Laserfiche WebLink
SWRCB , January 2002 Page of <br /> 6. PIPING SUMP TESTING <br /> Test Method Developed By : Sump Manufacturer Industry Standard X Professional Engineer <br /> Other (Specify) _ <br /> Test Method Used : Pressure Vacuum — X Hydrostatic <br /> Other (Specify) <br /> Test Equipment Used : Caldwell Level Change Indicator Equipment Resolution : . 002 <br /> fSump # 1 -87 Sump # 2-91 Sump # 3-Diesel Sump # <br /> Sump Diameter : 48" 48" 48 " <br /> Sump Depth : 71 " — 67 68" <br /> Sump Material : Fiberglass Fiberglass Fiberglass <br /> Height from Tank Top to Top of 10" 14" 14' <br /> Highest Piping Penetration : — <br /> Height from Tank Top to Lowest 22„ 21 " 22» <br /> F. leetrical Penetration : — ---- -- —____-- _ <br /> Condition of sump prior to testing: Dry Dry Dry <br /> Portion of Sump TestedWater Level 26" Water Level 25 " Water Level 26" — <br /> Does turbine shut down when <br /> sump sensor detests liquid ( both Yes Yes Yes <br /> product and water , . <br /> Turbine shutdown response time Not Alarmed Not Alarmed Not Alarmed <br /> Is system programmed for fail -safe Yes Yes Yes <br /> shutdown?' — <br /> Was fail -safe verified to be No No No <br /> operational ?* <br /> Wait time between applying WFater 5 Minutes 5 Minutes 5 Minutes <br /> and startin test : <br /> "Test Start Time : 8 : 52 8 :02 8 : 07 _ <br /> Initial Reading ( Ri ) : . 001 . 001 . 001_ <br /> Test End Time : 1 9 : 22 8 : 32 8 : 37 <br /> Final Reading ( RO : . 001 .001 .001 <br /> Test Duration : 30 Minutes 30 Minutes 30 Minutes <br /> Change in Reading ( RF- Rj ) : 0 — 0 -� 0 — <br /> Pass/Fail Threshold or Criteria: . 005/30 Minutes .005/30 Minutes .005/30 Minutes <br /> Test Result , - — Pass Pass- — -- _ Pass _ <br /> Was sensor removed for testing? Yes _ Yes , L-- — Yes <br /> Was sensor properly replaced and Yes Yes --�-- Yes <br />[ verified functional after <br /> Comments — ('include infot •tttatiutt on repairs made prior to testing, and reconunended follotit�-tip for failed tests) _ <br /> if the entire depth of the sump is not tested , specify how much was tested . If the answer to any of the questions indicated with an <br /> asterisk ( * ) is "NO" or "NA ", the entire sump must be tested . ( See SWRCB LG- 160 ) <br />