Laserfiche WebLink
UNDERGROUND STORAGE TANK <br /> OVERFILL PREVENTION EQUIPMENT INSPECTION REPORT FORM (Page 1 of 1 ) <br /> Type of Action ❑ Installation Inspection ❑ Repair Inspection ❑x 36 Month Inspection <br /> I . FACILITY INFORMATION <br /> CERS ID Date of Overfill Prevention Equipment Inspection <br /> 10169781 10/5/2018 <br /> Business Name (Same as Facility Name or DBA-Doing Business As) <br /> Colonial Energy #40134 <br /> Business Site Address City ZIP Code <br /> 1434 W . Yosemite Ave Manteca 95337 <br /> II . UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION <br /> Name of UST Service Technician Performing the Inspection (Print as shown on the ICC Certification.) Phone # <br /> Nicholas C Janoe ( 916 ) 373 - 1166 <br /> Contractor / Tank Tester License # ICC Certification # ICC Certification Expiration Date <br /> 617238 8712764 4/ 11 /2019 <br /> Overfill Prevention Equipment Inspection Training and Certifications (List applicable certifications.) <br /> OPW <br /> III . OVERFILL PREVENTION EQUIPMENT INSPECTION INFORMATION <br /> Inspection Method ❑x Manufacturer Guidelines (Specify) : <br /> Used : OPW Install & Maintenance Guidelines <br /> ❑ Industry Code or Engineering Standard (Specify) : <br /> ❑ Engineered Method (Specify) : <br /> Attach the inspection procedures and all documentation required to determine the results. # of Attached Pages <br /> TANK ID : (By tank number, stored product, etc.) 87 Gasoline 91 Gasoline Diesel <br /> What is the tank inside diameter? (Inches) 953/4 11 953 /4 11 953/4 11 <br /> Is the fill piping secondarily contained ? ❑ Yes 0 No ❑ Yes IE No ❑ Yes ❑x No ❑ Yes ❑ No <br /> Is the vent piping secondarily contained ? ❑ Yes 0 No ❑ Yes 0 No ❑ Yes x❑ No ❑ Yes ❑ No <br /> Overfill Prevention Equipment Manufacturer(s) OPW OPW OPW <br /> What is the overfill prevention equipment response ❑ Shuts Off Flow ❑ Shuts Off Flow ❑ Shuts Off Flow ❑ Shuts Off Flow <br /> when activated ? ❑x Restricts Flow ❑x Restricts Flow IX1 Restricts Flow ❑ Restricts Flow <br /> (Check all that apply.) <br /> ❑ AN Alarm ❑ AN Alarm ❑ AN Alarm ❑ AN Alarm <br /> Are flow restrictors installed on vent piping ? ❑ Yes ❑ No ❑ Yes ❑ No ❑ Yes ❑ No ❑ Yes ❑ No <br /> At what level in the tank is the overfill prevention set <br /> to activate? (Inches from bottom of tank.) 863/8 863 /8 <br /> What is the percent capacity of the tank at which the <br /> overfill prevention equipment activates? 95 % 95 % <br /> Is the overfill prevention in proper operating condition ❑x Yes ❑x Yes ❑ Yes ❑ Yes <br /> to respond when the substance reaches the <br /> appropriate level? ❑ No (Specify in V.) ❑ No (Specify in V.) ❑ No (Specify in V.) ❑ No (Specify in V.) <br /> IV. SUMMARY OF INSPECTION RESULTS _ <br /> Overfill Prevention Inspection Results 9 Pass ❑ Fail 9 Pass ❑ Fail ❑ Pass 0 Fail ❑ Pass ❑ Fail <br /> V. COMMENTS <br /> Any items marked "Fail' must be explained in this section. Any additional comments may also be provided here. <br /> Unable to inspect the diesel drop tube due to the nipple and spill container being seized together. The bottom of the spill <br /> container was turning while trying to loosen the nipple . <br /> VI . CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS INSPECTION <br /> I hereby certify that the overfill prevention equipment was inspected in accordance with California Code of Regulations , Title 23 , <br /> Division 3 , Chapter 16 , Section 2637 .2 and all the information contained herein is accurate. <br /> UST Service Technician Signature , J. <br /> If the facility has more components than this form accomnlVdates, additional copies of this page may be attached. <br /> CERS = California Environmental Reporting System, ID = Identification, UST = Underground Storage Tank, ICC = Intemational Code Council, AA/ = Audible and Visual <br />