A J OA U I Environmental Health Department <br /> COUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> A&A GAS FOOD MART 1 1330 E YOSEMITE AVE, MANTECA November 18, 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 318 CCR 2666(c), 2643(c)(1) Leak detector failed to detect a 3.0 gallons per hour leak at 10 pounds per square inch. <br /> OBSERVATION: The 91 line leak detector failed to detect a leak when tested. <br /> REGULATION GUIDANCE: All line leak detectors shall be capable of detecting a 3-gallon per hour leak at 10 psi. <br /> CORRECTIVE ACTION: The leak detector was replaced and retested during the inspection. A"UST Retrofit <br /> Verification with Inspector Already Onsite"form has been completed and provided to the operator and contractor. <br /> This was corrected on site. <br /> This is a minor violation. <br /> Overall Inspection Comments: <br /> An inspection report was provided to the facility operator on the day of inspection. The report was amended by <br /> the EHD. The amended report replaces the initial report. Violations # 315, and 318 was corrected on site. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by December 21, 2019. <br /> Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate ($152). To schedule an <br /> appointment, please call (209) 468-3420. <br /> The following was observed during this inspection: <br /> -Liquid in under dispenser Containment (UDC) 1/2 and 9/10 <br /> Reviewed documents <br /> - Training Certificate <br /> -Alarm History <br /> -Monthly inspection reports <br /> The following was provided during this inspection: Schedule of free CU PA classes, [list everything that was <br /> provided, hard copies or via email] <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: Inspector: Inspector Phone: <br /> Printed Name and Title: PAUL NSO, EHS Trainee (209)468-3432 <br /> FA0012355 PR0515864 SCO01 11/18/2019 <br /> EHD 23-01 Rev.9/20/2019 Page 7 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />