEG (MOUNT AT +46" TO BOTTOM OR AS NOTED) CIRCUIT BREAKER, MEDIUM VOLTAGE (AS SPECIFIED), TO THE SATISFACTION OF THE PROJECT ENGINEER.
<br /> 30A, 250V, 32, TWIST LOCK RECEPTACLE DRAW-OUT TYPE
<br /> $3 20A, 120/277V, 3-WAY TOGGLE TYPE SWITCH 8. ALL LAY-IN TYPE LIGHT FIXTURES SHALL BE SECURED WITH SCREWS IN ALL 4 CORNERS
<br /> 480V, 10, RECEPTACLE AMPS/kW AS NOTED
<br /> MOUNT AT +46" TO BOTTOM OR AS NOTED) DISCONNECT SWITCH AND WITH 2 SLACK WIRES ON DIAGONAL CORNERS, PER NEC AND IBC REQUIRMENTS.
<br /> DIMMER SWITCH, TYPE AND RATING AS NOTED 9. THE CONTRACTOR SHALL REMOVE ALL LIGHT FIXTURE BALLASTS CONTAINING. PCB AS
<br /> $D DIRECTED BY THE PROJECT ENGINEER. IN BRIEF, THE CONTRACTOR SHALL REMOVE THE
<br /> ■ 480V, 30, RECEPTACLE AMPS/kW AS NOTED (MOUNT AT +46" TO BOTTOM OR AS NOTED) VFD VARIABLE FREQUENCY DRIVE BALLASTS AND DEPOSIT THEM IN A SPECIALLY MARKED DRUM FURNISHED BY THE
<br /> PROJECT MANAGER AT THE JOB SITE.
<br /> K
<br /> 20A, 120/277V, KEYED SWITCH STARTER
<br /> BOX AROUND ANY OUTLET INDICATES OUTLETS INSTALLED IN FLOOR (MOUNT AT +46" TO BOTTOM OR AS NOTED) 10. ALL MATERIALS SHALL BE NEW AND UNUSED, AND OF THE BEST QUALITY. ALL MATERIAL
<br /> INSTALLED SHALL BE U.L. LISTED OR AS REQUIRED BY LOCAL BUILDING CODES.
<br /> 20A, 250V, 30, TWIST LOCK RECEPTACLE $OS WALL MOUNTED OCCUPANCY SENSOR WITH MANUAL OVERRIDE SWITCH SPECIAL SYSTEMS SYMBOLS 11. ALL CONDUIT ROUTED THROUGH THE ROOF OR OUTSIDE WALL SHALL BE MADE
<br /> (MOUNT AT +46" TO BOTTOM OR AS NOTED)
<br /> WATERTIGHT. OWNER
<br /> 250V, 10, RECEPTACLE AMPS/kW AS NOTED OS CEILING MOUNTED OCCUPANCY SENSOR 12. ALL CONCRETE AND BLOCK WALL PENETRATIONS SHALL BE CORE DRILLED. COORDIANTE
<br /> GB SECURITY SYSTEM GLASS BREAK SENSOR WITH LANDLORD PRIOR TO CORE DRILLING.
<br /> O 250V, 30, RECEPTACLE AMPS/kW AS NOTED O-i WALL MOUNTED LIGHT FIXTURE 13. THE CONTRACTOR SHALL PROVIDE ALL FUSES AND CIRCUIT BREAKERS WHERE REQUIRED
<br /> CR SECURITY SYSTEM CARD READER BY THE NEW CONSTRUCTION DOCUMENTATIONS.
<br /> OTHER POWER SYMBOLS O 14. VERIFY VOLTAGE, CURRENT AND PHASES FOR ALL EQUIPMENT TO BE INSTALLED INCLUDING DOLLAR GENERAL
<br /> CEILING MOUNTED LIGHT FIXTURE OWNER FURNISHED EQUIPMENT. VERIFY PROPER ROTATION AS DIRECTED BY THE PROJECT 100 MISSION RIDGE
<br /> $M TOGGLE TYPE MANUAL MOTOR TYPE SWITCH WITH THERMAL OVERLOAD PROTECTION KP SECURITY SYSTEM KEYPAD ENGINEER PRIOR TO ENERGIZING MOTOR DRIVEN EQUIPMENT.
<br /> WITH LOCK-OUT KIT, TYPE AS NOTED (MOUNT AT +46" TO BOTTOM OR AS NOTED) C�7GOODLETTSVILLE, TN 37072
<br /> EMERGENCY LIGHT FIXTURE WITH TWIN HEAD, BATTERY AND CHARGER, WALL MOUNTED 15. ALL EMERGENCY CIRCUIT J-BOX COVERS TO BE PAINTED BLUE AND THE CONDUIT TO
<br /> JUNCTION BOX 4 11/16" SQ. X 2 1/8" D (MINIMUM)
<br /> O MD MOTION DETECTOR
<br /> HAVE A BLUE STRIPE EVERY 30'-0".
<br /> PP POWER PACK FOR CEILING MOUNTED OCCUPANCY SENSOR MIC MICROPHONE JACK 16. ALL ELECTRICAL PANELS, DISCONNECTS, CABINETS, CONTROLS, RECEPTACLES, J-BOXES,
<br /> ISI EXTERNALLY OPERATED FUSIBLE DISCONNECT SWITCH, SIZE AND ETC. SHALL BE MARKED, TAGGED AND IDENTIFIED. NOTE FEEDER SOURCE WHERE
<br /> u TYPE AS NOTED APPLICABLE.
<br /> P®
<br /> COMBINATION MAGNETIC STARTER AND FUSIBLE DISCONNECT SWITCH, SIZE AND SOUND SYSTEM SPEAKER JACK
<br /> CONTROL DIAGRAM SYMBOLS 17. POWER ACTIVATED ANCHORS ("RAMSET") SHALL NOT BE USED WITHIN ANY BUILDINGS OR REVISIONS
<br /> TYPE AS NOTED
<br /> DS DOOR SWITCH/CONTACT STRUCTURES.
<br /> ® SINGLE PHASE STARTER W/ H.O.A. 18. CONTRACTOR SHALL FIELD VERIFY ROUTING/LOCATION OF ALL CONDUIT AND EQUIPMENT
<br /> PRIOR TO ORDERING MATERIALS.
<br /> TC TIME CLOCK
<br /> U MOTOR 19. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER TRADES AS REQUIRED.
<br /> E2 VARIABLE FREQUENCY DRIVE �• LIMIT SW. N.O. Da CCTV SYSTEM CAMERA 20. CONTRACTOR SHALL PROVIDE ALL MATERIALS EXCEPT AS NOTED AND MAKE ALL
<br /> NECESSARY CONNECTIONS TO NEWLY INSTALLED EQUIPMENT.
<br /> ABBREVIATIONS -� LIMIT SW. N.C.
<br /> O INTERCOM SPEAKER 21. THE OWNER MUST APPROVE ALL POWER Al SAFETY SYSTEM OUTAGES REQUIRED TO
<br /> COMPLETE THE PROJECT.
<br /> MR MUD RING ONLY 22. UPON COMPLETION OF THE PROJECT, ALL CHANGES SHALL BE DOCUMENTED, AND
<br /> • LIMIT SW. HELD OPEN REDLINED AS-BUILT DRAWINGS SHALL BE TURNED OVER TO THE OWNER BY THE
<br /> A AMPERES ©G COMBINATION CLOCK & INTERCOM SPEAKER CONTRACTOR.
<br /> AC AT 6" ABOVE COUNTER • (WALL MOUNTED) 23. CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR, PATCHING, AND PAINTING OF ALL
<br /> �— LIMIT SW. HELD CLOSED FINISHES AFFECTED BY THIS WORK INCLUDING THE RESEALING OF FIRE WALL BREACHES.
<br /> AG ABOVE GROUND
<br /> AP WIRELESS ACCESS POINT 24. CONTRACTOR SHALL FIELD VERIFY LOCATIONS OF ALL EXISTING UNUSED CONDUIT AND
<br /> AIC AMPS INTERRUPTING CURRENT �• TIMER CONTACT ON DELAY W
<br /> N.C.T.C. J-BOXES AND REUSE THE SAME AS NECESSARY.
<br /> C.B. CIRCUIT BREAKER TIMER CONTACT ON DELAY /25. ALL WIRING SHALL BE DUAL RATED THHN THWN STRANDED COPPER UNLESS NOTED
<br /> CKT CIRCUIT ~� N.C.T.0. OTHERWISE.
<br /> Cl CEILING COMMUNICATIONS SYMBOLS 26. WIRE COLOR CODE:
<br /> CU COPPER • THERMAL SW, N.O.
<br /> A) 208Y/120V 480Y/277V
<br /> EDF ELECTRIC DRINKING FOUNTAINPHASE A BLACK BROWN
<br /> THERMAL SW. N.C. Zk COMBINATION TELEPHONE/DATA OUTLET AT +16" TO BOTTOM (OR AS NOTED) PHASE B RED ORANGE
<br /> PHASE C BLUE YELLOW
<br /> E PREFIX FOR EMERGENCY
<br /> EC EMPTY CONDUIT WITH PULL STRING0-7 NEUTRAL WHITE GRAY
<br /> o PRESSURE SW. N.O. 1j FLOOR MOUNTED TELEPHONE OUTLET GROUND GREEN GREEN CONSULTANT
<br /> EMO EMERGENCY POWER-OFF �� B)
<br /> IX TELEPHONE OUTLET AT +16" TO BOTTOM (OR AS NOTED) CONTROL------------------------- RED
<br /> EX EXISTING PRESSURE SW. N.C. Zee
<br /> (X INDICATES NUMBER OF JACKS, IF MORE THAN ONE) NEUTRAL------------------------- WHITE
<br /> FOT FIBER OPTIC TRANSMITTERPOWER --------------------------BLACK Engineering
<br /> DATA OUTLET AT +16"
<br /> �
<br /> LEVEL SW. N.O. �X (X INDICATES NUMBER OFOJAOCKS ,, IF(OR MORE THO
<br /> FU FUSE AN ONE) EXTERNALLY ENERGIZED CONTROL WIRE------ YELLOW E E Group, LLC•
<br /> FWE FURNISHED WITH EQUIPMENT 27. TELEPHONE AND DATA CABLE:
<br /> LEVEL SW. N.C. A) IN SHOP AREAS-THE CONTRACTOR SHALL PULL ALL TELEPHONE AND DATA CABLE AS 7
<br /> GFCIGROUND FAULT CIRCUIT INTERRUPTER FURNISHED BY THE OWNER AND COIL 15 FEET AT EACH END. MARK AND TAG BOTH ENDS
<br /> GROUNDING SYMBOLS AS DIRECTED BY THE PROJECT ENGINEER. Suit S Alma School Road,
<br /> GFP GROUND FAULT PROTECTION o FLOW SW. N.O. Suite 120 V. 480.222.8835
<br /> B) IN OFFICE AREAS-INSTALL OUTLET BOX FOR TELEPHONE AND DATA WHERE SHOWN ON Mesa, Arizona 85210 F. 480.222.8836
<br /> GND GROUND THE DRAWINGS AND PROVIDE PULL STRING FROM OUTLET BOX TO ABOVE CEILING. PUNCH 20021 EO1.dwg
<br /> HPC HIGH PRESSURE CONTACT 7 FLOW SW. N.C. HOLES THROUGH CROSS MEMBERS, INSTALL GROMMETS AND ROUTE PULL STRING THROUGH
<br /> O GROUNDING ROD TEST WELL GROMMETS, CABLE TO BE INSTALLED BY OWNER. SEAL
<br /> IG ISOLATED GROUND TW
<br /> 28. PRIME AND PAINT ALL EXPOSED UNFINISHED METAL PARTS, AS DIRECTED BY THE PROJECT `
<br /> KA KILOAMPERES ENGINEER.
<br /> NORMALLY OPEN PUSHBUTTON (MOMENTARY) • EXOTHERMIC WELD PROFESS/pNq
<br /> kVA KILOVOLT - AMPERES 29. ALL MOUNTINGS HEIGHTS FOR BOXES ARE FROM FINISHED FLOOR TO THE CENTER OF BOX, �F,� MUK Sl �.
<br /> n I � UNLESS OTHERWISE NOTED. ��
<br /> 0 NORMALLY CLOSED PUSHBUTTON (MOMENTARY)
<br /> kW KILOWATT T—T GROUND BUS 30. ALL TRASH AND DEBRIS SHALL BE REMOVED FROM THE BUILDING AT THE END OF EACH v
<br /> LFMC LIQUIDTIGHT FLEXIBLE METAL CONDUIT DAY OR AS DIRECTED BY THE CONSTRUCTION COORDINATOR. E18714
<br /> • TIMER CONTACT OFF DELAY EXP.03-31-21
<br /> LT LIQUID TIGHT CONDUIT N.C.T.C. EARTH/CHASIS GROUND 31. ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS.
<br /> F
<br /> LTG LIGHTING NI CEROCONTACT OFF DELAY = 32. 4" HOUSE KEEPING PADS SHALL BE FURNISHED FOR ALL FLOOR MOUNTED ELECTRICAL `l'TgTF�ECTR
<br /> ICP
<br /> MCS MOLDED CASE SWITCH EQUIPMENT, BY OTHERS. OF CA��F
<br /> M.O. MANUALLY OPERATED OO FOOT SW. N.O. GROUNDING RISER UP TO LIGHTNING PROTECTION 33. REFER TO INSTRUMENTATION AND CONTROL DRAWINGS FOR MOTOR STARTER SCHEMATICS.
<br /> MT MOUNT O�Q FOOT SW. N.C.
<br /> NF NON FUSED MISCELLANEOUS SYMBOLS
<br /> NL NIGHT LIGHT G PILOT LIGHT
<br /> PC POWER CENTER \ 0 _ 2 - POSITION SELECT SWITCH
<br /> sm
<br /> PNL PANEL / ARCHITECTS
<br /> PWR POWER
<br /> +1_ 0
<br /> 1 REVISION NOTE TAG. 2423 Edwards Street
<br /> REC RECEPTACLE — 3 - POSITION SELECT SWITCH Berkeley, CA 94702
<br /> RGS RIGID GALVANIZED STEEL do
<br /> Q O O KEYED NOTES T: 510.655. 1922
<br /> SB STRAIGHT BLADE o
<br /> ILLUMINATED PUSH BUTTON
<br /> SES SERVICE ENTRANCE SECTION TITLESYMBOLS,
<br /> TL TWIST LOCK NOTE:
<br /> PILOT LIGHT 75 CONDUIT TYPES ABBREVIATIONS AND
<br /> TTB TELEPHONE TERMINAL BOARD
<br /> Q UC UNDER COUNTER NOT ALL SYMBOLS, ABBREVIATIONS AND NOTES APPLY TO THIS PROJECT. GENERAL NOTES
<br /> CD �
<br /> CM USB USB PORT (WITH DUPLEX RECEPTACLE) o- ,U� PILOT LIGHT, PUSH TO TEST UNDERGROUND CONDUIT ISSUED
<br /> SHEET
<br /> o _q
<br /> V VOLTS
<br /> CONDUIT UP
<br /> LU CONDUIT DOWN 7/24/2020
<br /> �
<br /> N o VCB VACUUM CIRCUIT BREAKER RELAY COIL
<br /> �o HOME RUM TO PANELBOARD OR AS NOTED
<br /> SUBMITTAL
<br /> VFD VARIABLE FREQUENCY DRIVE
<br /> TN CONDUIT STUB-OUT, MARK AND CAP AS DIRECTED
<br /> CD
<br /> N WH WATER HEATER STARTER COIL WITH OVERLOAD BREAK IN CONDUIT
<br /> oa EOO 1
<br /> WP WEATHERPROOF " �
<br /> JOB NO.
<br /> o a)
<br /> E XFMR TRANSFORMER
<br /> 20021
<br /> COPYRIGHT© PSM ARCHITECTS, INC 2020
<br />
|