Laserfiche WebLink
A J OA U I Environmental Health Department <br /> COUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> A&A GAS FOOD MART 1 1330 E YOSEMITE AVE, MANTECA November 18, 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 206 CCR 2712 Failure to comply with UST operating permit conditions. <br /> OBSERVATION: The Monitoring panel software was updated on 9/20/2019 and a permit/notification was not <br /> obtained from the EHD. <br /> REGULATION GUIDANCE: Emergency repairs relating to UST system monitoring and release detection may be <br /> performed by a properly licensed, trained, and certified contractor pursuant to the EHD's policy and a permit <br /> obtained within one business day from the EHD. All other repairs must have a permit submitted to and approved by <br /> the EHD prior to beginning work. <br /> CORRECTIVE ACTION: Immediately obtain a permit from the EHD for the [UST COMPONENT REPAIR OR <br /> REPLACEMENT] . A"Failure to Obtain a Permit" penalty applies. <br /> This is a minor violation. <br /> 209 CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br /> OBSERVATION: The designated operator failed to document all the alarms from the attached alarm history on the <br /> 7/26/19 designated operator inspection report and failed to check that they were responded to appropriately. The <br /> missing alarms include: L 7 dispenser#1/2. <br /> -The designated operator inspection report of 6/28/2019 was not signed and dated by the owner/operator. <br /> REGULATION GUIDANCE: During the inspection, the designated operator shall review the alarm history since the <br /> previous inspection, check that each alarm was documented and responded to appropriately, and attach a copy of <br /> the alarm history with documentation taken in response to any alarms to the inspection report. <br /> CORRECTIVE ACTION: Ensure that designated operators performing inspections at this facility are including all of <br /> the required information on the reports. <br /> This is a minor violation. <br /> FA0012355 PR0515864 SCO01 11/18/2019 <br /> EHD 23-01 Rev.9/20/2019 Page 5 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />